<3> Values shown are specific to 200 V class drives. Double the value for 400 V class drives. Multiply the value by 2.875 for 600 V class drives.
<4> The display resolution depends on the ND selection. This value has two decimal places (0.01 kW) if the drive is set for a maximum applicable
u
U2: Fault Trace
No.
(Addr.
Hex)
Name
Description
Analog Output
Level
Unit
U2-01
(80)
Current Fault
Displays the current fault.
No signal output
available
–
U2-02
(81)
Previous Fault
Displays the previous fault.
No signal output
available
–
U2-03
(82)
Frequency Reference at
Previous Fault
Displays the frequency reference at the previous fault.
No signal output
available
0.01 Hz
U2-04
(83)
Output Frequency at
Previous Fault
Displays the output frequency at the previous fault.
No signal output
available
0.01 Hz
U2-05
(84)
Output Current at Previous
Fault
Displays the output current at the previous fault.
No signal output
available
U2-07
(86)
Output Voltage at
Previous Fault
Displays the output voltage at the previous fault.
No signal output
available
0.1 Vac
U2-08
(87)
DC Bus Voltage at
Previous Fault
Displays the DC bus voltage at the previous fault.
No signal output
available
1 Vdc
U2-09
(88)
Output Power at Previous
Fault
Displays the output power at the previous fault.
No signal output
available
0.1 kW
U2-11
(8A)
Input Terminal Status at
Previous Fault
Displays the input terminal status at the previous fault. Displayed as in
U1-10.
No signal output
available
–
U2-12
(8B)
Output Terminal Status at
Previous Fault
Displays the output status at the previous fault. Displays the same status
displayed in U1-11.
No signal output
available
–
U2-13
(8C)
Drive Operation Status at
Previous Fault
Displays the operation status of the drive at the previous fault. Displays the
same status displayed in U1-12.
No signal output
available
–
U2-14
(8D)
Cumulative Operation
Time at Previous Fault
Displays the cumulative operation time at the previous fault.
No signal output
available
1 h
U2-15
(7E0)
Soft Starter Speed
Reference at Previous
Fault
Displays the speed reference for the soft starter at the previous fault.
No signal output
available
0.01 Hz
U2-20
(8E)
Heatsink Temperature at
Previous Fault
Displays the temperature of the heatsink when the most recent fault
occurred.
No signal output
available
1 °C
U2-27
(7FA)
Motor Temperature at
Previous Fault (NTC)
Displays the temperature of the motor when the most recent fault occurred. No signal output
available
1 °C
U2-30
(3008)
Date Year at Previous
Fault
Displays the year when the most recent fault occurred.
No signal output
available
–
U2-31
(3009)
Date Month and Day at
Previous Fault
Displays the date and day when the most recent fault occurred.
No signal output
available
–
U2-32
(300A)
Time Hours and Minutes at
Previous Fault
Displays the time when the most recent fault occurred.
No signal output
available
–
B.14 U: Monitors
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
481
B
Parameter List
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......