5.6 F: Option Settings
u
F1: PG Speed Control Card Settings
Yaskawa offers PG-X3, PG-B3, PG-RT3, and PG-F3 motor encoder PG option cards. Use the CN5-C port when using only
one PG option card and use the CN5-C and CN5-B ports when using two PG option cards. When programming one of the
multi-function input terminals to act as a switch between two motors (H1-
oo
= 16), use the card connected to port CN5-C
for motor 1 and use the card connected to CN5-B for motor 2.
lists the parameters that must be set for each option card port.
Table 5.35 Option Card Ports and Corresponding Parameters
Port
Parameters
CN5-C and CN5-B (common) F1-02 to F1-04, F1-08 to F1-11, F1-14
CN5-C only
F1-01, F1-05, F1-06, F1-12, F1-13, F1-18 to F1-21
CN5-B only
F1-31 to F1-37
n
F1-01, F1-31: PG 1 and PG 2 Pulses Per Revolution
Sets the number encoder number of pulses per revolution.
No.
Parameter Name
Option Port
Setting Range
Default
F1-01
PG 1 Pulses Per Revolution
CN5-C
1 to 60000 ppr
1024 ppr
F1-31
PG 2 Pulses Per Revolution
CN5-B
1 to 60000 ppr
1024 ppr
<1> Setting range is 0 to 15000 in PM motor control modes
n
F1-02, F1-14: PG Open (PGo) Circuit Operation Selection, Detection Time
A PGo fault is triggered if the drive receives no pulse signal for longer than the time set in F1-14. Set the stopping method for
a PGo fault in parameter F1-02.
Note:
An oC error may occur depending on motor speed and load conditions.
No.
Parameter Name
Option Port
Setting Range
Default
F1-02
Operation Selection at PG Open Circuit (PGo)
CN5-B, CN5-C
0 to 4
1
F1-14
PG Open-Circuit Detection Time
CN5-B, CN5-C
0.0 to 10.0 s
2.0 s
Parameter F1-02 Settings:
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only
Note:
Due to potential damage to motor and machinery, refrain from using the “Alarm only” or “No alarm display” settings except under special
circumstances.
Setting 4: No alarm display
Note:
Due to potential damage to motor and machinery, refrain from using the “Alarm only” or “No alarm display” settings except under special
circumstances.
n
F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time
An oS fault is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set in F1-09. Set the
stopping method for an oS fault in parameter F1-03.
Note:
In AOLV/PM, the motor will coast to a stop (F1-03 = 1). The setting for F1-03 cannot be changed to 0, 2, or 3.
No.
Parameter Name
Option Port
Setting Range
Default
F1-03
Operation Selection at Overspeed (oS)
CN5-B, CN5-C
0 to 3
1
F1-08
Overspeed Detection Level
CN5-B, CN5-C
0 to 120%
115%
F1-09
Overspeed Detection Delay Time
CN5-B, CN5-C
0.0 to 2.0 s
Determined by A1-02
Parameter F1-03 Settings:
5.6 F: Option Settings
264
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual