7 Transfer of Parameter Settings
32
YASKAWA America, Inc.
PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide
Parameters with Default Value or Setting Range Differences
Some of the setting ranges and default settings for certain parameters differ between V1000 and GA500.
only lists
setting range or default setting differences
between similar V1000 and GA500 parameters.
is not a comprehensive comparison of all parameter differences between V1000 and GA500. For example, GA500
parameters that have no equal in the V1000 are omitted.
Table 15 Parameters with Setting Range or Default Value Differences
Reg.
No.
Param.
No.
Name
Description
Setting Range
Initial Setting
Base Unit
GA500
V1000
GA500
V1000
0x0100 A1-00 Language Selection
Language selection for the digital operator.This
parameter is not reset when the drive is
initialized by parameter A1-03.
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
8: Czech
9: Russian
10: Turkish
11: Polish
12: Greek
0~12
0~7
O2-09
Depend
O2-09
Depend
DEC
0x0101 A1-01
Access Level
Selection
Restricts user access to parameter settings.The
set access level restricts what parameters the
keypad will display, and what parameters the
user can set.
0: Operation Only
1: User Parameters
2: Advanced Level
3: Expert Level
0~3
0~2
2
2
DEC
0x0102 A1-02
Control Method
Selection
Selects the Control Method of the drive.
0: V/f Control without PG
2: Open Loop Vector
5: PM Open Loop Vector
8: EZ Vector
Note: Does not return to the default setting when
the drive is initialized.
0,2,5,6,8
0,
2,
5
O2-09
Depend
0
DEC
0x0103 A1-03 Initialize Parameters
Resets parameters to default values.
0: Keypad or Multi-Speed Selection
1110: User Initialization
2220: 2-Wire initialization
3330: 3-Wire initialization
0,1110,222
0,3330
0,
1110,
2220,
3330,
5550
0
0
DEC
0x0189 B2-01
DC Injection Braking
Start Frequency
Sets the frequency at which DC Injection braking
starts when Ramp to Stop (b1-03 = 0) is selected.
If b2-01< E1-09, DC Injection braking starts at
E1-09.
Note: Zero Speed restrictions are active in Flux
Loop Vector Mode.
0.0~10.0
0.0~10.0
A1-02
Depend
0.5
DEC Hz
0x01BB B2-13
Short Circuit Brake
Time at Stop
Sets the time for Short-Circuit Brake operation at
stop in units of 0.01 s. Used to stop a motor
rotating due to inertia. Disabled when set to 0.00.
0.00~25.50 0.00~25.50
A1-02
Depend
0.50
DEC sec