4.6 Application Selection
4.6 Application Selection
Several Application Presets are available to facilitate drive setup for commonly used applications. Selecting one of these
Application Presets automatically assigns functions to the input and output terminals, and sets certain parameters to
values appropriate for the application that was selected. In addition, the parameters most likely to be changed are
assigned to the group of User Parameters, A2-01 through A2-16. User Parameters are part of the Setup Group, and
provide quicker access to by eliminating the need to scroll through multiple menus.
An Application Preset can either be selected from the Application Selection display in the Setup Group (
Simplified Setup Using the Setup Group on page 141
) or in parameter A1-06. The following presets can be selected:
Note: 1.
An Application Preset can only be selected if all drive parameters are on at their original default settings. It may be necessary to
initialize the drive by setting A1-03 to “2220” or “3330” prior to selecting an Application Preset.
2.
Do not set any value outside the allowable range for A1-06 (Application Presets). If an out-of-range value is set, “APPL” will be
displayed flashing in the Setup group and the up and down arrow keys cannot be used. If this happens, press the ESC key to return to
the Setup group. It will then be possible to switch to another mode using the up and down arrow keys. Setting the values to A1-06 out
of the setting range will not affect the operation of the drive.
3.
The values set for A1-06 cannot be changed except by initializing the values by setting A1-03=2220, and then making new settings.
If you will encounter a problem if all of the parameters are initialized, the setting of A1-06 does not need to be changed.
WARNING!
Confirm the drive I/O signals and external sequence before performing a test run. Setting parameter A1-06 may change
the I/O terminal function automatically from the default setting. Failure to comply may result in death or serious injury.
Table 4.5 Application Preset (A1-06)
◆
Setting 1: Water Supply Pump Application
Table 4.6 Water Supply Pump: Parameter Settings
Table 4.7 Water Supply Pump: User Parameters (A2-01 to A2-16)
No.
Parameter Name
Setting Range
Default
A1-06
Application Preset
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC fan
5: Air compressor
6: Hoist
7: Crane (Traveling)
0
No.
<1> Values shown here are for 200 V class drives. Double values when using a 400 V class unit.
Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-04
Reverse Operation Selection
1: Reverse Prohibited
C1-01
Acceleration Time 1
1.0 s
C1-02
Deceleration Time 1
1.0 s
C6-01
Drive Duty Mode Selection
1: Normal Duty (ND)
E1-03
V/f Pattern Selection
F: Custom V/f pattern
E1-07
Middle Output Frequency
30.0 Hz
E1-08
Middle Output Frequency Voltage
50.0 V
L2-01
Momentary Power Loss Operation Selection
1: Enabled
No.
Parameter Name
No.
Parameter Name
b1-01
Frequency Reference Selection 1
E1-08
Middle Output Frequency Voltage
b1-02
Run Command Selection 1
E2-01
Motor Rated Current
b1-04
Reverse Operation Selection
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
C1-01
Acceleration Time 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
C1-02
Deceleration Time 1
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
E1-03
V/f Pattern Selection
L5-01
Number of Auto Restart Attempts
E1-07
Middle Output Frequency
−
−