5.7 H: Terminal Functions
H parameters assign functions to the external terminals.
u
H1: Multi-Function Digital Inputs
n
H1-01 to H1-08: Functions for Terminals S1 to S8
.
No.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to 9F
40 (F)
: Forward Run Command (2-Wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to 9F
41 (F)
: Reverse Run Command (2-Wire sequence)
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to 9F
24: External Fault
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 9F
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to 9F
: Multi-Step Speed Reference 1
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to 9F
: Multi-Step Speed Reference 2
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 9F
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 9F
Table 5.29 Multi-Function Digital Input Terminal Settings
Setting
Function
Page
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference Selection
7
Accel/Decel Time Selection 1
8
Baseblock Command (N.O.)
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Drive Overheat Alarm (oH2)
C
Analog Terminal Input Selection
F
Through Mode
10
Up Command
11
Down Command
12
Forward Jog
13
Reverse Jog
14
Fault Reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer Function Input
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Program Lockout
1E
Reference Sample Hold
20 to 2F External Fault
30
PID Integral Reset
31
PID Integral Hold
Setting
Function
Page
32
Multi-Step Speed Reference 4
34
PID Soft Starter Cancel
35
PID Input Level Selection
40
Forward Run Command (2-Wire sequence)
41
Reverse Run Command (2-Wire sequence)
42
Run Command (2-Wire sequence 2)
43
FWD/REV Command (2-Wire sequence 2)
47
Node Setup
51
Disable Sequence Timers
52
Cancel Active Sequence Timer
60
DC Injection Braking Command
61
External Speed Search Command 1
62
External Speed Search Command 2
63
Field Weakening
65
KEB Ride-Thru 1 (N.C.)
66
KEB Ride-Thru 1 (N.O.)
67
Communications Test Mode
68
High Slip Braking (HSB)
6A
Drive Enabled
75
Up 2 Command
76
Down 2 Command
7A
KEB Ride-Thru 2 (N.C.)
7B
KEB Ride-Thru 2 (N.O.)
A8
Secondary PI Disable (N.O.)
A9
Secondary PI Disable (N.C.)
AA
Secondary PI Inverse Operation
AB
Secondary PI Integral Reset
AC
Secondary PI Integral Hold
AD
Select Secondary PI Parameters
5.7 H: Terminal Functions
YASKAWA SIEP YAIP1U 01C AC Drive - P1000 Technical Manual
205
5
Parameter Details
Содержание P1000
Страница 4: ...This Page Intentionally Blank 4 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 26: ...i 2 General Safety This Page Intentionally Blank 26 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 140: ...4 11 Test Run Checklist This Page Intentionally Blank 140 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 430: ...A 4 Drive Derating Data This Page Intentionally Blank 430 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 504: ...B 16 Defaults by Drive Model This Page Intentionally Blank 504 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 568: ...D 3 UL and CSA Standards This Page Intentionally Blank 568 YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual...
Страница 591: ...Index This Page Intentionally Blank YASKAWA SIEP YAIP1U 01C AC Drive P1000 Technical Manual 591...
Страница 593: ......