6 CC-Link Option Drive Parameters
YASKAWA ELECTRIC
SIEP C730600 22C V1000 Option CC-Link Technical Manual
19
6
CC-Link Option Drive Parameters
Confirm proper setting of the all parameters in
before starting network communications.
Table 8 Parameter Settings
No.
Name
Description
Default
b1-01
<1> To start and stop the drive with the CC-Link master device using serial communications, set b1-02 to “3”. To control the frequency reference of the drive via the master device, set b1-01
to “3”.
<2> If set to 3, then the drive will continue to operate when a fault is detected. Take proper measures such as installing an emergency stop switch.
<3> The drive default setting is 2.0 s, but this default setting will automatically be changed to 0.0 s when SI-C3/V is connected.
<4> Software versions 1012 and later have F6-07 and F6-08 both set to 1.
<5> Power must be cycled in order for any setting changes to take affect.
<6> All station addresses must be unique. If set to 0, the L.ERR light will turn on and a Station Address Error (AEr) will occur.
<7> A total of 42 nodes can be connected, assuming that all connections are inverter drives.
The following conditions apply when connecting devices that are not drives to the network:
Frequency Reference Selection
Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
b1-02
Run Command Selection
Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS communications
3: Option PCB
1
F6-01
Operation Selection after
Communications Error
Determines drive response when a bUS error is detected during communications with the CC-Link Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-02
External Fault Detection Conditions
(EF0)
Sets the condition for external fault detection (EF0)
0: Always detected.
1: Detected only during operation.
0
F6-03
Stopping Method for External Fault
from Communication Option
Determines drive response for external fault input (EF0) detection during CC-Link communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-04
bUS Error Detection Delay Time
Set the maximum time the drive should wait for a communication error to occur (bUS).
Range 0.0 to 5.0 s
0.0 s
F6-07
NetRef/ComRef Selection Function
0: Multi-step speed reference disabled (F7 mode)
1: Multi-step speed reference allowed (V7 mode)
1
F6-08
Reset Communication Related
Parameters
Determines which communication-related parameters are set back to their original default values when the drive is
initialized.
0: Do not reset F6-
and F7-
parameters when the drive is initialized using parameter A1-03.
1: Rest F6-
and F7-
parameters when the drive is initialized using parameter A1-03.
Note:
Setting this parameter does not affect communication-related parameters.
0
F6-10
Station Address
0 to 64
0
F6-11
Comm Speed
0: 156 kbps
1: 625 kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps
0
A: number of remote I/O nodes........ 64 max
B: number of remote device nodes... 42 max
C: number of local nodes.................. 26 max
a: number of units that occupies 1 node
b: number of units that occupies 2 nodes
c: number of units that occupies 3 nodes
d: number of units that occupies 4 nodes
{(1
u
a)+(2
u
b)+(3
u
c)+(4
u
d)}
≦
64
{(
16
u
A
)
+
(
54
u
B
)
+
(
88
u
C
)} ≦
2304
(
(
)
)