background image

RECEIVING

When  the  absorption  chiller  is  delivered  to 

the job site, inspect for any transit damage. Report

any damage to the carrier and note on the bill of

lading. Notify the Yazaki Sales Representative or

Distributor before proceeding with the installation

of a damaged unit.

UNIT NAMEPLATE

The  UNIT  NAMEPLATE  is  located  on  the

lower  right  hand  side  of  the  front  panel  on  each

absorption  chiller  unit. Check  that  the  model 

number,  flow  rates  and  electrical  specifications 

are  compatible  with  the  system  design  and 

services available.

RIGGING

Remove the crate from the absorption chiller.

When access is restricted, it may be necessary to

remove the skid to reduce overall height.

Each unit has four eye bolts in the top panel

which should be used for lifting.

Care  should  be  taken  at  all  times  during 

rigging  and  handling  of  the  absorption  chiller  to

avoid  damage  to  the  panels  and  external  pipe

connections. DO NOT DROP.

Attach a sling to the four eye bolts in the top

panel as shown in Fig.1 and ensure that the rope

angle is greater than 60

O

to the horizontal plane.

Always  carry  the  absorption  chiller  in  a  NEAR

VERTICAL POSITION. DO NOT TIP OVER.

The  dry  weight  and  overall  dimensions  are

shown in PHYSICAL DATA on Page 3 as a guide

for rigging (add 6 in. to overall height for skid).

When  moving  the  absorption  chiller,  check

that the route is accessible. The minimum access

dimensions for a skid mounted chiller are shown 

in Fig.2.

LOCATION

Yazaki  absorption  chillers  have  a  weather-

proof  cabinet  suitable  for  either  indoor  or  outdoor

installation.

Select  a  location  with  due  consideration  for

the  proximity  of  the  cooling  tower,  chilled/hot

water coils and service access.

The minimum space requirements, shown in

Fig.3, must be provided around and above each

chiller for installation and service access.

Fig. 1 RIGGING

MODEL

DIMENSION

WFC-SC10

WFC-SC20

WFC-SC30

WFC-SH10

WFC-SH20

WFC-SH30 

A

93 

98 

98 

B

63 

75 

88 

C

63 

75 

88 

D

63 

75 

88 

Fig. 2 ACCESS CLEARANCES (IN.)

The  roof  on  which  equipment  is  to  be 

installed  shall  be  capable  of  supporting  the 

operating  weight  of  the  absorption  chiller, 

associated  pumps,  cooling  tower  and  piping.

Install the equipment on a well drained surface of

the roof at least 6 ft. from the edge. If the roof is

poorly  drained  at  the  equipment  or  in  the 

passageway to the equipment a suitable platform

of  walkway  should  be  provided  adjacent  to  the

equipment  and  control  panels  so  that  it  can  be

serviced safely.

10

INSTALLATION

Содержание Aroace WFC-SC10

Страница 1: ...t medium hot water at 158o F to 203o F from a process cogeneration solar or other waste heat source CONTENTS INSTALLATION INSTRUCTIONS WFC SC10 20 30 WFC SH10 20 30 GENERAL Page STANDARD SPECIFICATION...

Страница 2: ...c a p a C 2 This equipment should only be installed by trained and qualified personnel who are familiar with absorption chillers All precautions in these instructions on tags and labels attached to t...

Страница 3: ...ms 6 Fuses 4 Installation Instructions 1 and Operating Instructions 1 MODEL DESIGNATION WFC Water Fired Single Effect Absorption Chiller Chiller Heater Model Selection SC Chiller SH Chiller Heater Coo...

Страница 4: ...tion Box 19 1 4 TOP 3 5 Field Wiring Junction Box 31 5 4 9 26 4 29 9 33 1 26 4 4 Eye Bolts For Lifting Mounting Plate 7 5 38 2 LEFT FRONT REAR 0 8 74 8 9 0 6 1 12 5 16 4 Cooling Water Outlet 2 NPT Coo...

Страница 5: ...tlet 2 1 2 NPT Cooling Water Absorber Inlet 2 1 2 NPT 3C Note Cooling Water Crossover Pipe Field Connections Shown In Are 3 Sweat Type L Copper 14 8 5 EQUIPMENT DIMENSIONS WFC SC30 SH30 All dimensions...

Страница 6: ...TYPICAL SYSTEM DESIGN SINGLE MODULE WFC SC10 SH10 WFC SC20 SH20 WFC SC30 SH30 6...

Страница 7: ...TYPICAL SYSTEM DESIGN MULTIPLE MODULES 2 X MODULES WFC SC20 SH20 WFC SC30 SH30 7...

Страница 8: ...CN2 TMC1 CPU CPU CPU S3 EGBON HM CM CHD CHE S4 S5 S6 S7 S8 S11S12 S13 S14 S3 S4 S5 S6 S7 S8 S11S12 S13 S14 CP TB2 CN 16 LTPV CIRCUIT LTVP FE P2E P1E CIR HIR IRS LS AC24V DCP ST2 IF1 IF2 MGC2 4 OUC 5 T...

Страница 9: ...ating status General fault alarm Additional interlock NC or NO Input control from temp switch 36 5 F ON 39 2 F OFF OPTIONAL CONTROL BOX CONNECTIONS TERMINAL DESCRIPTION REMARKS S1 S2 Heat medium suppl...

Страница 10: ...POSITION DO NOT TIP OVER The dry weight and overall dimensions are shown in PHYSICAL DATA on Page 3 as a guide for rigging add 6 in to overall height for skid When moving the absorption chiller check...

Страница 11: ...WFC SC30 SH30 FRONT WFC SC20 SH20 FRONT WFC SC20 SH20 A C FRONT WFC SC20 SH20 FRONT WFC SC10 SH10 D E F Mounting Plate Fig 3 INSTALLATION CLEARANCES IN 11 INSTALLATION AREA MODEL DIM IN No WFC A B 1...

Страница 12: ...ing water crossover piping CHILLED HOT WATER PIPING The chilled hot water piping contains chilled water during cooling operation and hot water during heating operation and must be adjustment plates sh...

Страница 13: ...pipe and interlock the switch with the absorption chiller controls refer to Optional Field Wiring Connections circuit should be filled with a glycol solution of adequate concentration to prevent freez...

Страница 14: ...d 3 way valve CWV will bypass cooling water to the sump whenever the cooling water inlet temperature is below 65O F Wherever possible install the cooling tower at the same level or above the absorptio...

Страница 15: ...on the left side of each unit Optional field wiring connections for accessories and alarms are provided in the should be drained from the chiller heater When the cooling water circuit is not drained...

Страница 16: ...ONLY Option 3 HEAT INPUT CONTROL BY HEAT MEDIUM BYPASS VALVE ONLY OPTIONAL COOLING WATER TEMPERATURE CONTROL With Cooling Water Valve Override OPTIONAL COOLING WATER TEMPERATURE CONTROL Without Cooli...

Страница 17: ...TDO for CWV STANDARD JUNCTION BOX CONNECTIONS TERMINAL DESCRIPTION REMARKS 3 P1D P1E Chilled hot water pump thermal overload 4 P2D P2E Cooling water pump thermal overload 5 FD FE Cooling tower fan th...

Страница 18: ...ls the cooling water temperature by cycling the cooling tower fan 4 A Limit Switch 3VOP installed on the heat medium bypass valve closes when the valve is open 5 Optional controls override the Cooling...

Страница 19: ...ONS TERMINAL DESCRIPTION REMARKS S1 S2 Heat medium RFH supply shutdown S9 S10 Auxiliary boiler BO 17 18 Input control EGON Heat available from temp switch 2 3 on CN Cooling Water flow Input control 11...

Страница 20: ...nnect within sight of and readily accessible to the equipment per Section 440 14 of the National Electrical Code DO NOT CLOSE THE DISCONNECT until approved by an Authorized Yazaki Service Provider CON...

Страница 21: ...t medium circuits may cause scal ing or corrosion if not correctly analyzed and maintained within the limits specified in Table 2 In some areas the water supply will contain minerals that cause scalin...

Страница 22: ...OT operate the chiller 5 Power supply available near the chiller for a vacuum pump D CONTROL WIRING 1 Motor contactors and manual controls installed for all external motors 2 Control wiring 24V AC ins...

Страница 23: ......

Страница 24: ...STEMS INC 701 E PLANO PARKWAY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web www yazakienergy com This symbol on the product s nameplate means i...

Отзывы: