3
Deployment
3.1 Installation
The cloudPanel is suitable for the installation in operating tables and control cabinet
fronts. The installation happens via the backside. The cloudPanel is provided with a fixing
technique that allows an easy connection with a crosstip screwdriver. A fast and easy
device change is possible.
For the installation into a operating tableau and control cabinet fronts, the cloudPanel
requires the following front plate cutting:
cloudPanel
A x B in mm
HA1-L1A41-0
271 x 186 mm
To fix the cloudPanel mounting clips are included. For the installation a small crosstip
screwdriver is required.
1.
Push the cloudPanel [3] from the front side into the front panel cutting [1] until it
touches the panel with the seal [2].
2.
Put the mounting clips [4] on all four sides of the cloudPanel into the openings. The
screws should point in the direction of the front panel.
3.
Screw the screws from the other side with the crosstip screwdriver [5].
n
For the cabling of the DC 24V power supply (18 ... 32 VDC) a black plug is included.
The connector is a plug with screw contacts. The associated label is located on the
back of the cloudPanel.
n
The cloudPanel must always be grounded to earth. Grounding helps limit the effects
of noise due to electromagnetic interference.
n
Use the power supply terminal marked with
for grounding.
n
The power supply circuit may be floating or grounded. In the latter case, connect to
the ground the power supply as shown in figure with a dashed line.
n
When using the floating power scheme, note that the cloudPanel internally connects
the power to the ground with a 1MΩ resistor in parallel with a 4.7nF capacitor.
Overview
Installation cutting
Installation
Connect power supply
VIPA HMI
Deployment
Installation
HB160 | TP-cloud | HA1-L1A41-0 | en | 18-02