![YASKAWA U1000 Series Скачать руководство пользователя страница 394](http://html.mh-extra.com/html/yaskawa/u1000-series/u1000-series_technical-manual_907114394.webp)
394
YASKAWA ELECTRIC
SIEP C710636 02B YASKAWA U1000 Technical Manual
7.2 Inspection
7.2 Inspection
Power electronics have limited life and may exhibit changes in characteristics or performance deterioration after years of
use under normal conditions. To help avoid such problems, it is important to perform preventive maintenance and
periodic inspection on the drive.
Drives contain a variety of power electronics such as power transistors, semiconductors, capacitors, resistors, fans, and
relays. The electronics in the drive serve a critical role in maintaining proper motor control.
Follow the inspection lists provided in this chapter as a part of a regular maintenance program.
Note:
The drive will require more frequent inspection if it is placed in harsh environments, such as:
High ambient temperatures
Frequent starting and stopping
Fluctuations in the AC supply or load
Excessive vibrations or shock loading
Dust, metal dust, salt, sulfuric acid, chlorine atmospheres
Poor storage conditions.
Perform the first equipment inspection one to two years after installation.
◆
Recommended Daily Inspection
outlines the recommended daily inspection for Yaskawa drives. Check the following items on a daily basis to
avoid premature deterioration in performance or product failure. Copy this checklist and mark the “Checked” column
after each inspection.
Table 7.1 General Recommended Daily Inspection Checklist
Inspection Category
Inspection Points
Corrective Action
Checked
Motor
Inspect for abnormal oscillation or noise coming from the motor.
• Check the load coupling.
• Measure motor vibration.
• Tighten all loose components.
Cooling
Inspect for abnormal heat generated from the drive or motor and
visible discoloration.
• Check for excessive load.
• Loose connections
• Check for dirty heatsink or motor.
• Ambient temperature
Inspect drive cooling fan and circulation fan operation.
• Check for clogged or dirty fan.
• Check fan operation drive parameter.
Environment
Verify the drive environment complies with the specifications listed
in
Installation Environment on page 50
• Eliminate the source of contaminants or correct poor
environment.
Load
The drive output current should not be higher than the motor or drive
rating for an extended period of time.
• Check for excessive load.
• Check the motor parameter settings of the drive.
Power Supply Voltage
Check main power supply and control voltages.
• Correct the voltage or power supply to within nameplate
specifications.
• Verify all main circuit phases.
SIEP_C710636_02B_1_0.book 394 ページ 2015年11月25日 水曜日 午後4時56分