5 Installation Procedure
24
YASKAWA ELECTRIC
TOBP C730600 23C 1000-Series Option SI-P3/V, SI-P3/T Installation Manual
7.
Attach the PROFIBUS-DP Option cover to the front of the PROFIBUS-DP Option.
Figure 14
Figure 14 Attach Cover
Note:
When using the drive in an area that may require displaying warning information in Japanese or
Chinese, a label is provided with the Profibus-DP Option. This label can be placed over the
English and French warnings on the front of the Profibus-DP Option.
◆
Communication Cable Specifications
To ensure proper performance, Yaskawa recommends using PROFIBUS-DP-dedicated
cables that fulfill the specifications in
Table 6
. For more information on cables, refer to the
PROFIBUS-DP website at http://www.profibus.com.
■
Cable Requirements
Table 6 Communication Cable Requirements
Condition
Specifications
Impedance
135 to 165
Ω
at a frequency of (3 to 20 MHz)
Capacity
30 pF/m maximum
Loop Resistance
110
Ω
/km maximum
Core Cross-Section
0.34 mm
2
minimum
Core Diameter
0.64 mm minimum
Tabs should line up