A.4 Drive Specifications
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
457
Sp
eci
fi
cat
ions
A
A.4 Drive Specifications
Note: 1.
Perform rotational Auto-Tuning to obtain the performance specifications given below.
2.
For optimum performance life of the drive, install the drive in an environment that meets the required specifications.
Item
<1> Current derating is required. Select control modes in accordance with the drive capacity.
Specification
Control
Characteristics
Control Method
The following control methods can be set using drive parameters:
• V/f Control (V/f)
• V/f Control with PG (V/f w/PG)
• Open Loop Vector Control (OLV)
• Closed Loop Vector Control (CLV)
• Open Loop Vector Control for PM (OLV/PM)
• Advanced Open Loop Vector Control for PM (AOLV/PM)
• Closed Loop Vector Control for PM (CLV/PM)
Frequency Control Range
0.01 to 400 Hz
Frequency Accuracy
(Temperature Fluctuation)
Digital input: within ±0.01% of the max output frequency (-10°C to +40°C)
Analog input: within ±0.1% of the max output frequency (25°C ±10°C)
Frequency Setting Resolution
Digital inputs: 0.01 Hz
Analog inputs: 1/2048 of the maximum output frequency setting (11 bit plus sign)
Output Frequency Resolution
0.001 Hz
Frequency Setting Signal
Main speed frequency reference: DC -10 to +10 V (20 k
Ω
), DC 0 to +10 V (20 k
Ω
), 4 to 20 mA (250
Ω
),
0 to 20 mA (250
Ω
), Main speed reference: Pulse train input (max. 32 kHz)
Starting Torque
V/f, V/f w/PG: 150% at 3 Hz
OLV: 200% at 0.3 Hz
CLV, AOLV/PM, CLV/PM: 200% at 0.0 min
-1
OLV/PM: 100% at 3 Hz
Speed Control Range
V/f, V/f w/PG: 1:40
OLV: 1:200
CLV, CLV/PM: 1:1500
OLV/PM: 1:20
AOLV/PM: 1:100
Speed Control Accuracy
OLV:
±
0.2% (25°C ±10°C), CLV:
±
0.02% (25°C ±10°C)
Speed Response
OLV: 10 Hz (25°C ±10°C)
CLV: 250 Hz (25°C ±10°C)
Torque Limit
Parameters setting allow separate limits in four quadrants (available in OLV, CLV, AOLV/PM, CLV/PM)
Accel/Decel Time
0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)
Braking Torque
Same value as overload tolerance
V/f Characteristics
User-selected programs and V/f preset patterns possible
Main Control Functions
Torque Control, Droop Control, Speed/torque Control Switching, Feed Forward Control, Zero Servo Function, Momentary
Power Loss Ride-Thru, Speed Search, Synchronous Transfer with Commercial Power Supply, Overtorque/Undertorque
Detection, Torque Limit, 17 Step Speed (max), Accel/decel Switch, S-curve Accel/decel, 3-wire Sequence, Auto-tuning
(rotational, stationary tuning), Dwell, Cooling Fan on/off Switch, Slip Compensation, Torque Compensation, Frequency
Jump, Upper/lower Limits for Frequency Reference, DC Injection Braking at Start and Stop, PID Control (with sleep
function), Energy Saving Control, MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), Fault Restart,
Application Presets, DriveWorksEZ (customized function), Removable Terminal Block with Parameter Backup Function,
Online Tuning, Overexcitation Deceleration, Inertia (ASR) Tuning, High Frequency Injection, etc.
Protection
Functions
Power Supply Regeneration
Available
Motor Protection
Electronic thermal overload relay
Momentary Overcurrent Protection
Drive stops when output current reaches about 200% of the rated current
Overload Protection
Drive stops after 60 s at 150% of rated Heavy Duty output current
Overvoltage Protection
200 V class: Stops when input voltage exceeds approx. 315 V
400 V class: Stops when input voltage exceeds approx. 630 V
Undervoltage Protection
200 V class: Stops when input voltage falls below approx. 150 V
400 V class: Stops when input voltage falls below approx. 300 V
Momentary Power Loss Ride-Thru
Immediately stop after 2 ms or longer power loss.
Continuous operation during power loss than 2 s (standard)
Heatsink Overheat Protection
Thermistor
Stall Prevention
Stall Prevention is available during acceleration, deceleration, and during run.
Ground Protection
Electronic circuit protection
Charge LED of Capacitor for Control
Power Supply
Remains lit until control power supply voltage falls below 50 V
Environment
Area of Use
Indoors
Ambient Temperature
-10 to 40
°
C (IP20/NEMA 1, UL Type 1 enclosure)
-10 to 50
°
C (IP00 enclosure)
Humidity
95 RH% or less (no condensation)
Storage Temperature
-
20°C to 60
°
C (short-term temperature during transportation)
Altitude
Up to 1000 meters
Vibration/Shock
10 to 20 Hz: 9.8 m/s
2
(2
0028 to 2
0248, 4
0011 to 4
0414)
10 to 20 Hz: 5.9 m/s
2
(4
0477 to 4
0930)
20 to 55 Hz: 5.9 m/s
2
(2
0028 to 2
0081, 4
0011 to 4
0077)
20 to 55 Hz: 2.0 m/s
2
(2
0104 to 2
0248, 4
0096 to 4
0930)
Standards
• UL508C
• IEC/EN 61800-3, IEC/EN 61800-5-1
• EN ISO 13849-1 Cat.3 PLe, IEC/EN 61508 SIL3
Protection Design
IP00 enclosure, IP20/NEMA 1, UL Type 1 enclosure