background image

 

ROUTINE MAINTENANCE 

 

Routine 

maintenance 

should 

be 

provided  throughout  the  life  of  the 
equipment in order to ensure satisfactory 
operation and performance. 

During  the  warranty  period,  an  ASP 

must  be  engaged  to  provide  routine 
maintenance  at  the  beginning  of  each 
cooling  season 

(spring  changeover) 

and 

heating  season 

(fall  changeover)

.    When 

the  chiller-heater  is  used  for  process 
cooling  or  heavy  load  operation,  it  may 
be  necessary  to  schedule  additional 
service 

visits 

to 

evacuate 

non-

condensable  gasses  from  the  vacuum 
section. 

Be  aware  that  during  the  first  few 

months  of  operation,  non-condensable 
gases  may  accumulate  at  a  greater  rate 
than  expected  as  the  inhibitor  coating  in 
the unit finishes forming.  However, after 
approximately 3 months, the formation of 
non-condensable gases should decrease 
to the normal expected rates. 

Each  routine  maintenance  item  is 

covered  in  detail,  many  in  step-by-step 
detail,  in  Section  5  of  the  Service 
Manual.  What is provided here is a brief 
summary  of  what  the  Service  Manual 
covers.

 

EVACUATION OVERVIEW 

 

Arguably the most important aspect of 

maintenance  for  the  chiller-heater  is 
maintaining  a  proper  level  of  vacuum.  
Evacuation  is  performed  at  the  front  of 
the  machine.    The  evacuation  service 
valves are referred to as Service Valve A 

(upper) 

and  Service  Valve  B 

(lower)

.  

Refer to Fig.  4 for detail on where these 
valves are located at the front of the unit. 

The  evacuation  service  valves  are 

back-seating  access  valves  similar  to 
those  used  throughout  the  refrigeration 
industry.   The  stem  has  a  10mm  square 
head.    The  stem  secures  a  copper  seal 
to  a  steel  seat  inside  the  valve.    Do  not 
over-torque  this  valve  or  else  the  seal 
can  become  damaged  and  compromise 
vacuum integrity.   

Yazaki  offers  a  torque  wrench 

(P/N 

N7510)

 specifically for use with this service 

valve. 

A  number  of  precautions  should  be 

observed  at  all  times  during  evacuation.  
Key points are: 

 

***  Great  care  must  be  taken  to 

ensure  that  no  oil  enters  the  Yazaki 
chiller-heater!    Permanent  damage 
could result from even a small amount 
of  oil  being  introduced  into  the 
vacuum section! *** 

 

 

Never

  leave  a  vacuum  pump  running 

unattended.    Power  loss  could  allow 
the  chiller-heater  vacuum  section  to 
suck oil out of the pump in a matter of 
minutes. 

 

Never

  have  the  Service  Valve  open 

unless  the  vacuum  pump  is  running 
and  the  integrity  of  the  vacuum  lines 
between  the  valve  and  the  pump  has 
been verified as tight. 

 

Never

 

have 

the  vacuum 

pump 

discharge  tube  in  the  water  bucket 
unless  the  vacuum  pump  is  running.  
The  vacuum  pump  could  suck  water 
from  the  bucket  and  contaminate  the 
oil charge. 

 

Never

  pull  a  vacuum when  the  unit  is 

running  in  Heat  mode.    Only  pull  a 
vacuum in 

“Off” or “Cool” modes. 

Содержание AROACE CH-MG150

Страница 1: ...ty of this or any other equipment CONTENTS GENERAL Page ABSORPTION PRINCIPLE 2 COOLING OPERATION 3 HEATING OPERATION 4 CONTROLS GENERAL INFORMATION 5 CONTROL ADJUSTMENTS 8 CONTROL SEQUENCE 12 OPERATIO...

Страница 2: ...ING INSTRUCTIONS may affect the equipment performance and product Warranty If the equipment does not operate as expected check the Troubleshooting Guide in these instructions BEFORE calling your Yazak...

Страница 3: ...bundle The heat absorbed by the cooling water is rejected to a cooling tower or alternative system The liquid refrigerant that drips off the tubing bundle joins the liquid refrigerant that resulted f...

Страница 4: ...ed refrigerant vapor and leaving a more concentrated solution The refrigerant vapor flows through a changeover valve into the Evaporator section The concentrated solution flows through another changeo...

Страница 5: ...back to the same concentration level as when it started the cycle Absorber ABS Liquid refrigerant that condensed on the outer surface of the Evaporator tubing bundle drips into the Absorber sump Conce...

Страница 6: ...ed manner by Building Automation Systems BAS BMS when Remote Operation is engaged Additional controls and interlocks may be required in some instances These controls and their functions can be explain...

Страница 7: ...er has been set up at the factory and SHOULD NOT BE ADJUSTED Universal replacements are NOT recommended Only use OEM parts for the solution pump and controller Fig 5 Hitachi VFD Controller Control Pan...

Страница 8: ...control box for troubleshooting observe all safety warnings on the chiller heater and in these instructions Only qualified and trained personnel should have access to the live electrical parts inside...

Страница 9: ...tioned to the left whenever the unit is to be in normal operating condition Position this switch to the right when adjusting the burner Position this switch to the middle when the unit is to sit dorma...

Страница 10: ...ard CAT5 cable one was provided from the factory connect the ACT5 to the Main CPU Board located in the upper right of the control box There is a jack in the upper middle of the CPU Board See Figure 8...

Страница 11: ...board could result To engage Economy Mode close a circuit between TB1 75 and TB1 76 When that circuit is closed the Main CPU Board logic will automatically apply a modifier to the temperature set poi...

Страница 12: ...tant that the chiller heater have control over the pumps to allow for controlled shut down under normal and abnormal conditions Running the chilled water pump at all times is discouraged as the chille...

Страница 13: ...e Absorber and Condenser tubing bundles 4 When two or more absorption chiller heaters are installed in parallel set all units to the same operating mode HEATING 1 Select ON on the DIRECT OPERATION sec...

Страница 14: ...epare the unit for long term shutdown Without running in Heat mode some water will be trapped in upper portions of the chiller heater and could potentially damage the unit should it freeze in the wint...

Страница 15: ...lves are referred to as Service Valve A upper and Service Valve B lower Refer to Fig 4 for detail on where these valves are located at the front of the unit The evacuation service valves are back seat...

Страница 16: ...well on a vessel as large as the chiller heater vacuum section Just because the vacuum pump has stopped producing bubbles in the water bucket does NOT mean the vacuum level is adequate A digital vacu...

Страница 17: ...to help prevent potential tube damage during freezing conditions TROUBLESHOOTING SYMPTOM Chiller Heater does not operate Possible Cause REMEDY No High Voltage Check the LED for the Power indication o...

Страница 18: ...umn An O mark indicates the potential issue should this line item go out of acceptable range 2 When water temperature rises above 104 F 40 C the tendency for corrosion rises remarkably As such there m...

Страница 19: ...e GP sensor reads above 252 F 122 C in heating mode 27 Chilled water flow switch error Flow Switch FS1 is open when it should be closed 28 Cooling water flow switch error Optional cooling water Flow S...

Страница 20: ...EMS INC 701 E PLANO PKWY SUITE 305 PLANO TEXAS 75074 6700 Phone 469 229 5443 Fax 469 229 5448 Email yazaki yazakienergy com Web www yazakienergy com This symbol on the product s nameplate means it is...

Отзывы: