10 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC
SIEP C730600 24A V1000 Option CANopen Technical Manual
29
002CH
Drive Status 2
bit 0
During Run
bit 1
Zero Speed
bit 2
Speed Agree
bit 3
User Speed Agree
bit 4
Frequency Detection 1
bit 5
Frequency Detection 2
bit 6
Drive Ready
bit 7
During Undervoltage
bit 8
During Baseblock
bit 9
Frequency Reference from Operator Keypad
bit A
Run Command from Operator Keypad
bit B
Over/Undertorque 1, 2
bit C
Frequency Reference Loss
bit D
During Fault Restart
bit E
Fault
bit F
Communication Timeout
002DH
Output Terminal Status
bit 0
Multi-Function Contact Output (terminal MA/MB-MC)
bit 1
Multi-Function Photocoupler Output 1 (terminal P1 - PC)
bit 2
Multi-Function Photocoupler Output 2 (terminal P2 - PC)
bit 3 - 6
Reserved
bit 7
Fault Contact (terminal MA/MB-MC)
bit 8 to bit F
Reserved
002EH Reserved
002FH
Frequency Reference Bias (from Up/ Down 2 Function), 0.1% units
0030H
Reserved
0031H
DC Bus Voltage, 1 V units
0032H
Torque Monitor, 1% units
0033H
Reserved
0034H
Product Code 1 [ASCII], Product Type (V0 for V1000)
0035H
Product Code 2 [ASCII], Region Code
0036H to 0037H
Reserved
0038H
PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H
PID Input, 0.1% units, signed, 100% / max. output frequency
003AH
PID Output, 0.1% units, signed, 100% / max. output frequency
003B to 003CH
Reserved
003DH
Communications Error Contents
bit 0
CRC Error
bit 1
Data Length Error
bit 2
Reserved
bit 3
Parity Error
bit 4
Overrun Error
bit 5
Framing Error
bit 6
Timeout
bit 7 to bit F
Reserved
003EH
Output Frequency
r/min
003FH
0.01% units
0040H to 004AH
Used for various monitors U1-
.
004BH
Drive status (U1-12)
bit 0
During Run
bit 1
During Zero Speed
bit 2
During Reverse Run
bit 3
During Fault Reset Signal Input
bit 4
During Speed Agree
bit 5
Drive Ready
bit 6
Alarm
bit 7
Fault
bit 8
During Operation Error (oPE
)
bit 9
During Momentary Power Loss
bit A
Motor 2 selected
bit B
Reserved
bit E
ComRef status, NetRef status
bit F
ComCtrl status, NetCtrl status
004CH to 007E
Used for various monitors U1-
, U4-
, U5-
and U6-
.
007FH
Alarm Code, refer to
Alarm Register Contents on page 33
for alarm codes.
0080H to 0097H
Used for monitors U2-
, U3-
. Refer to
Fault Trace / History Register Contents on page 32
for register value descriptions.
0098H
High Word of Accumulated Operation Time Monitor (U4-01)
0099H
Low Word of Accumulated Operation Time Monitor (U4-01)
009AH
High Word of Cooling Fan Operation Time Monitor (U4-03)
009BH
Low Word of Cooling Fan Operation Time Monitor (U4-03)
00ABH
Drive Rated Current