2.7 Communications with a Mitsubishi PLC (QnA-compatible 3E Frame Protocol)
Using the MSG-SNDE Function with the MP3000 as the Master
2-147
Ethernet Communications
Device Memory and Corresponding Registers in the MP3000
The following tables show the relationship between registers in the MP3000 and device memory in the
Mitsubishi Q/QnA-series PLC. Use device addresses within the ranges listed in the tables below according
to the conditions of the Mitsubishi Q/QnA-series PLC slave.
A read or write command is automatically generated by specifying the address in the MP3000 that corre-
sponds to the device to be read from or written to in the Mitsubishi Q/QnA-series PLC.
To read data from or write data to the address specified in PARAM14 and PARAM15 of the MSG-SNDE
function, specify the register address in the MP3000 that corresponds to the device address in the Mitsubi-
shi Q/QnA-series PLC. Select whether to read or write by setting the function code in parameter
PARAM12 for the MSG-SNDE function.
* Access file registers by using the ZR notation for accessing continuous file registers. The R* notation cannot be used.
Writing Data into D10000
Set PARAM14 and PARAM15 to the MW10000 register in the MP3000 that corresponds to
D10000, and set PARAM12 to 0B or 10 hex.
Reading Data from M001000
Set PARAM14 and PARAM15 to the MB005748 register in the MP3000 that corresponds to
M001000, and set PARAM12 to 01 hex.
Note: To access a relay, specify a bit address in PARAM14 and PARAM15. For MB005748, this would
be 9192 decimal.
Bit Device Conversion Table
Device Name
Data Range
Notation
Mitsubishi PLC
MP3000
Input Relays
Hexadecimal
X000000 to X001FFF
MB000000 to MB00511F
Output Relays
Hexadecimal
Y000000 to Y001FFF
MB000000 to MB00511F
Internal Relays
Decimal
M000000 to M008191
MB005120 to MB01023F
Latch Relays
Decimal
L000000 to L008191
MB010240 to MB01535F
Step Relays
Decimal
S000000 to S008191
MB015360 to MB02047F
Link Relays
Hexadecimal
B000000 to B001FFF
MB020480 to MB02559F
Annunciators
Decimal
F000000 to F002047
MB025600 to MB02687F
Link Special Relays
Decimal
SM000000 to SM002047
MB026880 to MB02815F
Timer Contacts
Decimal
TS000000 to TS002047
MB005120 to MB00639F
Timer Coils
Decimal
TC000000 to TC002047
MB006400 to MB00767F
Counter Contacts
Decimal
CS000000 to CS001023
MB007680 to MB00831F
Counter Coils
Decimal
CC000000 to CC001023
MB008320 to MB00895F
Word Device Conversion Table
Device Name
Data Range
Notation
Mitsubishi PLC
MP3000
Data Registers
Decimal
D000000 to D012287
MW00000 to MW12287
Link Registers
Hexadecimal
W000000 to W001FFF
MW12288 to MW20479
Link Special Registers
Decimal
SD000000 to SD002047
MW20480 to MW22527
File Registers
Hexadecimal
ZR000000 to ZR007FFF
∗
MW22528 to MW55295
Timer Registers
Decimal
TN000000 to TN002047
MW00000 to MW02047
Counter Registers
Decimal
CN000000 to CN001023
MW02048 to MW03071
Example
Example