3

Terminals for Model (with bi-directional thyristor):

     

 

Terminals for Model:

 

ND/F/E-6701M, 6702M                                                        NG-6001, 6401, 6002,6302, 6402,

 

6011,6411,6012,6312,6412

 

 

 

 

 

 

 

 

         

 

 

   

 

                                           

Power supply voltage:                                                                                 
198 to 242 VAC (Including power supply voltage variation)(50Hz)                                                                                                                                                           
Control output rated: 
Relay contact output: 240 VAC, 3A(Resistive load)                                                       

Voltage output:0 to 12 VDC (Load resistance 600

Ω

  or more) 

 

3.3 Panel layoutl 

 

Measured value (PV)display unit (Red) 

Displays measured value (PV). 

 

Displays  various  characters  depending  on  the 

instrument. 

Set value (SV)display unit (Green) 

Displays set value (SV) 

 

Displays various each parameter set value depending 

on the instrument. 

Indicator 

 

Auto-tuning(AT)  Indicator  [Green].  Flashes  during 

auto-tuning execution. 
 

Control  output

OUT

indicator  [Green]  turned  on   

when outputs operate 

Alarm  output  indicator  (ALM)[Red]  turned  on  when 

output operate 

  Function key                                                                                                   

Used for displaying the change and confirm of the   

    Parameters 

⑤、⑥

Adjusting key to change the digital code and/or 

the key to express entering the auto-tuning state 
 

.  Used  for  adjusting  the  digital  code  displayed  or 

entering the auto-tuning state.

   

 
 
 
 
 
 
 

 
                                                         

 

 
4.1

 Sequence to pick up the functions of the instrument 

 

                                Power on 

 

        Upper row displays code

INP

),

lower Row   

          displays type No. 

Display input type

 

                                                                                       

          Upper row: Input high limit, lower row                                    Automatically turn over after 4 seconds displaying 

          input low limit(Display input Lange)                               

 

          Upper row displays process value, lower                          Automatically return over when not press any key over 1 minute 

            row displays set value(Standard mode) 

 

                                                    Press function key            Upper row displays setting code (SP,), lower row 

                                                                                              displays set value

Update the setting mode 

 

 

                                        Press function over 4 seconds    Upper row displays function code (AL

), Lower row displays 

                                                                                            control parameters

Changing the control parameters

 

 
Example

Input: Thermocouple E, 0~400

.When turn on power, display:

 

 

1

      

PV                                  PV 

            

                                                                                                                                             

 

        

SV                                  SV                       

(Standard display mode)

 

                                          

 

 
 
 
 

Code

 

InP 

Type

 

 

Input signal 

Type 

Range

(℃)

 

Type 

of 

input

  

 

Thermocouple 

0~600 

 

0~800 

PT100L 

 

RTD 

Pt100 

0~99.9 

PT100H 

 
 

Pt100 

-200~800 

Cu50 

Cu50 

0~99.9 

 

4.2 The detail description for every function   

If upper row displays 

OVER

 the sensor is in open circuit or the input signal excesses the range of measurement. 

The method for changing set value: 

Press 

 key the high row displays SP. Press

 or 

key

the low row displays the needed value. Again press 

 key, return 

to the standard display mode. 

The method for changing control parameter: 

Press 

 key over 4 seconds, the high row displays the parameter display code. Press 

 or 

 key the low row displays the   