Setting 0: Disabled
Setting 1: Enabled
■
C3-21: Motor 2 Slip Compensation Gain
Used to improve speed accuracy for motor 2. Functions in the same way that C3-01 functions for motor 1.
Adjust this parameter only after the motor 2 rated current (E4-01), motor 2 rated slip (E4-02), and the motor 2 no-load
current (E4-03) have all been set.
C3-01: Slip Compensation Gain on page 218
for details on adjusting this parameter.
Note:
Default setting is 0.0 in V/f Control (E3-01 = 0). Default setting is 1.0 in Open Loop Vector Control (E3-01 = 2) and Closed Loop
Vector Control (E3-01 = 3). In Closed Loop Vector Control, slip compensation gain acts as an adaptable gain.
■
C3-22: Motor 2 Slip Compensation Primary Delay Time
Functions for motor 2 in the same way that C3-02 functions for motor 1.
C3-02: Slip Compensation Primary Delay Time on page 219
for instructions on how to adjust this parameter.
Note:
The default for V/f Control (E3-01 = 0) is 2000 ms. The default for Open Loop Vector Control (E3-01 = 2) is 200 ms.
■
C3-23: Motor 2 Slip Compensation Limit
Sets the upper limit for the slip compensation function as a percentage of the motor rated slip (E4-02).
The slip compensation limit is constant throughout the constant torque range (frequency reference
≤
E3-06). In the
constant power range (frequency reference
>
E3-06), it is increased based on C3-23 and the output frequency as shown in
.
Figure 5.35
Figure 5.35 Slip Compensation Limit
■
C3-24: Motor 2 Slip Compensation Selection during Regeneration
Functions for motor 2 in the same way that C3-04 functions for motor 1.
Setting 0: Disabled
Setting 1: Enabled (6 Hz and above)
Setting 2: Enabled (compensation provided wherever possible)
No.
Parameter Name
Setting Range
Default
C3-05
Output Voltage Limit Operation Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
C3-21
Motor 2 Slip Compensation Gain
0.0 to 2.5
Determined by E3-01
No.
Parameter Name
Setting Range
Default
C3-22
Motor 2 Slip Compensation Primary Delay Time
0 to 10000 ms
Determined by E3-01
No.
Parameter Name
Setting Range
Default
C3-23
Motor 2 Slip Compensation Limit
0 to 250%
200%
No.
Parameter Name
Setting Range
Default
C3-24
Motor 2 Slip Compensation Selection during Regeneration
0 to 2
0
E3-04
E3-06
×
C3-23
C3-23
E3-04
Maximum Output
Frequency
E3-06
Base
Frequency
Output Frequency