background image

TP-ECO | 62E-MHC0 | Manual

HB160 | TP-ECO | 62E-MHC0 | en | 17-01

VIPA HMI

Touch Panel - T

www.vipa.com/en/service-support/manual

Содержание TP-ECO

Страница 1: ...TP ECO 62E MHC0 Manual HB160 TP ECO 62E MHC0 en 17 01 VIPA HMI Touch Panel TP604LC www vipa com en service support manual...

Страница 2: ...62E MHC0_000_TP604LC 1 GB 2017 VIPA GmbH Ohmstr 4 91074 Herzogenaurach Telephone 49 9132 744 0 Fax 49 9132 744 1864 Email info vipa com Internet www vipa com...

Страница 3: ...ger 33 3 5 Connection to a PLC system 35 3 6 Operating system Windows Embedded CE 6 0 Core 36 3 6 1 General 36 3 6 2 Structure 37 3 7 Integrated Server 41 3 7 1 General 41 3 7 2 ftp server 41 3 7 3 VN...

Страница 4: ...he EMC equitable assembly of installations 69 5 2 EMC equitable assembly 72 5 3 EMC equitable cabling 73 5 4 Special precautions providing high noise immunity 76 5 5 Checklist for the EMC compliant in...

Страница 5: ...ective purchase contract Hereby VIPA GmbH declares that the products and systems are in compliance with the essential requirements and other relevant provisions Conformity is indicated by the CE marki...

Страница 6: ...MHC0 DH 01 Windows CE 6 0 Core TP 604LC 62E MHC0 CB 01 Windows CE 6 0 Prof The manual is targeted at users who have a background in automation technology The manual consists of chapters Every chapter...

Страница 7: ...onnel in the n project design department n installation department n commissioning n operation CAUTION The following conditions must be met before using or commis sioning the components described in t...

Страница 8: ...es that have been damaged by electrostatic discharges can fail after a temperature change mechanical shock or changes in the electrical load Only the consequent implementation of protection devices an...

Страница 9: ...ly suitable for monitoring and controlling of process cycles n 62E MHC0 DH Windows CE 6 0 Core Movicon 11 CE Basic 512 I O Bytes n 62E MHC0 CB Windows CE 6 0 Prof Movicon 11 CE Standard 4096 I O bytes...

Страница 10: ...nterface optional 2 3 Structure 2 3 1 Overview 1 MPI PROFIBUS DP interface COM 3 optional 2 RS232 interface COM 1 3 RS232 RS422 RS485 interface COM 2 4 Display with touch sensitive area touch screen 1...

Страница 11: ...k for Ethernet communication 3 Host USB A interface 4 Slot for DC 24V voltage supply Please make sure that the Touch Panel always has to be supplied with external voltage Bottom view Back view VIPA HM...

Страница 12: ...2 3 2 Interfaces VIPA HMI Hardware description Structure Interfaces HB160 TP ECO 62E MHC0 en 17 01 12...

Страница 13: ...25 pin SubD female RS232 RS422 RS485 inter face VIPA HMI Hardware description Structure Interfaces HB160 TP ECO 62E MHC0 en 17 01 13...

Страница 14: ...uired for Ethernet Using the Host USB A interface USB mouse keyboard stick or USB hard discs can be connected The Touch Panel has got an integrated power supply The power supply has to be pro vided wi...

Страница 15: ...el has a flash disk with a size of 128Mbyte After the start of Windows CE this memory is listed as Flashdisk at My Device The connection of USB sticks and USB drives by use of the Host USB A interface...

Страница 16: ...ation depth 51mm The degrees of protection are only guaranteed when the following is observed Material thickness at the mounting cut out 2 5 6mm The deviation from the plane for the panel cut out is 0...

Страница 17: ...on voltage to reference earth Inputs outputs AC DC 50V test voltage AC 500V Protective measures against short circuit Environmental conditions to EN 61131 2 Climatic Storage transport EN 60068 2 14 20...

Страница 18: ...000MHz 10V m 80 AM 1kHz 1 4GHz 2 0GHz 3V m 80 AM 1kHz 2GHz 2 7GHz 1V m 80 AM 1kHz EN 61000 4 6 HF conducted 150kHz 80MHz 10V 80 AM 1kHz EN 61000 4 4 Burst degree of severity 3 EN 61000 4 5 Surge degre...

Страница 19: ...mory 256 MB User memory 128 MB Available memory user data 50 MB SD MMC Slot CF Card Slot Typ II CFast Slot Time Real time clock buffered Clock buffered period min 26 w Type of buffering Manganese Rech...

Страница 20: ...ted value DC 24 V Power supply permitted range DC 20 4 28 8 V Reverse polarity protection Current consumption no load operation 0 16 A Current consumption rated value 0 3 A Inrush current 75 A I t 0 3...

Страница 21: ...thickness 6 mm Net weight 500 g Environmental conditions Operating temperature 0 C to 50 C Storage temperature 20 C to 60 C Certifications UL certification yes KC certification VIPA HMI Hardware desc...

Страница 22: ...memory 128 MB Available memory user data 50 MB SD MMC Slot CF Card Slot Typ II CFast Slot Time Real time clock buffered Clock buffered period min 26 w Type of buffering Manganese Rechargeable Lithium...

Страница 23: ...V Power supply permitted range DC 20 4 28 8 V Reverse polarity protection Current consumption no load operation 0 16 A Current consumption rated value 0 3 A Inrush current 75 A I t 0 36 A s Power loss...

Страница 24: ...ess 6 mm Net weight 500 g Environmental conditions Operating temperature 0 C to 50 C Storage temperature 20 C to 60 C Certifications UL certification yes KC certification VIPA HMI Hardware description...

Страница 25: ...e installation of the panel 4 mounting clips and a small hexagon socket key are required 1 Push the operator panel 3 from the front side into the front panel cutting 1 until it touches the panel with...

Страница 26: ...dule only at the holding plate and avoid touching the board Store respectively send the interface module always in the corresponding ESD packaging 1 Remove the cover plate of the COM3 port by removing...

Страница 27: ...e module in the device until the holding plate fits to the housing Here the interface module is put into the right position by 2 inner guide rails VIPA HMI Deployment under Windows CE 6 0 Core Install...

Страница 28: ...te always snaps to the lugs otherwise the holding plate can not be screwed 4 Mount the screws again After installation the interface module is automatically recognized and can be configured VIPA HMI D...

Страница 29: ...condensation the device must be absolutely dry before connected to power To avoid overheat during operation the device must not be laid open to direct sun light After opening the control cabinet or de...

Страница 30: ...for the Startup Manager The password will be requested when interrupting the start countdown or before closing the Startup Managers by Exit By default no password is defined In Control Panel Open the...

Страница 31: ...ch the power supply off the panel off and on After the restart the calibration window is opened 4 Re calibrate the panel as described After calibration tap anywhere on the screen The calibration windo...

Страница 32: ...u get back to the select menu By default the configuration of the Startup Manager the registry settings for the back light the local settings and the LAN settings will be saved by Backup in Flashdisk...

Страница 33: ...ing in the background such as the transport service of Movicon CEUpload Server exe 1 Call www vipa com 2 Click Service Support Downloads Firmware 3 Via HMI TP ECO Panels navigate to your Panel and dow...

Страница 34: ...wait a moment After successful execution the following completion screen appears 9 Confirm this window with OK remove the SD card and re start the panel The panel should start with the Startup Manager...

Страница 35: ...on of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via field bus and Ethernet...

Страница 36: ...area is recognized and the program reacts accordingly The following types of entry are differentiated Double click A double click has to be executed like mouse operation by touching the area at the s...

Страница 37: ...like e g applications system settings file browser etc 2 Open applications For every open application a button is to be found in the task bar There is no button for minimizing The switch between the a...

Страница 38: ...e implemented At pushed Shift key At pushed a key Please note that can exclusively be entered via the software key board Keyboard At pushed Shift key Software keyboard Keyboard Large KB VIPA HMI Deplo...

Страница 39: ...ialog windows for the display properties opens Here you may change the settings for the monitor options For example you may adjust the brightness and contrast via the register Settings n Calibrate tou...

Страница 40: ...Power Properties you may set the break time and the dimming of the back lighting For this choose AC Power at Power Scheme and then set the appropriate time A set suspend mode shuts down the Touch Pan...

Страница 41: ...erver and receives an answer A server is an application that waits for the contact request of a client application and exchanges messages with it after contact start This communication type is called...

Страница 42: ...nitor the IP address data via in the taskbar 4 After you ve confirmed the pre settings start your ftp client e g Windows Explorer and enter the following text into the address bar ftp wince vipatp IP...

Страница 43: ...ars in the task bar You may also start the VNC server at the Touch Panel via a Telnet connection by entering the command winvnc in the command console with an active Telnet connection 3 Now start the...

Страница 44: ...resources of the network PC test server To test the physical connection a PING to the IP address of the network PC may be executed if there are problems while contacting the network PC The connection...

Страница 45: ...rk printer The printer may now be accessed as network printer For example you may print the content of the current directory using dir network printer The listing command for all network connections o...

Страница 46: ...e installation of the panel 4 mounting clips and a small hexagon socket key are required 1 Push the operator panel 3 from the front side into the front panel cutting 1 until it touches the panel with...

Страница 47: ...dule only at the holding plate and avoid touching the board Store respectively send the interface module always in the corresponding ESD packaging 1 Remove the cover plate of the COM3 port by removing...

Страница 48: ...e module in the device until the holding plate fits to the housing Here the interface module is put into the right position by 2 inner guide rails VIPA HMI Deployment under Windows CE 6 0 Prof Install...

Страница 49: ...te always snaps to the lugs otherwise the holding plate can not be screwed 4 Mount the screws again After installation the interface module is automatically recognized and can be configured VIPA HMI D...

Страница 50: ...sible dangerous voltage available For all signal connections only screened cables are permitted Signal cables must not be let within the same cable shaft as high voltage cables 4 3 1 VIPA Startup Mana...

Страница 51: ...h Image a list of all the firmware images is shown which are available on the panel and connected storage media These images will be listed with create data and version number Choose your new image If...

Страница 52: ...using the buttons and 5 seconds are default Via Rotation the orientation of the panel can be changed Via Program start with you can add programmes which have to start automatically 1 Select start and...

Страница 53: ...get back to the start screen of the VIPA Startup Manager 4 4 Installation Movicon and Startup Manager After an image update it is necessary to re install Movicon and Startup Manager The cur rent data...

Страница 54: ...via double click on the fol lowing symbol After start up the following window appears 7 Click Make All the necessary files are copied and the registry is accordingly adjusted The progress is displaye...

Страница 55: ...screen appears 9 Confirm this window with OK remove the SD card and re start the panel The panel should start with the Startup Manager after the restart VIPA HMI Deployment under Windows CE 6 0 Prof...

Страница 56: ...on of the HMI SCADA project engineering platforms your project is run able By using the according communication driver the Touch Panel supports connecting options to the PLC via field bus and Ethernet...

Страница 57: ...ching an area at the touch screen this area is recognized and the program reacts accordingly The following types of entry are differentiated Double click A double click has to be executed like mouse o...

Страница 58: ...components of your Touch Panel like e g applications system settings file browser etc 2 Open applications For every open application a button is to be found in the task bar There is no button for min...

Страница 59: ...ou to select one of the available software keyboards At the moment the following standard keyboards are implemented At pushed Shift key At pushed a key Please note that can exclusively be entered via...

Страница 60: ...rd allows you to enter key entries without connecting an external keyboard As soon as an entry is required the software keyboard is automatically shown Hide Input Panel hides the keyboard again Large...

Страница 61: ...egister Calibration by fol lowing the instructions n Set Ethernet parameters The dialog field for pre setting an Ethernet address is to be found at Start Settings Network and Dial up Connections The d...

Страница 62: ...tion of the server A client is an application that uses the service of a server within a network For example a web browser is a client because at every call of a website it sends a request to a web se...

Страница 63: ...start the Internet Explorer The settings are saved Below is explained how to establish of a ftp connection between a Windows based PC with Windows Explorer as ftp client and your Touch Panel 1 Connect...

Страница 64: ...ter the following into the address bar IP address webadmin 2 Enter the following into the authentification n User name wince n Password vipatp 4 7 4 Telnet server Telnet is a text based client server...

Страница 65: ...Panel content for remote control Operation is performed via PC keyboard and mouse Condition for the VNC communication is that the VNC server is started on the Touch Panel and a VNC client on the PC Y...

Страница 66: ...he IP address of the Touch Panel at VNC server Click on OK and enter the password vipatp You can change the password over the configuration file for this execute vncconfig exe Now a VNC connection is...

Страница 67: ...ser name password and where app user group After successful login the following message appears Successfully mapped to network name The connected network drive is then available on the Touch Panel wit...

Страница 68: ...is net use You may terminate already assigned network resources via net use local_name d Example net use data d deletes the network connection to the drive archive of test server Test print List netwo...

Страница 69: ...MC planning before installing the components and take conceivable interference causes into account Electromagnetic interferences may interfere your control via different ways n Electromagnetic fields...

Страница 70: ...tive coupling Inductive or magnetic coupling occurs between two current active line loops The magnetic flows associated with the currents induct interference vol tages The coupling is proportional to...

Страница 71: ...tudes the one sided laying of the isolation may be favourable Lay the line isolation extensively on an isolation protected earth conductor rail directly after the cabinet entry and fix the isolation w...

Страница 72: ...age even in case of an error Thus you have to connect the ground with the protected earth conductor To avoid ground loops local distant ground constructions cubicles construction and machine parts hav...

Страница 73: ...groups Group A Group B Group C Group D Group A 1 2 3 4 Group B 2 1 3 4 Group C 3 3 1 4 Group D 4 4 4 1 1 The lines may be installed in common bundles or cable trusses 2 The lines have to be installed...

Страница 74: ...e equipotential bonding conductor must not exceed 10 of the impedance of the screen where screened signal lines are connected between the dif ferent sections of the plant and the screening is connecte...

Страница 75: ...e cover Do not connect the screen to PIN 1 of the connector In case of stationary operations it is recommended that the remove the insulation from the screened cable without cutting the screen and to...

Страница 76: ...diode using a varistor using RC network Every cubicle must be provided with a power outlet for the PU These outlets must be wired to the distribution system which is also used to connect the neutral...

Страница 77: ...een grounded by means of grounding straps connected to the body of the cubicle Cable routing Cabling divided into groups Power cables 230 400V and signal lines installed in separate channels or bunche...

Отзывы: