NOTICE
Damage to Equipment. When you use the drive with a non-grounding, high-resistance grounding, or
asymmetric-grounding network, put the EMC Filter screw or screws in the OFF position to disable the built-in EMC filter. If you
do not disable the built-in EMC filter, it will cause damage to the drive.
If you lose an EMC filter switch screw, use
to find the correct replacement screw and install the new
screws with the correct tightening torque.
NOTICE
Only use the screws specified in this manual. If you use screws that are not approved, it can cause damage to
the drive.
Table 1.12 Screw Sizes and Tightening Torques
Model
Screw Size
Tightening Torque
N
∙
m
4012 - 4056
M4 × 20
1.0 - 1.3
◆
United Kingdom Conformity Assessed Marking
Figure 1.15 UKCA Mark
Information about Manufacturer
YASKAWA ELECTRIC CORPORATION (Manufacturer)
2-1 Kurosaki-shiroishi, Yahatanishi-Ku, Kitakyushu 806-0004 Japan
http://www.yaskawa.co.jp
YASKAWA EUROPE GmbH (EU Contact)
Philipp-Reis-Str. 6, 65795 Hattersheim am Main, Germany
http://www.yaskawa.eu.com/
YASKAWA ELECTRIC (UK) LTD (UK Contact)
1 Hunt Hill, Glasgow G68 9LF, United Kingdom
https://www.yaskawa.co.uk/
The UKCA Mark identifies that the product meets environmental and safety standards in the United Kingdom
(Statutory Instruments).
Products manufactured, sold, or imported in Great Britain (England, Wales, and Scotland) must display the
UKCA Mark.
United Kingdom standards include the Supply of Machinery (Safety) Regulations (Machinery) for machine
manufacturers, the Electrical Equipment (Safety) Regulations (Low voltage) for electronics manufacturers, and
the Electromagnetic Compatibility Regulations (EMC) for controlling noise.
This product displays the UKCA Mark in accordance with the Machinery Directive, the Low Voltage Directive,
and the EMC Directive.
Table 1.13 Designated Standards
Statutory Instruments
Designated Standards
Supply of Machinery (Safety) Regulations
S.I. 2008 No. 1597
EN ISO 13849-1:2015 (PL e (Cat.3))
IEC/EN IEC 62061 (Maximum SIL3)
EN 61800-5-2 (SIL3)
Electrical Equipment (Safety) Regulations
S.I. 2016 No. 1101
EN 61800-5-1
Electromagnetic Compatibility Regulations
S.I. 2016 No. 1091
EN 61800-3
Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic
Equipment Regulations
S.I. 2012 No. 3032
EN IEC 63000
*1
Refer to
“
UK Declaration of Conformity
”
for the year of the Designated Standards.
The customer must display the UKCA Mark on the final device containing this product. Customers must verify
that the final device complies with UK standards.
Содержание LA700 Series
Страница 316: ...9 316 YASKAWA TOMPYEULA7002A LA700 Series Installation and Operation Instruction 9 3 9 4 A B C 5 D 9 4...
Страница 322: ...9 322 YASKAWA TOMPYEULA7002A LA700 Series Installation and Operation Instruction 9 7 1 1 2 B1 B2...
Страница 324: ...9 324 YASKAWA TOMPYEULA7002A LA700 Series Installation and Operation Instruction 9 9 1 MEMOBUS Modbus H5 11 1...