Parameter overview
Operating parameters
Description
Assignment
Output format
Here specify the range of values for the output. The CPU
hereby determines the pulse duration:
n
Per mil
–
Output value is within 0 ... 1000
–
Pulse duration = (Output value / 1000) x period
duration
n
S7 Analog value:
–
Output value is Siemens S7 analog value 0 ...
27648
–
Pulse duration = (Output value / 27648) x period
duration
Per mil
Time base
Here you can set the time base, which will apply for resolu-
tion and range of values of the period duration, minimum
pulse duration and on-delay.
n
1ms: The time base is 1ms
n
0.1ms: Time base is 0.1ms
0.1ms
On-delay
This parameter is ignored.
0
Period duration
With
period duration
you define the length of the output
sequence, which consists of pulse duration and pulse
pause.
Range of values:
Time base 1ms: 1 ... 87ms
Time base 0.1ms: 0.4 ... 87.0ms
50*
Minimum pulse duration
With the
minimum pulse duration
you can suppress short
output pulses and short pulse pauses. All pulses or
pauses, which are smaller than the
minimum pulse dura-
tion
, are suppressed. This allows you to filter very short
pulses (spikes), which can not be recognized by the
periphery.
Range of values:
Time base 1ms: 0 ... Period duration / 2 * 1ms
Time base 0.1ms: 2 ... Period duration / 2 * 0.1ms
2
*) This value can vary depending on the configuration tool and can be out of range. Values, which are out of range are invalid and must be adjusted accordingly!
5.9.5 Status indication
Digital output
LED
green
Description
DO +0.0
Pulse train 0 has "1" signal
Pulse train 0 has "0" signal
DO +0.1
Pulse train 1 has "1" signal
Pulse train 1 has "0" signal
VIPA System MICRO
Deployment I/O periphery
Pulse train > Status indication
HB400 | CPU | M13-CCF0000 | en | 18-50
154