4.4 Command Option Attachable-type FT82 SERVOPACKs with INDEXER Modules
4-114
4.4
Command Option Attachable-type FT82 SERVOPACKs with INDEXER Modules
The following table lists the parameters.
Note: Do not change the following parameters from their default settings.
•
Reserved parameters
•
Parameters not given in this manual
•
Parameters that are not valid for the Servomotor that you are using, as given in the parameter table
•
The following parameters will be set automatically when the INDEXER Module is mounted. Do
not change the settings of these parameters.
Pn002 = n.
X, Pn205, Pn207 = n.X
, Pn50A to Pn512, Pn517, and Pn522
•
Parameters that are unique to the INDEXER Module will be set automatically the first time the
power supply is turned on after the INDEXER Module is mounted. Up to 10 s may be required
for the SERVOPACK to start.
Parameter
No.
Size
Name
Setting
Range
Setting
Unit
Default
Setting
Applicable
Motors
When
Enabled
Classi-
fication
Refer-
ence
Pn000
2
Basic Function Selec-
tions 0
0000h to
10B1h
–
0000h
All
After
restart
Setup
–
Pn001
2
Application Function
Selections 1
0000h to
1142h
–
0000h
All
After
restart
Setup
–
Continued on next page.
Note
n.
X
Rotation Direction Selection
Reference
0
Use CCW as the forward direction.
*1
1
Use CW as the forward direction. (Reverse Rotation Mode)
n.
X
Reserved parameter (Do not change.)
n.
X
Reserved parameter (Do not change.)
n.X
Reserved parameter (Do not change.)
n.
X
Motor Stopping Method for Servo OFF and Group 1 Alarms
Reference
0
Stop the motor by applying the dynamic brake.
*1
1
Stop the motor by the applying dynamic brake and then release
the dynamic brake.
2
Coast the motor to a stop without the dynamic brake.
n.
X
Reserved parameter (Do not change.)
n.
X
Main Circuit Power Supply AC/DC Input Selection
Reference
0
Input AC power as the main circuit power supply using the L1, L2,
and L3 terminals (do not use shared converter).
*1
1
Input DC power as the main circuit power supply using the B1/
and
2 terminals or the B1 and
2 terminals (use an external
converter or the shared converter).
n.X
Warning Code Output Selection
Reference
0
Output only alarm codes on the /ALO1 to /ALO3 terminals.
*1
1
Output both warning codes and alarm codes on the /ALO1 to
/ALO3 terminals. If there is an alarm, the alarm code is output.