harmonic filter module during installation. Remove the temporary cover before startup, as the cover will reduce ventilation and cause
the harmonic filter module to overheat.
◆
Installation Orientation and Spacing
Install the drive upright as illustrated in
to maintain proper cooling.
Figure 2.1
Figure 2.1 Correct Installation Orientation
■
Single Drive Installation
and
show the installation distance required to maintain sufficient space for airflow and wiring.
CIMR-U
2
0028 to 2
0248, 4
0011 to 4
0590
Figure 2.2
Figure 2.2 Correct Installation Spacing
Note:
IP20/NEMA 1, UL Type 1 enclosure and IP00 enclosure models require the same amount of space above and below the drive for
installation.
CIMR-U
4
0720 to 4
0930 and Harmonic Filter Module
Figure 2.3
Figure 2.3 Correct Installation Spacing (CIMR-U
4
0720A and Harmonic Filter Module)
A – 50 mm minimum
D – 120 mm minimum
B – 30 mm minimum
E – Airflow direction
C – 200 mm minimum
A – 50 mm minimum
D – 120 mm minimum
B – 30 mm minimum
E – 60 mm minimum
C – 200 mm minimum
F – Airflow direction
A
C
A
B
B
D
E
Side Clearance
Top/Bottom Clearance
Side Clearance
Top/Bottom Clearance
A
A
C
B
B
E
D
F
CIMR-U
4
0720A
Harmonic
Filter Module