4.3 The Drive and Programming Modes
The drive has a Drive Mode to operate the motor and a Programming Mode to edit parameter settings.
Drive Mode:
In Drive Mode the user can operate the motor and observe U Monitor parameters. Parameter settings cannot be
edited or changed when in Drive Mode.
Programming Mode:
In Programming Mode the user can edit and verify parameter settings and perform Auto-Tuning. When
the drive is in Programming Mode it will not accept a Run command unless b1-08 is set to 1.
Note:
1.
If b1-08 is set to 0, the drive will only accept a Run command in Drive Mode. After editing parameters, the user must exit the Programming
Mode and enter Drive Mode before operating the motor.
2.
Set b1-08 to 1 to allow motor operation from the drive while in Programming Mode.
u
Navigating the Drive and Programming Modes
The drive is set to operate in Drive Mode when it is first powered up. Switch between display screens by using the
and
keys.
Mode
Contents
Operator Display
Description
Power Up
Frequency
Reference
(default)
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
FREF (AI)
Rdy
RSEQ
RREF
FWD
JOG
This display screen allows the user to monitor and change the frequency reference while
Refer to The Drive and Programming Modes on page 140
Note:
The user can select the data displayed when the drive is first powered up
with parameter o1-02.
Drive Mode
Monitor Display
- MODE -
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
DRV
Monitor Menu
Rdy
RSEQ
RREF
FWD
JOG
Lists the monitor parameters (U
o
-
oo
parameters) available in the drive.
Press the Enter Key and then use the Up, Down, ESC, and Reset keys to navigate through
the drive monitors.
Programming
Mode
Verify Menu
- MODE -
PRG
Modified Consts
HELP
DATA
FWD
Modified
X Parameters
Lists all parameters that have been edited or changed from default settings.
Verifying Parameter Changes: Verify Menu on page 143
.
Setup Group
HELP
- MODE -
PRG
Quick Setting
DATA
FWD
A select list of parameters necessary to get the drive operating quickly.
Using the Setup Group on page 144
.
Note:
Parameters listed in the Setup Group differ depending the Application
Preset in parameter A1-06.
Refer to Application Selection on page 154
.
Parameter
Setting Mode
HELP
- MODE -
PRG
DATA
Programming
FWD
Allows the user to access and edit all parameter settings.
.
Auto-Tuning
Mode
HELP
- MODE -
PRG Rdy
Auto-Tuning
DATA
AUTO
FWD
Motor parameters are calculated and set automatically.
.
4.3 The Drive and Programming Modes
140
YASKAWA ELECTRIC SIEP C710636 04D U1000 Industrial MATRIX Drive Technical Manual
Содержание U1000 iQpump Drive