3.10 Control I/O Connections
u
Sinking/Sourcing Mode Switch for Digital Inputs
Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external power
supply for the digital inputs S1 to S7 as shown in
(Default: Sink mode, internal power supply).
NOTICE: Do not short terminals SP and SN. Failure to comply will damage the drive.
Table 3.12 Digital Input Sink/Source/External Power Supply Selection
Mode
Drive Internal Power Supply
(Terminals SN and SP)
External 24 Vdc Power Supply
Sinking Mode (NPN)
SC
S7
S6
24 Vdc
SP
SN
SC
S7
S6
24 Vdc
SP
SN
External
24 Vdc
Sourcing Mode (PNP)
SC
S7
S6
24 Vdc
SP
SN
SC
S7
S6
24 Vdc
SP
SN
External
24 Vdc
u
Input Signal Selection for Terminals A1 and A2
Terminals A1 and A2 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as
explained in
. Set parameters H3-01 and H3-09 accordingly as shown in
.
Note:
If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency
reference.
Table 3.13 Jumper S1 Settings
Terminal
Voltage Output
Current Output
Terminal A1
A2
A1
V
I
A2
A1
V
I
Terminal A2
A2
A1
V
I
A2
A1
V
I
3.10 Control I/O Connections
100