
B.3 Parameter Table
380
YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual
u
E: Motor Parameters
n
E1: V/f Pattern for Motor 1
n
E2: Motor 1 Parameters
No.(Addr.)
<7> Default setting value is dependent on the motor code set to E5-01.
<15> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<17> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<34> Default setting value is determined by the control mode (A1-02).
<35> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<38> The setting range varies according to the motor code entered to E5-01 when using OLV/PM. The setting range is 0.0 to 400.0 Hz when E5-01
is set to FFFFH.
Name
Description
Setting
Page
E1-01
(300H)
Input Voltage Setting
This parameter must be set to the power supply voltage.
WARNING!
Drive input voltage (not motor voltage) must be set in E1-01 for the protective
features of the drive to function properly. Failure to do so may result in equipment damage and/
or death or personal injury.
Default: 200 V
Min: 155 V
Max: 255 V
E1-03
(302H)
V/f Pattern Selection
F: Custom V/f, E1-04 through E1-13 settings define the V/f pattern
Default: F
Min: –
Max: F
E1-04
(303H)
Maximum Output Frequency
To set linear V/f characteristics, set the same values for E1-07 and E1-09. In this case, the
setting for E1-08 will be disregarded. Ensure that the four frequencies are set according to these
rules:
E1-09
≤
E1-07
<
E1-06
≤ Ε1−11 ≤
E1-04
Note that if E1-11 = 0, then both E1-11 and E1-12 are disabled, and the above conditions do not
apply.
Note:
Some parameters may not be available depending on the control mode.
• E1-07, E1-08 and E-10 are available only in the following control modes: V/f Control, V/f
with PG, Open Loop Vector.
• E1-11, E1-12 and E-13 are available only in the following control modes: V/f Control, V/f
with PG, Open Loop Vector, Closed Loop Vector.
Default:
Min: 40.0 Hz
Max: 400.0 Hz
E1-05
(304H)
Maximum Voltage
Default:
Min: 0.00 V
Max: 255.0 V
E1-06
(305H)
Base Frequency
Min: 0.0 Hz
Max: E1-04
E1-07
(306H)
Middle Output Frequency
Default:
Min: 0.0 Hz
Max: E1-04
E1-08
(307H)
Middle Output Frequency Voltage
Default:
Min: 0.0 V
Max: 255.0 V
E1-09
(308H)
Minimum Output Frequency
Default:
Min: 0.0 Hz
Max: E1-04
E1-10
(309H)
Minimum Output Frequency
Voltage
Default:
Min: 0.0 V
Max: 255.0 V
E1-11
(30AH)
Middle Output Frequency 2
Default: 0.0 Hz
Min: 0.0 Hz
Max: E1-04
E1-12
(30BH)
Middle Output Frequency Voltage
2
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
E1-13
(30CH)
Base Voltage
Default: 0.0 V
Min: 0.0 V
Max: 255.0 V
No.(Addr.)
Name
Description
Setting
Page
E2-01
(30EH)
Motor Rated Current
Sets the motor nameplate full load current in Amps. Automatically set during Auto-Tuning.
Default:
Min: 10% of drive rated
current
Max: 200% of drive
rated current
E2-02
(30FH)
Motor Rated Slip
Sets the motor rated slip. Automatically set during Auto-Tuning.
Default:
Min: 0.00 Hz
Max: 20.00 Hz
E2-03
(310H)
Motor No-Load Current
Sets the no-load current for the motor. Automatically set during Auto-Tuning.
Default:
Min: 0 A
Max: E2-01
E2-04
(311H)
Number of Motor Poles
Sets the number of motor poles. Automatically set during Auto-Tuning.
Default: 4
Min: 2
Max: 48
All Modes
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
All Modes
Output Voltage (V)
Frequency (Hz)
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
OLV/PM
AOLV/PM
CLV
V/f w/PG
CLV/PM
V/f
OLV
Содержание T1000A
Страница 4: ...4 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 32: ...1 5 Component Names 32 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 104: ...4 10 Test Run Checklist 104 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 334: ...7 5 Drive Replacement 334 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...
Страница 362: ...A 6 Drive Derating Data 362 YASKAWA ELECTRIC SIEP C710616 30B YASKAWA AC Drive T1000A Technical Manual...