5.10 o: Operator Related Settings
♦ o3: Copy Function
These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory o f the digital operator to facilitate the transfer o f those settings to other drives that are the same model, capacity,
and same control mode setting. Refer to
Copy Function Related Displays on page 264
for a description o f errors and
displays.
■ o3-01 Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
Name
Setting Range
Default
o3-01
Copy Function Selection
0 to 3
0
0: Copy Select (no function)
1: INV --> OP READ
Copies all parameters from the drive to the digital operator.
Note: The copy protection for the digital operator is enabled by default. Set o3-01 to 1 to unlock copy protection.
2: OP --> INV W RITE
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
3: OP<-->INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
■ o3-02 Copy Allowed Selection
Allows and restricts the use of the Copy function.
No.
Name
Setting Range
Default
o3-02
Copy A llow ed Selection
0 or 1
0
0: Disabled
1: Enabled
♦ o4: Maintenance Monitor Settings
■ o4-01: Cumulative Operation Time Setting
Sets the cumulative operation time of the drive. The user can also manually set this parameter to begin keeping track of
operation time from some desired value. Total operation time can be viewed in monitor U4-01.
Note: The value in o4-01 is set in 10 h units. For example, a setting o f 30 will set the cumulative operation time counter to 300 h. 300 h
will also be displayed in m onitor U4-01.
No.
Name
Setting Range
Default
o4-01
Cumulative Operation Time Setting
0 to 9999
0
■ o4-02: Cumulative Operation Time Selection
Selects the conditions for how the drive keeps track of its total operation time. This time log can be viewed in U4-01.
No.
Name
Setting Range
Default
o4-02
Cumulative Operation Time Selection
0 or 1
1
Setting 0: Power on time
The drive logs the time it is connected to a power supply, regardless if the motor is running or not.
Setting 1: Run time
The drive logs the time that the output is active. This includes whenever the Up/Down command is active (even if the
motor is not rotating) and when there is voltage output.
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual
215
P
a
ra
m
e
te
r
D
e
ta
il
s
Содержание L1000A Series
Страница 68: ...3 11 Wiring Checklist 72 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 264: ...6 8 Diagnosing and Resetting Faults 268 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 308: ...8 5 Installing Peripheral Devices 312 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 316: ...A 5 Drive Derating Data 320 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...
Страница 390: ...C 12 Self Diagnostics 394 YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual...