YASKAWA
SIEPYEULA5001C LA500 Technical Manual
12.4
d: References
d parameters [References]
set the frequency reference input method and dead band range. They also set torque
control, field weakening, and field forcing functions.
WARNING!
Sudden Movement Hazard. Use fast stop circuits to safely and quickly stop the drive. After you wire the fast stop
circuits, you must check their operation. Test the operation of the fast stop function before you use the drive. If you do not test
the fast stop circuit before you operate the drive, it can cause serious injury or death.
WARNING!
Sudden Movement Hazard. You must install external safety circuitry. The drive does not have protection against
accidental load drops. Install electrical and/or mechanical safety circuit mechanisms that are isolated from the drive circuitry. If
you do not use external safety circuitry, the drive could drop the load and cause serious injury or death.
◆
d1: Speed Reference
■
d1-01: Speed Reference 1
No.
(Hex.)
Name
Description
Default
(Range)
d1-01
(0280)
RUN
Speed Reference 1
Sets the Speed reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 120.00 Hz)
■
d1-02: Speed Reference 2
No.
(Hex.)
Name
Description
Default
(Range)
d1-02
(0281)
RUN
Speed Reference 2
Sets the speed reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 120.00 Hz)
■
d1-03: Speed Reference 3
No.
(Hex.)
Name
Description
Default
(Range)
d1-03
(0282)
RUN
Speed Reference 3
Sets the Speed reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 120.00 Hz)
■
d1-04: Speed Reference 4
No.
(Hex.)
Name
Description
Default
(Range)
d1-04
(0283)
RUN
Speed Reference 4
Sets the Speed reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 120.00 Hz)
■
d1-05: Speed Reference 5
No.
(Hex.)
Name
Description
Default
(Range)
d1-05
(0284)
RUN
Speed Reference 5
Sets the Speed reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 120.00 Hz)
■
d1-06: Speed Reference 6
No.
(Hex.)
Name
Description
Default
(Range)
d1-06
(0285)
RUN
Speed Reference 6
Sets the Speed reference in the units from
o1-03 [Frequency Display Unit Selection]
.
0.00 Hz
(0.00 - 120.00 Hz)
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
V/f
OLV
Содержание LA500
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 10: ...10 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 18: ...i 3 Glossary 18 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 24: ...1 2 Features and Advantages of Control Methods 24 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 38: ...2 8 Install the Keypad in a Control Panel or Another Device 38 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 74: ...3 14 Wiring Checklist 74 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 134: ...5 5 EN81 20 Compliant Circuit with no Motor Contactor 134 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 135: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 135 6 Network Communications 6 1 MEMOBUS Modbus Communications 136...
Страница 164: ...6 1 MEMOBUS Modbus Communications 164 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 202: ...7 10 Troubleshooting Without Fault Display 202 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 218: ...8 6 Storage Guidelines 218 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 234: ...10 6 Peripheral Devices and Options 234 YASKAWA SIEPYEULA5001C LA500 Technical Manual...
Страница 375: ...YASKAWA SIEPYEULA5001C LA500 Technical Manual 375...