Register No.
Contents
000FH
Control Selection Setting
bit 0
Reserved
bit 1
PID Setpoint Input
bit 2
Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)
bit 3
Torque compensation input (enables the setting from MEMOBUS/Modbus)
bit 4 to B
Reserved
bit C
Enable Terminal S5 Input for Broadcast Data
bit D
Enable Terminal S6 Input for Broadcast Data
bit E
Enable Terminal S7 Input for Broadcast Data
bit F
Enable Terminal S8 Input for Broadcast Data
0010H to 001AH
Reserved
001BH
Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)
001CH
Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)
001DH
Digital Output Option DO-A3 Output (Binary)
001EH to 001FH
Reserved
0A93H
bit 1
RTC Disable
bit 2
Dynamic Noise Ctrl
3004H
Set Time – Hours/Minutes (HHmm)
3005H
Set Date – Year/Day of Week (YYdd)
3006H
Set Date – Month/Day (MMDD)
3007H
RTC Set Command/Status
bit 0
Complete
bit 1
Set RTC data using registers 3004H to 3006H
bit 8
Failed
302FH
RTC Enter
bit 0
Overwrite RTC data using registers 3004H to 3006H. Only effective when 3030H (RTC Enter Enable) is
set.
3030H
bit 1
RTC Enter Enable
bit 2
RTC TIE Fault Enable
u
Monitor Data
Monitor data can be read only.
Register No.
Contents
0020H
Drive Status 1
bit 0
During Run
bit 1
During Reverse
bit 2
Drive Ready
bit 3
Fault
bit 4
Data Setting Error
bit 5
Multi-Function Contact Output 1 (terminal M1-M2)
bit 6
Multi-Function Contact Output 2 (terminal M3-M4)
bit 7
Multi-Function Contact Output 3 (terminal MD-ME-MF)
bit 8 to bit D
Reserved
bit E
When ComRef has been enabled
bit F
When ComCtrl has been enabled
C.9 MEMOBUS/Modbus Data Table
388