Digital Operator Display
Fault Name
FbH
Excessive PID Feedback
PID feedback input is greater than the level set to b5-36 for longer than the time set to b5-37. Set b5-12
to 2 or 5 to enable fault detection.
Cause
Possible Solution
Parameters are set inappropriately
Check b5-36 and b5-37 settings.
Incorrect PID feedback wiring
Correct the wiring.
There is a problem with the feedback sensor
• Check the sensor on the control side.
• Replace the sensor if damaged.
Digital Operator Display
Fault Name
FbL
PID Feedback Loss
PID feedback loss detection is programmed to trigger a fault (b5-12 = 2 or 5) and the PID feedback level
is below the detection level set to b5-13 for longer than the time set to b5-14.
Cause
Possible Solution
Parameters are set inappropriately
Check b5-13 and b5-14 settings.
Incorrect PID feedback wiring
Correct the wiring.
There is a problem with the feedback sensor
• Check the sensor on the control side.
• Replace the sensor if damaged.
Digital Operator Display
Fault Name
GF
Ground Fault
• A current short to ground exceeded 50% of rated current on the output side of the drive.
• Setting L8-09 to 1 enables ground fault detection.
Cause
Possible Solution
Motor insulation is damaged
• Check the insulation resistance of the motor.
• Replace the motor.
A damaged motor cable is creating a short
circuit
• Check the motor cable.
• Remove the short circuit and reapply power to the drive
• Check the resistance between the cable and the ground terminal .
• Replace the cable.
Excessive leakage current at the drive output
• Reduce the carrier frequency.
• Reduce the amount of stray capacitance.
The drive started to run during a current offset
fault or while coasting to a stop
• Set b3-01 to 1 to enable Speed Search at Start.
• Perform Speed Search 1 or 2 (H1-
oo
= 61 or 62) via one of the external terminals.
Hardware problem
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
Digital Operator Display
Fault Name
LF
Output Phase Loss
• Phase loss on the output side of the drive.
• Setting L8-07 to 1 or 2 enables Phase Loss Detection.
Cause
Possible Solution
The output cable is disconnected
• Check for wiring errors and properly connect the output cable.
• Correct the wiring.
The motor winding is damaged
• Check the resistance between motor lines.
• Replace the motor if the winding is damaged.
The output terminal is loose
• Apply the tightening torque specified in this manual to fasten the terminals.
Wire Gauges and Tightening Torques on page 85
The rated current of the motor being used is
less than 5% of the drive rated current
Check the drive selection and motor capacities.
An output transistor is damaged
If the problem continues, replace the control board or the entire drive. Contact Yaskawa or a Yaskawa
representative for instructions on replacing the control board.
A single-phase motor is being used
The drive cannot operate a single phase motor.
6.4 Fault Detection
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
299
6
Troubleshooting
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......