YASKAWA
TOEP YAICOM 22A BACnet MS/TP Installation & Technical Manual
35
No.
(Hex.)
Name
Description
Default
(Range)
Note:
Available for option card software versions VST800265
and later.
F6-45
(02FB)
Drive Node
Address
Sets the BACnet MS/TP MAC address (physical node
address).
1
(0 - 127)
F6-46
(02FC)
Communication
Speed Selection
Sets the communication speed.
0 : 1200 bps
1 : 2400 bps
2 : 4800 bps
3 : 9600 bps
4 : 19200 bps
5 : 38400 bps
6 : 57600 bps
7 : 76800 bps
8 : 115200 bps
3
(0 - 8)
F6-47
(02FD)
Drive Transmit
Wait Time
Sets the time the drive waits to send response data after it
receives data from the master.
5 ms
(5 - 65 ms)
F6-48
(02FE)
BACnet Device
Object Identifier
0
Sets the Instance Identifier of the BACnet Device Object,
where the
F6-48
value is the least significant word.
Note:
This parameter and
F6-49
set the Instance Identifier of the
BACnet Device Object.
Example 1: Set the Device Object Instance Identifier to
1234
. 1234 decimal is equal to 4D2H (hexadecimal). Set
F6-48 = 4D2H
and
F6-49 = 0.
Example 2: Set the Device Object Instance Identifier to
1234567
. 1234567 decimal is equal to 12D687H. Set
F6-
48 = D687H
and
F6-49 = 12H.
1
(0 - FFFFH)