![YASKAWA U1000 Series Скачать руководство пользователя страница 455](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114455.webp)
A.2 Three-Phase 200 V Class Drives
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
455
Sp
eci
fi
cat
ions
A
A.2 Three-Phase 200 V Class Drives
Table A.2 Power Ratings (Three-Phase 200 V Class)
Item
<1> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<2> Rated input capacity is calculated with a power line voltage of 240 V
×
1.1.
<3> The rated output current of the drive output amps should be equal to or greater than the motor rated current.
<4> Carrier frequency is set to 4 kHz. Current derating is required in order to raise the carrier frequency.
<5> If the harmonic current distortion is needed to be 5% or less, the maximum output voltage will be the equivalent to the input voltage
×
0.87.
C7-60 (Output Voltage Limit Mode Selection) is needed to be changed from the default setting.
<6> User-adjustable
Specification
CIMR-U
2
0028
0042
0054
0068
0081
0104
0130
0154
0192
0248
Input/
Output
Rating
Input Current (A)
HD Rating
20
25
38
49
62
74
95
118
140
175
ND Rating
25
38
49
62
74
95
118
140
175
226
Rated Input Capacity (kVA)
HD Rating
9
12
17
22
28
34
43
54
64
80
ND Rating
12
17
22
28
34
43
54
64
80
103
Rated Output Current (A)
HD Rating
22
28
42
54
68
81
104
130
154
192
ND Rating
28
42
54
68
81
104
130
154
192
248
Overload Tolerance
HD Rating: 150% of rated output current for 60 s
ND Rating: 120% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency
4 kHz (User adjustable up to 10 kHz. Derating may be required.)
Maximum Output Voltage (V)
Proportional to input voltage
Maximum Output Frequency (Hz)
400 Hz
Power
Supply
Rated Voltage Rated Frequency
Three-phase 200 to 240 Vac 50/60 Hz
Allowable Voltage Fluctuation
-15 to 10%
Allowable Frequency Fluctuation
±
3% (Frequency fluctuation rate: 1 Hz/100 ms or less)
Allowable Phase Power Supply Voltage Unbalance
2% or less
Harmonic Current Harmonic Distortion
5% or less (IEEE519 compliant)
Input Power Factor
0.98% or more (During rated operation)
SIEP_C710636_02B_1_0.book 455 ページ 2015年11月25日 水曜日 午後4時56分