Terminals for Model (with bi-directional thyristor):
⑷
Terminals for Model:
ND/F/E-6701M, 6702M NG-6001, 6401, 6002,6302, 6402,
6011,6411,6012,6312,6412
Power supply voltage:
198 to 242 VAC (Including power supply voltage variation)(50Hz)
Control output rated:
Relay contact output: 240 VAC, 3A(Resistive load)
Voltage output:0 to 12 VDC (Load resistance 600
Ω
or more)
3.3 Panel layoutl
①
Measured value (PV)display unit (Red)
•
Displays measured value (PV).
•
Displays various characters depending on the
instrument.
②
Set value (SV)display unit (Green)
•
Displays set value (SV)
•
Displays various each parameter set value depending
on the instrument.
③
Indicator
•
Auto-tuning(AT) Indicator [Green]. Flashes during
auto-tuning execution.
•
Control output
(
OUT
)
indicator [Green] turned on
when outputs operate
•
Alarm output indicator (ALM)[Red] turned on when
output operate
④
Function key
•
Used for displaying the change and confirm of the
Parameters
⑤、⑥
Adjusting key to change the digital code and/or
the key to express entering the auto-tuning state
•
. Used for adjusting the digital code displayed or
entering the auto-tuning state.
4.1
Sequence to pick up the functions of the instrument
Power on
Upper row displays code
(
INP
),
lower Row
displays type No.
(
Display input type
)
Upper row: Input high limit, lower row Automatically turn over after 4 seconds displaying
input low limit(Display input Lange)
Upper row displays process value, lower Automatically return over when not press any key over 1 minute
row displays set value(Standard mode)
Press function key Upper row displays setting code (SP,), lower row
displays set value
(
Update the setting mode
)
Press function over 4 seconds Upper row displays function code (AL
…
), Lower row displays
control parameters
(
Changing the control parameters
)
Example
:
Input: Thermocouple E, 0~400
.When turn on power, display:
℃
1
PV PV
SV SV
(Standard display mode)
Code
InP
Type
Input signal
Type
Range
(℃)
Type
of
input
1
E
Thermocouple
E
0~600
2
K
K
0~800
3
PT100L
RTD
Pt100
0~99.9
4
PT100H
Pt100
-200~800
5
Cu50
Cu50
0~99.9
4.2 The detail description for every function
If upper row displays
“
OVER
”
the sensor is in open circuit or the input signal excesses the range of measurement.
The method for changing set value:
Press
key the high row displays SP. Press
or
key
,
the low row displays the needed value. Again press
key, return
to the standard display mode.
The method for changing control parameter:
Press
key over 4 seconds, the high row displays the parameter display code. Press
or
key the low row displays the