![YASKAWA PS-A10L Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/yaskawa/ps-a10l/ps-a10l_installation-manual_3247193029.webp)
YASKAWA ELECTRIC
TOBP C730600 48B YASKAWA AC Drive Option 24 V Power Supply Installation Manual
29
6 Verifying Operation
6
Verifying Operation
After properly wiring and installing the 24 V Power Supply Option, use the following
procedure to check for normal operation.
◆
Procedure
1.
Make sure the drive main circuit power is on and 24 V external power is supplied to
the 24 V connector plug. Switch off the main power supply to the drive. The 24 V
external power supply should provide power to the drive’s control circuit.
2.
A red LED on the 24 V Power Supply Option indicates proper operation.
3.
The operator on the drive should display “Uv” for about 10 seconds to indicate an
undervoltage situation.
Note:
If “Uv” does not flash on the display screen, check the wiring. If “Uv” fails to appear on the
operator after confirming proper wiring, the drive or the 24 V Power Supply Option may be
damaged.
◆
Power Supply and the Control Circuit
outlines the various conditions under which the 24 V Power Supply Option provides
power to the control circuit.
Table 7 Power Supply and Control Circuit
Drive Main Circuit
Input Power Supply
Power from 24 V Power
Supply Option
Control Circuit
Operation in Drive
Drive Operation
ON
ON
Normal operation
Possible
ON
OFF
Possible
OFF
ON
Not possible
OFF
OFF
Stop
Not possible
Содержание PS-A10L
Страница 2: ...This Page Intentionally Blank...