1.7 H: Terminal Functions
H parameters assign functions to the external terminals.
u
H1: Multi-Function Digital Inputs
n
H1-01 to H1-08: Functions for Terminals S1 to S8
.
No.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to B2
40 (F)
<1>
: Forward Run Command (2-Wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to B2
41 (F)
<1>
: Reverse Run Command (2-Wire sequence)
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to B2
24: External Fault (N.O., always detected, coast to stop)
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to B2
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to B2
3 (0)
<1>
: Multi-Step Speed Reference 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to B2
4 (3)
<1>
: Multi-Step Speed Reference 2
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to B2
6 (4)
<1>
: Jog Reference Selection
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to B2
8: External Baseblock Command
<1> Number appearing in parenthesis is the default value after performing a 3-Wire initialization (A1-03 = 3330).
Table 1.31 Multi-Function Digital Input Terminal Settings
Setting
Function
Page
0
3-Wire Sequence
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
6
Jog reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Analog Terminal Input Selection
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer Function Input
19
PID Disable
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F External Fault
30
PID Integral Reset
31
PID Integral Hold
34
PID Soft Starter Cancel
35
PID Input Level Selection
40
Forward Run Command (2-Wire sequence)
41
Reverse Run Command (2-Wire sequence)
Setting
Function
Page
42
Run Command (2-Wire sequence 2)
43
FWD/REV Command (2-Wire sequence 2)
44
Offset Frequency 1
45
Offset Frequency 2
46
Offset Frequency 3
47
Node Setup
50
Motor Pre-Heat 2
51
Sequence Timer Disable
52
Sequence Timer Cancel
60
Motor Pre-Heat 1
61
External Speed Search Command 1
62
External Speed Search Command 2
63
Field Weakening
67
Communications Test Mode
69
Jog 2
6A
Drive Enabled
6D
AUTO Mode Select
6E
HAND Mode Select
70
Drive Enable2
A4
BP Emergency Override
A5
BP Drive/Bypass Selection
A6
BP BAS Interlock
A7
BP Customer Safeties
A8
PI2 Disable (N.O.)
A9
PI2 Disable (N.C.)
AA
PI2 Inverse Operation
AB
PI2 Integral Reset
AC
PI2 Integral Hold
AD
Select PI2 Parameters
1.7 H: Terminal Functions
78
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual