5 Installation Procedure
YASKAWA ELECTRIC
SIEP C730600 22C V1000 Option CC-Link Technical Manual
17
Communication Cable Wiring
Procedure
Follow the instructions below to connect the communications cable to the terminal block.
NOTICE:
Tighten all terminal screws according to the specified tightening torque. Tightening screws too tight could damage the terminal block, and leaving screws too loose
can cause a short-circuit or drive malfunction.
1.
Connect the communications cable to the terminal block as shown in the diagram below.
Note:
Communication lines should be separated from main circuit wiring and other electrical lines. (Tightening torque: 0.22 to 0.25 (N
m))
Figure 15
Figure 15 Comm Cable Wiring
2.
Ensure all wiring connections are tightened and wire insulation is not pinched in the terminal block. Remove any stray wire strands that touch
other terminals.
3.
After the terminal block is fully attached to the option unit, tighten the screws on the left and right sides of the terminal block. (Tightening
torque: 0.22 to 0.25 (N
m))
Note:
Be sure to put the option cover back on after you have completed all necessary wiring.
Figure 16
Figure 16 Terminal Block Installation
Communication Cable Specifications
Use only CC-Link dedicated communication cable; the Yaskawa warranty does not cover other cable types. For more information on cables, refer to
the CC-Link website at http://www.cc-link.org/.
Yaskawa recommends using CC-Link cables suitable for the conditions listed in
Table 7 Communication Cable Requirements
Specifications
Cable Type
triple-core shielded twisted-pair cable
Gauge
8.0 mm max
Drain Wire
20 lines / 0.18 mm or 24 lines / 0.18 mm
Electrical
Characteristics
Conductor Resistance (20
°
C)
37.8
Ω
/km
Insulation Resistance
10000 M
Ω
km or more
Voltage Tolerance
500 Vdc, 60 s
Capacitance (1 kHz)
60 nF/km max
Impedance
1 MHz
110 ±15
Ω
5 MHz
110 ± 6
Ω
Attenuation (20
°
C)
1 MHz
1.6 dB / 100 m max
5 MHz
3.5 dB / 100 m max
DA DB DG SLD SLD
Terminal block
Preparing wire ends:
Screwdriver blade size
When not using
terminal extensions
about 5.5 mm
up to
2.5 mm
Blade width
up to 0.4 mm
Pull back the sheilding and lightly
twist the end with fingers, keeping
the ends from fraying
CC-Link comm cable
(do not soldered ends)
Loosen the screws and
insert the cable into the
opening on the terminal block
screwdriver blade size
up to
3.5 mm
blade width
up to 0.6 mm
SIEP_C730600_22C_3_0.book 17 ページ 2022年8月23日 火曜日 午後1時4分