![YASKAWA U1000 Series Скачать руководство пользователя страница 487](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114487.webp)
B.3 Parameter Table
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
487
t
B
■
E5: PM Motor Settings
E4-05
(325H)
Motor 2 Line-to-Line Resistance
Sets the phase-to-phase resistance for motor 2. Automatically set during Auto-Tuning.
Default:
Min: 0.000
Ω
Max: 65.000
Ω
E4-06
(326H)
Motor 2 Leakage Inductance
Sets the voltage drop for motor 2 due to motor leakage inductance as a percentage of rated
voltage. Automatically set during Auto-Tuning.
Default:
Min: 0.0%
Max: 40.0%
E4-07
(343H)
Motor 2 Motor Iron-Core
Saturation Coefficient 1
Set to the motor iron saturation coefficient at 50% of magnetic flux for motor 2. Automatically
set during Auto-Tuning.
Default: 0.50
Min: 0.00
Max: 0.50
E4-08
(344H)
Motor 2 Motor Iron-Core
Saturation Coefficient 2
Set to the motor iron saturation coefficient at 75% of magnetic flux for motor 2. This value is
automatically set during Auto-Tuning.
Default: 0.75
Min: E4-07
Max: 0.75
E4-09
(33FH)
Motor 2 Mechanical Loss
There is normally no need to change this parameter from the default value.
Sets the motor mechanical loss for motor 2 as a percentage of motor rated power (kW).
Default: 0.0%
Min: 0.0%
Max: 10.0%
E4-10
(340H)
Motor 2 Iron Loss
Sets the motor iron loss.
Default:
Min: 0 W
Max: 65535 W
E4-11
(327H)
Motor 2 Rated Power
Sets the motor rated capacity in kW. Automatically set during Auto-Tuning.
Default:
Min: 0.00 kW
Max: 650.00 kW
<9> Default setting value is dependent on the drive model (o2-04) and the Drive Duty (C6-01).
<72> Display is in the following units.
CIMR-U
2
0028, 2
0042, and 4
0011 to 4
0027: 0.01 A units
CIMR-U
2
0054 to 2
0248, and 4
0034 to 4
0930: 0.1 A units
No.(Addr.)
Name
Description
Setting
Page
E5-01
(329H)
Motor Code Selection
(for PM Motors)
Enter the Yaskawa motor code for the PM motor being used. Various motor parameters are
automatically set based on the value of this parameter. Setting that were changed manually will
be overwritten by the defaults of the selected motor code.
Note1.
Set to FFFF when using a non-Yaskawa PM motor or a special motor.
2.
If an alarm or hunting occurs even though a motor code is used, enter the value indicated
on the nameplate. For more details, refer to
Auto-Tuning for Permanent Magnet
.
Default:
Min: 0000
Max: FFFF
E5-02
(32AH)
Motor Rated Power
(for PM Motors)
Sets the rated capacity of the motor.
Default:
Min: 0.10 kW
Max: 650.00 kW
E5-03
(32BH)
Motor Rated Current
(for PM Motors)
Sets the motor rated current.
Default:
Min: 10% of drive rated
current
Max: 150% of drive
rated current
E5-04
(32CH)
Number of Motor Poles
(for PM Motors)
Sets the number of motor poles.
Default:
Min: 2
Max: 48
E5-05
(32DH)
Motor Stator Resistance (r1)
(for PM Motors)
Set the resistance for each motor phase.
Default:
Min: 0.000
Ω
Max: 65.000
Ω
E5-06
(32EH)
Motor d-Axis Inductance (Ld)
(for PM Motors)
Sets the d-axis inductance for the PM motor.
Default:
Min: 0.00 mH
Max: 300.00 mH
No.(Addr.)
Name
Description
Setting
Page
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
SIEP_C710636_02B_1_0.book 487 ページ 2015年11月25日 水曜日 午後4時56分