6.2 Drive Alarms, Faults, and Errors
168
YASKAWA EUROPE SIEP
YASKAWA AC Drive L1000V Technical Manual
n
Minor Faults and Alarms
for an overview of possible alarm codes. Conditions such as overvoltages can trip faults and alarms.
It is important to distinguish between faults and alarms to determine the proper corrective actions. When the drive detects
an alarm, the ALM indicator LED blinks and the alarm code display flashes. Most alarms trigger a digital output
programmed for alarm output (H2-
= 10). A fault (not an alarm) is present if the ALM LED lights without blinking.
for information on fault codes.
Table 6.3 Minor Fault and Alarm Displays
Digital Operator Display
Name
Minor Fault Output
(H2-
= 10)
Page
LED Operator
LCD Operator
bb
Drive Baseblock
No output
boL
Braking Transistor Overload
YES
CrST
Cannot Reset
YES
dEv
Speed Deviation (simple PG feedback control modes)
YES
EF
Up/Down Command Error
YES
to
EF3 to EF7
External Fault (input terminal S3 to S7)
YES
Hbb
Safe Disable Signal Input
L8-88 = 0: YES
L8-88 = 1: No (default)
HbbF
Safe Disable Circuit Fault Signal Input
L8-88 = 0: YES
L8-88 = 1: No (default)
HCA
High Current Alarm
YES
LT-1
Cooling Fan Maintenance Time
No output
LT-2
Capacitor Maintenance Time
No output
LT-3
Soft Charge Bypass Relay Maintenance Time
No output
LT-4
IGBT Maintenance Time (90%)
No output
oH
Heatsink Overheat
YES
oL3
Overtorque Detection 1
YES
oL4
Overtorque Detection 2
YES
oS
Overspeed (for Control Mode with Encoder)
YES
ov
DC Bus Overvoltage
YES
PGo
Encoder Disconnected (for Control Mode with Encoder)
YES
TrPC
IGBT Maintenance Time (90%)
YES
UL3
Undertorque Detection 1
YES
UL4
Undertorque Detection 2
YES
Uv
Undervoltage
YES
voF
Output Voltage Detection Error
YES
Содержание Lift Inverter L1000V
Страница 4: ...4 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 28: ...1 4 Component Names 28 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 62: ...3 10 Wiring Checklist 62 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 100: ...4 8 Verifying Parameter Settings and Backing Up Changes 100 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 162: ...5 12 U Monitor Parameters 162 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 266: ...C 5 EN81 1 Conform Circuit with one Motor Contactor 266 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 279: ...8 YASKAWA EUROPE SIEP YASKAWA AC Drive L1000V Technical Manual...
Страница 281: ...10 YASKAWA ELECTRIC SIEP C710616 33C YASKAWA AC Drive L1000A Technical Manual...