
EN-15
3. The Class 2 power supply must be used for the control circuits. See table below.
4. Varispeed L7 is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrcal
amperes, 240 VAC maximum (200 V Class) and 480 VAC maximum (400 V Class).
Use a circuit breaker or fuses having an interrupting rating not less than 100,000 RMS symmetrical
ampers, 600 VAC maximum.
5. Motor Overheat Protection: To protect the motor from overheating, set the E2-01 parameter in the Inverter
to the same value as the level of the motor rated current.
For Meeting CE Marking
For precautions on the CE Marking, refer to the instruction manual.
2055
60-12 (2perPh)
150-10 (2perPh)
4022
14-6
14-6
4030
22-6
22-6
4037
38-8
38-8
4045
60-8
60-8
4055
60-8
60-8
Input/Output
Terminal Power
Supply
Multi-func-
tion contact
inputs
S1, S2, S3, S4, S5
S6, S7, SC, BB,
LVLC power supply when using in-
ternal power supply. Class 2 pow-
er supply when using external
power supply
Analog in-
puts
+V, A1, AC
Inverter Model
CIMR-L7
∗
JST Kit P/N
Input
Output
BB1