n
Harmonic Filter Module
Table 2.2 Harmonic Filter Module Installation Environment
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
IP00/Open Type enclosure: -10 °C to +50 °C (14 °F to 122 °F)
Harmonic filter module reliability improves in environments without wide temperature fluctuations.
When using the harmonic filter module in an enclosure panel, install a cooling fan or air conditioner in the area to ensure
that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the harmonic filter module.
Humidity
95% RH or less and free of condensation
Storage Temperature
-20 °C to +60 °C (-4 °F to +104 °F)
Surrounding Area
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude
1000 m (3281 ft.) or lower, up to 3000 m (9843 ft.) with derating.
Refer to Altitude Derating on page 488
Vibration
10 to 20 Hz: 5.9 m/s
2
20 to 55 Hz: 2.0 m/s
2
Orientation
Install the harmonic filter module vertically to maintain maximum cooling effects.
NOTICE: Avoid placing peripheral devices, transformers, or other electronics near the harmonic filter module, as the noise created can lead
to erroneous operation. Take proper steps to shield the harmonic filter module from noise if such devices must be used in close proximity.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the harmonic filter module during installation.
Failure to comply could result in damage to the harmonic filter module. Place a temporary cover over the top of the harmonic filter module
during installation. Remove the temporary cover before start-up, as the cover will reduce ventilation and cause overheat.
u
Installation Orientation and Spacing
NOTICE: Install the drive upright as illustrated in
. Failure to comply may damage the drive due to improper cooling.
Figure 2.1 Correct Installation Orientation
NOTICE: Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling.
2.2 Mechanical Installation
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
59
2
Mechanical Installation
Содержание U1000 iQpump Drive