16.2 Alarm Displays
16.2.4 Displaying the Alarm History
16-43
16
Maintenance
16.2.4
Displaying the Alarm History
The alarm history displays up to the last ten alarms that have occurred in the SERVOPACK.
Note: The following alarms are not displayed in the alarm history: A.E50 (EtherCAT Synchronization Error), A.E60
(Reception Error in EtherCAT Communications), and FL-1 to FL-5.
Preparations
No preparations are required.
Applicable Tools
The following table lists the tools that you can use to display the alarm history and the applica-
ble tool functions.
Operating Procedure
Use the following procedure to display the alarm history.
1.
Click the
Servo Drive Button in the workspace of the Main Window of the Sig-
maWin+.
2.
Select
Display Alarm
in the Menu Dialog Box.
The Alarm Display Dialog Box will be displayed.
3.
Click the
Alarm History
Tab.
The following display will appear and you can check the alarms that occurred in the past.
This concludes the procedure to display the alarm history.
Tool
Function
Reference
Digital Operator
Fn000
Σ
-7-Series Digital Operator Operating Manual
(Manual No.: SIEP S800001 33)
S
Alarm
−
Display Alarm
1. If the same alarm occurs consecutively within one hour, it is not saved in the alarm history.
If it occurs after an hour or more, it is saved.
2. You can clear the alarm history by clicking the
Clear
Button. The alarm history is not
cleared when alarms are reset or when the SERVOPACK main circuit power is turned OFF.
Alarm number: Alarm name
Alarms in order of occurrence
(Older alarms have higher numbers.)
Accumulated operation time
Total operation time to the point at which the alarm
occurred is displayed in increments of 100 ms
from when the control power supply and main cir-
cuit power supply turned ON.
For 24-hour, 365-day operation, measurements
are possible for approximately 13 years.
Information