Modbus Map SOLECTRIA XGI 1500 (Rev A)
DOCR-XXXXXX
25 of 30
To implement the same curve, the procedure is shown below.
Write “ 16 ” to register 40517 for HF2 Disconnect Time
Write “ 6200 ” to register 40518 for HF2 Freq Threshold
Write “ 30000 ” to register 40521 for HF1 Disconnect Time
Write “ 6050 ” to register 40522 for HF1 Freq Threshold
Write “ 16 ” to register 40455 for LF2 Disconnect Time
Write “ 5700 ” to register 40456 for LF2 Freq Threshold
Write “ 30000 ” to register 40459 for LF1 Disconnect Time
Write “ 5850 ” to register 40460 for LF1 Freq Threshold