![YASKAWA U1000 Series Скачать руководство пользователя страница 560](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114560.webp)
560
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
C.3 Connecting to a Network
C.3 Connecting to a Network
This section explains how to connect the drive to a MEMOBUS/Modbus network and the network termination required.
◆
Network Cable Connection
Follow the instructions below to connect the drive to a MEMOBUS/Modbus network.
1.
With the power shut off, connect the communications cable to the drive and the master. Use terminals TB5 for
MEMOBUS/Modbus.
Figure C.2
Figure C.2 Serial Communications Cable Connection Terminals (TB5)
Note:
Separate the communications cables from the main circuit cables and other wiring and power cables. Use shielded cables for the
communications cables, and properly shielded clamps to prevent problems with noise. When using RS-485 communications,
connect S+ to R+, and S- to R- as shown in the diagram below.
2.
Check or set the termination resistor selection at all slaves. Use the description in
for slaves that are U1000 drives.
3.
Switch the power on.
4.
Set the parameters needed for serial communications (H5-01 through H5-12) using the digital operator.
5.
Shut the power off and wait until the display on the digital operator goes out completely.
6.
Turn the power back on.
7.
The drive is now ready to begin communicating with the master.
◆
Wiring Diagram for Multiple Connection
explain the wiring diagrams for multiple connections using MEMOBUS/Modbus
communication.
■
RS-485 Interface
Figure C.3
Figure C.3 RS-485 Interface
(TB5)
S-
S+
R-
R+
IG
Send (-)
Send (+)
Receive (-)
Receive (+)
Shield Ground
U1000
U1000
U1000
S2
S2
S2
S–
S+
R–
R+
IG
S–
S+
R–
R+
IG
S–
S+
R–
R+
IG
R–
R+
S–
S+
IG
PLC
OFF
OFF
ON
SIEP_C710636_02B_1_0.book 560 ページ 2015年11月25日 水曜日 午後4時56分