6.8 Copy Function Related Displays
u
Tasks, Errors, and Troubleshooting
The table below lists the messages and errors that may appear when using the Copy function.
When executing the tasks offered by the Copy function, the operator will indicate the task being performed. When an error
occurs, a code appears on the operator to indicate the error. Note that errors related to the Copy function do not trigger a multi-
function output terminal that has been set up to close when a fault or alarm occurs. To clear an error, simply press any key on
the operator and the error display will disappear.
lists the corrective action that can be taken when an error occurs.
Note:
1.
Whenever using the copy function, the drive should be fully stopped.
2.
The drive will not accept a Run command while the Copy function is being executed.
3.
Parameters can only be saved to a drive when the voltage class, capacity, control mode, and software version match.
Table 6.13 Copy Function Task and Error Displays
Digital Operator Display
Task
CoPy
Writing Parameter Settings (flashing)
Cause
Possible Solutions
Parameters are being written to the drive.
This is not an error.
Digital Operator Display
Task
CPyE
Error Writing Data
Cause
Possible Solutions
Failed writing parameters
Attempt to write parameters again.
Digital Operator Display
Task
CSEr
Copy Unit Error
Cause
Possible Solutions
Hardware fault
Replace the operator or the USB Copy Unit.
Digital Operator Display
Task
dFPS
Drive Model Mismatch
Cause
Possible Solutions
The drives used in the copy and write process are
not the same model.
• The drive from which the parameters were
copied is a different model.
• The drive to be written to is a different model.
• Verify the model number of the drive from which the parameters were copied and the model of
the drive to which those parameters will be written.
• Make sure the two drives are the same model and have the same software version.
Digital Operator Display
Task
End
Task Complete
Cause
Possible Solutions
Finished reading, writing, or verifying parameters. This is not an error.
Digital Operator Display
Task
iFEr
Communication Error
Cause
Possible Solutions
A communication error occurred between the drive
and the operator or the USB copy unit.
Check the cable connection.
A non-compatible cable is being used to connect
the USB Copy Unit and the drive.
Use the cable originally packaged with the USB Copy Unit.
Digital Operator Display
Task
ndAT
Model, Voltage Class, Capacity Mismatch
Cause
Possible Solutions
6.8 Copy Function Related Displays
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
325
6
Troubleshooting
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......