B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
519
t
B
◆
q: DriveWorksEZ Parameters
◆
r: DriveWorksEZ Connection Parameters
◆
T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance
■
T1: Induction Motor Auto-Tuning
o4-07
(523H)
DC Bus Pre-Charge Relay
Maintenance Setting
Sets the value of the Maintenance Monitor for the soft charge bypass relay. See U4-06 to check
when the bypass relay may need to be replaced.
Default: 0%
Min: 0%
Max: 150%
o4-11
(510H)
U2, U3 Initialization
0: U2-
and U3-
monitor data is not reset when the drive is initialized (A1-03).
1: U2-
and U3-
monitor data is reset when the drive is initialized (A1-03). (The value
of o4-11 is automatically returned to 0.)
Default: 0
Min: 0
Max: 1
o4-12
(512H)
kWh Monitor Initialization
0: No action
1: Reset kWh data (The value of o4-12 is automatically returned to 0.)
Default: 0
Min: 0
Max: 1
o4-13
(528H)
Number of Run Commands
Counter Initialization
0: U4-02 monitor data is not reset when the drive is initialized (A1-03).
1: U4-02 monitor data is reset when the drive is initialized (A1-03). (The value of o4-13 is
automatically returned to 0.)
Default: 0
Min: 0
Max: 1
o4-19
(113AH)
Power Unit Price
Sets the energy price per 1 kWh. This parameter is used to calculate the power rate displayed for
total consumed power (U9-07 to U9-10) and total regenerated power (U9-11 to U9-14).
Default: 000.00
Min: 000.00
Max: 650.00
No. (Addr.)
Name
Description
Setting
Page
q1-01 to
q6-07
(1600H to
1746H)
DriveWorksEZ Parameters
Reserved for DriveWorksEZ
Refer to Help in the
DWEZ software.
No. (Addr.)
Name
Description
Setting
Page
r1-01 to
r1-40
(1840H to
1867H)
DriveWorksEZ Connection
Parameters 1 to 20 (upper/lower)
DriveWorksEZ Connection Parameters 1 to 20 (upper/lower)
Default: 0
Min: 0
Max: FFFFH
No. (Addr.)
Name
Description
Setting
Page
T1-00
(700H)
Motor 1/Motor 2 Selection
1: Motor 1 (sets E1-
, E2-
)
2: Motor 2 (sets E3-
, E4-
)
Default: 1
Min: 1
Max: 2
T1-01
(701H)
Auto-Tuning Mode Selection
0: Rotational Auto-Tuning
2: Stationary Auto-Tuning for Line-to-Line Resistance
3: Rotational Auto-Tuning for V/f Control (necessary for Energy Savings and Speed Estimation
Speed Search)
4: Stationary Auto-Tuning 2
5: Stationary Auto-Tuning 3
8: Inertia Tuning (perform Rotational Auto-Tuning prior to Inertia Tuning)
9: ASR Gain Tuning (perform Rotational Auto-Tuning prior to ASR Gain Auto-Tuning)
Note:
Inertia Tuning and ASR Gain Auto-Tuning might not be available if gears are between
the machine and the motor shaft.
Default: 0
Min: 0
Max: 4, 5, 8, 9
T1-02
(702H)
Motor Rated Power
Sets the motor rated power as specified on the motor nameplate.
Default:
Min: 0.00 kW
Max: 650.00 kW
T1-03
(703H)
Motor Rated Voltage
Sets the motor rated voltage as specified on the motor nameplate.
Default: 200.0 V
Min: 0.0 V
Max: 255.0 V
No. (Addr.)
Name
Description
Setting
Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
SIEP_C710636_02B_1_0.book 519 ページ 2015年11月25日 水曜日 午後4時56分