3  Electrical Installation

26

 

YASKAWA ELECTRIC

 TOEP C710616 38H YASKAWA AC Drive-L1000A Quick Start Guide

Figure 7  

Figure 6  Drive Standard Connection Diagram (example: CIMR-LU2

0033)

<1> Remove the jumper when installing a DC link choke. Models CIMR-LU2

0085 through 2

0415, 4

0045 

through 4

0605, and 5

0032 through 5

0200 come with a built-in DC link choke.

<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an 

optional regenerative converter or dynamic braking option. 

<3> Set up a thermal relay sequence to disconnect drive main power in the event of an overheat condition on the 

dynamic braking option.

<4> Self-cooling motors do not require the same wiring necessary for motors with separate cooling fans.

Shield ground terminal

+

+

DM

DM

H

1

H

2

HC

<10>

R/L1

S/L2

T/L3

Fuse

MC

2MCCB

MB

ON

OFF

THRX

SA

1

2

TRX

MC MA

TRX

Fault relay
contact

Braking resistor unit
Thermal relay trip contact

MC

MC

SA

SA

THRX

ELCB (MCCB)

R

T

S

Three-phase
power supply

200 to 240

 V

50

/

60

 Hz

<14>

2MCCB

r1

s1

t1

MC

Wiring sequence should shut off 
power to the drive when a fault 
output is triggered.

If running from a 400 V power 
supply or 600 V power supply, a 
step-down transformer is needed 
to reduce the voltage to 200 V.

P1

P2

C1

C2

Photo Coupler 1
(During Frequency Output)

Photo Coupler 2
(not used)

Digital output
5 to 48 Vdc
2 to 50 mA

(default setting)

+

+

+

+

Terminals -, +1, +2, B1, B2 are 
for connecting options. Never 
connect power supply lines to 
these terminals

DC link choke

(option)

U

X

Thermal relay

(option)

+

+

+

+

+

U

X

S

1

S

2

S

3

S

4

S

5

S

6

S

7

A

1

A

2

0 V

AC

R

R

S

S

IG

Drive

B

1

1

2

B

2

2 k

Ω

S

8

SC

0 V

FM

AM

AC

E (G)

<1>

<8>

<8>

<9>

<2><3>

+

24 V

+

V

MA

M

1

M

2

MB

MC

Jumper

Braking resistor
(option)

Up command / Stop

External Fault

Fault Reset

Multi-step Speed 1

Not Used

Multi-function 

digtial inputs

(default setting)

Sink / Source mode 
selection wire jumper
(default: Sink)

Multi-function 
analog inputs

Power 10.5 Vdc, max. 20 mA

Analog Input 1 (Speed Bias)
-10 to +10 Vdc (20 k

Ω

)

Analog Input 2 (Not used)
-10 to +10 Vdc  (20 k

Ω

)

V

Power supply, -10.5 Vdc, max. 20 mA

MEMOBUS/Modbus 

comm. RS485/422

max. 115.2 kBps

Termination resistor

(120 

Ω

, 1/2 W)

DIP 
Switch S2

Fault relay output
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

Multi-function relay output (Brake Release Command)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

Multi-function analog output 1
(Output Speed)
-10 to +10 Vdc (2mA)

Multi-function analog output 2
(Output Current)
-10 to +10 Vdc (2mA)

Main Circuit

Control Circuit

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

M

3

M

4

Multi-function relay output (Motor Contactor Close Command)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

M

5

M

6

Multi-function relay output (Drive Ready)
250 Vac, max. 1 A
30 Vdc, max 1 A
(min. 5 Vdc, 10 mA)

SP

SN

FM

+

AM

<7>

Down command / Stop

Multi-step Speed 2

Multi-step Speed 3

FE

SD

NC

a+

a-

b-

z-

b+

z+

IP
IG

IP12

IP5

IG

SG

TB2

A pulse monitor signal

B pulse monitor signal

Z pulse monitor signal

CN3 

PG

<4>

<2>

A+
A

B

Z

B+

Z+

TB1

PG

X3

CN5-C

CN5-B

CN5-A

Option card
connector

M

U/T

1

V/T

2

W/T

U/T1

V/T2

W/T3

3

Ground

Cooling fan

<6>

<5>

M

r1

s1

t1

FU

FV

FW

<12>

<13> <14>

<15>

EDM (Safety Electronic Device Monitor)

Safe Disable inputs

<11>

YEA_common

TOEP_C710616_38H_7_0.book  26 ページ  2015年11月11日 水曜日 午後7時40分

Содержание L1000A Series

Страница 1: ...50 HP To properly use the product read this manual thoroughly and retain for easy reference inspection and maintenance Ensure the end user receives this manual Type CIMR LU A COSMOS CI Receiving Mecha...

Страница 2: ...sion of Yaskawa No patent liability is assumed with respect to the use of the information contained herein Moreover because Yaskawa is constantly striving to improve its high quality products the info...

Страница 3: ...r simplified elevator system setup Control Mode Input parameters during tuning Tuning process Parameters set after Auto Tuning A1 02 7 T2 04 Motor Rated Power T2 05 Motor Rated Voltage T2 06 Motor Rat...

Страница 4: ...in parameter S Default 0 5 sec Range 0 0 to 3 0 sec S5 18 6DDH Brake torque check fall time Default 0 5 sec Range 0 0 to 3 0 sec S5 19 6DEH Brake torque check operating time which the brake torque is...

Страница 5: ...rs Refer to Types of Auto Tuning on page 73 Maintenance Check Using Drive Monitors Use drive monitors to check fans capacitors and other components may require maintenance Refer to Performance Life Mo...

Страница 6: ...4 YASKAWA ELECTRIC TOEP C710616 38H YASKAWA AC Drive L1000A Quick Start Guide TOEP_C710616_38H_7_0 book 4...

Страница 7: ...nnect to a PC 55 Wiring Checklist 56 4 Start Up Programming Operation 58 Using the Digital Operator 58 The Drive and Programming Modes 63 Start Up Flowcharts 66 Setup Procedure for Elevator Applicatio...

Страница 8: ...Motor Parameters 175 F Option Settings 179 H Multi Function Terminals 183 L Protection Functions 190 n Advanced Performance Set Up 195 o Operator Related Parameters 197 S Elevator Parameters 200 T Mo...

Страница 9: ...MEMOBUS Modbus specifications Use this manual to expand drive functionality and to take advantage of higher performance features General Precautions The diagrams in this manual may be indicated withou...

Страница 10: ...responsible for any injuries or equipment damage resulting from failure to heed the warnings in this manual Electrical Shock Hazard Do not connect or disconnect wiring or service the drive while the...

Страница 11: ...e has fully stopped a load install a switch to the drive output side to disconnect the motor and the drive Do not allow an external force to rotate the motor beyond the maximum allowable speed or to r...

Страница 12: ...in death or serious injury by fire from overheating resistors Do not use improper combustible materials Failure to comply could result in death or serious injury by fire Attach the drive to metal or...

Страница 13: ...th a default carrier frequency of 2 kHz CIMR LU2 0346 2 0415 5 kHz CIMR LU4 0112 to 4 0216 or 8 kHz CIMR LU2 0008 to 2 0115 4 0005 to 4 0091 and a 150 peak current Yaskawa recommends lowering the carr...

Страница 14: ...equipment such as braking resistors Failure to comply may cause resistor overheating fire and injury to personnel NOTICE To get the full performance life out of the electrolytic capacitors and circui...

Страница 15: ...tion and Shock The drive allows selection of high carrier PWM control and low carrier PWM control Selecting high carrier PWM can help reduce motor oscillation If resonance occurs install shock absorbi...

Страница 16: ...fter disconnecting power supply To conform to requirements make sure to ground the supply neutral for 400V class After opening the manual switch between the drive and motor please wait 5 minutes befor...

Страница 17: ...mon Quick Start Guide Design revision order PRG 7010 IND CONT EQ 7J48 B CIMR LU2A0018DAA REV A CIMR LU2A0018DAA AC3PH 200 240V 50 60Hz 18 9A AC3PH 0 240V 0 200Hz 17 5A 3 5 kg E131457 IP00 PASS MODEL C...

Страница 18: ...022 20 22 2 0060 20 60 4 0031 20 31 5 0027 25 27 2 0075 25 75 4 0039 25 30 39 5 0032 25 30 32 2 0085 30 85 4 0045 25 30 45 5 0041 40 41 2 0115 40 115 4 0060 40 60 5 0052 50 60 52 2 0145 50 145 4 0075...

Страница 19: ...he temporary cover before startup as the cover will reduce ventilation and cause the drive to overheat Environment Conditions Installation Area Indoors Ambient Temperature IP00 enclosure with top prot...

Страница 20: ...t exceed 40 C 104 F Installation Orientation Install the drive upright as illustrated in Figure 2 to maintain proper cooling Refer to Mechanical Installation on page 17 for details on installing the d...

Страница 21: ...2 0 2 G while it is suspended by the wires Do not overturn the drive while it is suspended by the wires Do not leave the drive suspended by the wires for long periods of time Horizontal Suspension of...

Страница 22: ...0 20 M5 4 8 8 0033 140 5 51 260 10 24 167 6 57 122 4 80 248 9 76 6 0 24 55 2 17 5 0 20 M5 4 8 8 0047 180 7 09 300 11 81 187 7 36 160 6 30 284 11 18 8 0 31 75 2 95 5 0 20 M5 5 6 12 3 0060 220 8 66 350...

Страница 23: ...5 2 17 5 0 20 M5 3 9 8 6 0024 180 7 09 300 11 81 167 6 57 160 6 30 284 11 18 8 0 31 55 2 17 5 0 20 M5 5 4 11 9 0031 180 7 09 300 11 81 187 7 36 160 6 30 284 11 18 8 0 31 75 2 95 5 0 20 M5 5 7 12 6 003...

Страница 24: ...160 6 30 284 11 18 8 0 31 75 2 95 5 0 20 M5 5 7 12 6 0022 220 8 66 350 13 78 197 7 76 192 7 56 335 13 19 8 0 31 78 3 07 5 0 20 M6 8 3 18 3 0027 220 8 66 350 13 78 197 7 76 192 7 56 335 13 19 8 0 31 7...

Страница 25: ...e L1000A Quick Start Guide 23 Mechanical Installation 2 IP00 Enclosure Drive t2 Figure 1 W1 4 d H1 H H2 Max W2 W t2 t1 D1 D D1 D H1 H2 H 4 d W1 W Max W2 t1 Figure 2 D1 D W H1 H2 H 6 d t2 Figure 3 t1 W...

Страница 26: ...00 19 69 800 31 50 350 13 78 370 14 57 10 0 39 773 30 43 13 0 51 130 5 12 4 5 0 18 4 5 0 18 M12 96 211 6 0260 500 19 69 800 31 50 350 13 78 370 14 57 10 0 39 773 30 43 13 0 51 130 5 12 4 5 0 18 4 5 0...

Страница 27: ...T1 V T2 W T3 3 2 1 B1 B2 from all other wiring Place motor wiring within its own conduit or cable tray with appropriate divider and use shielded motor cable where appropriate Improper wiring practices...

Страница 28: ...option U X Thermal relay option U X S1 S2 S3 S4 S5 S6 S7 A1 A2 0 V AC R R S S IG Drive B1 1 2 B2 2 k S8 SC 0 V FM AM AC E G 1 8 8 9 2 3 24 V V MA M1 M2 MB MC Jumper Braking resistor option Up command...

Страница 29: ...ut Terminals H1 H2 DM and DM on 600 V class models are designed to the functionality but are not certified to IEC EN 61800 5 2 ISO EN 13849 Cat 3 IEC EN 61508 SIL2 Insulation coordination class 1 12 M...

Страница 30: ...propriate Improper wiring practices could result in malfunction of drive due to electrical interference Figure 7 Drive main circuit configurations CIMR LU2 0008 to 2 0075 CIMR LU4 0005 to 4 0039 CIMR...

Страница 31: ...8 Figure 8 Removing the Terminal Cover 2 Push in on the tab located on the bottom of the terminal cover and gently pull forward to remove the terminal cover Figure 9 Figure 9 Removing the Terminal Co...

Страница 32: ...hielded motor cable where appropriate Improper wiring practices could result in malfunction of drive due to electrical interference Reattach the terminal cover after completing the wiring to the drive...

Страница 33: ...to remove it from the drive Figure 14 Figure 14 Removing the Digital Operator Reattaching the Digital Operator Insert the digital operator into the opening in the top cover while aligning it with the...

Страница 34: ...e front cover then swing the left side towards you as shown in Figure 18 until the cover comes off Figure 18 Figure 18 Remove the Front Cover Models CIMR LU2 0085 to 2 0415 4 0045 to 4 0605 and 5 0032...

Страница 35: ...to 2 0415 4 0045 to 4 0605 and 5 0032 to 5 0200 1 Slide the front cover so the hooks on the top connect to the drive Figure 19 Figure 19 Reattach the Front Cover Models CIMR LU2 0085 to 2 0415 4 0045...

Страница 36: ...ctions can loosen over time Improper wiring practices could result in drive malfunction due to loose terminal connections NOTICE Do not switch the drive input to start or stop the motor Frequently swi...

Страница 37: ...nsure that the wiring does not touch nearby terminals or the surrounding case Insulation Barrier Insulation barriers are packaged with drive models CIMR LU4A0370 through 4A0605 to provide added protec...

Страница 38: ...t of voltage drop Line drop voltage V wire resistance km wire length m current A 10 3 Refer to instruction manual TOBP C720600 0 for braking transistor option or braking resistor option wire gauges Us...

Страница 39: ...V T2 W T3 10 14 to 10 1 2 14 to 10 B1 B2 14 to 10 10 1 14 to 10 2 0018 R L1 S L2 T L3 10 18 to 10 M4 1 2 to 1 5 10 6 to 13 3 U T1 V T2 W T3 10 18 to 10 1 2 12 to 10 B1 B2 14 to 10 10 1 12 to 10 2 0025...

Страница 40: ...to 2 9 to 11 79 7 to 97 4 2 0180 R L1 S L2 T L3 1 0 2P 1 0 to 4 0 M10 18 to 23 159 to 204 U T1 V T2 W T3 1 0 2P 1 0 to 4 0 1 1 to 4 0 3 1 0 to 4 0 4 4 to 1 0 9 to 11 79 7 to 97 4 2 0215 R L1 S L2 T L...

Страница 41: ...w Size Tightening Torque N m lb in 4 0005 4 0006 4 0007 R L1 S L2 T L3 14 14 to 10 M4 1 2 to 1 5 10 6 to 13 3 U T1 V T2 W T3 14 14 to 10 1 2 14 to 10 B1 B2 14 to 10 10 1 14 to 10 4 0009 R L1 S L2 T L3...

Страница 42: ...250 1 3 to 1 0 3 6 to 1 0 4 6 to 4 4 0091 R L1 S L2 T L3 1 0 6 to 250 M8 9 to 11 79 7 to 97 4 U T1 V T2 W T3 1 6 to 250 1 3 to 1 0 3 4 to 1 0 4 6 to 4 4 0112 R L1 S L2 T L3 3 0 1 0 to 4 0 M10 18 to 23...

Страница 43: ...300 2P 4 0 to 300 1 3 0 to 300 3 3 0 to 300 1 1 to 3 0 4 0450 R L1 S L2 T L3 3 0 4P 3 0 to 300 M12 32 to 40 283 to 354 U T1 V T2 W T3 3 0 4P 3 0 to 300 1 1 0 to 300 3 1 0 to 300 1 0 1 0 to 300 4 0605...

Страница 44: ...6 5 4 to 6 0 47 8 to 53 1 5 0022 5 0027 R L1 S L2 T L3 6 6 to 4 M6 5 4 to 6 0 47 8 to 53 1 U T1 V T2 W T3 6 6 to 4 1 2 6 to 4 B1 B2 10 to 8 M5 2 7 to 3 0 23 9 to 26 6 6 10 to 6 M6 5 4 to 6 0 47 8 to 5...

Страница 45: ...0 2 0 to 300 M10 18 to 23 159 to 204 U T1 V T2 W T3 3 0 2 0 to 300 1 3 0 to 4 0 3 1 0 to 2 0 3 4 to 300 5 0172 R L1 S L2 T L3 300 2 0 to 600 M12 32 to 40 283 to 354 U T1 V T2 W T3 250 2 0 to 600 1 2 0...

Страница 46: ...ring practices could result in malfunction of drive due to electrical interference NOTICE Equipment Hazard Comply with proper wiring practices The motor may run in reverse if the phase order is backwa...

Страница 47: ...filter the leakage current exceeds 3 5 mA Therefore according to IEC EN 61800 5 1 at least one of the conditions below must be satisfied a The cross section of the protective earthing conductor must...

Страница 48: ...o the multi function digital inputs S3 to S8 multi function digital outputs M1 to M6 multi function photocoupler outputs P1 C1 P2 C2 multi function analog inputs A1 A2 and multi function analog monito...

Страница 49: ...S4 Multi function input 2 Fault Reset S5 Multi function input 3 Multi Step Speed Reference 1 S6 Multi function input 4 Multi Step Speed Reference 2 S7 Multi function input 5 Multi Step Speed Referenc...

Страница 50: ...gure 23 when driving a reactive load such as a relay coil Make sure the diode rating is greater than the circuit voltage 3 Terminals H1 H2 DM and DM on 600 V class models are designed to the functiona...

Страница 51: ...ng DIP switch S2 to the ON position No Signal Name Function Signal Level MEMOBUS Modbus Communication 1 R Communications input MEMOBUS Modbus communication Use an RS 485 or RS 422 cable to connect the...

Страница 52: ...ire ends with insulated sleeves before connecting to the drive Refer to Table 18 for dimensions Figure 25 Figure 25 Ferrule Dimensions Table 18 Ferrule Terminal Types and Sizes Terminal Block Terminal...

Страница 53: ...d of shielded cable to the appropriate ground terminal Improper equipment grounding could result in drive or equipment malfunction or nuisance trips NOTICE Separate wiring for output terminals MA MB M...

Страница 54: ...xceed 50 meters 164 ft for the control line between the drive and the operator when using an analog signal from a remote source to supply the frequency reference Failure to comply could result in poor...

Страница 55: ...h several switches used to adapt the drive I Os to the external control signals Figure 28 shows the location of these switches Refer to Control I O Configuration on page 54 for setting instructions Fi...

Страница 56: ...s SC and SP or SC and SN to select between Sink mode Source mode or external power supply for the digital inputs S1 to S8 as shown in Table 19 Default Sink mode internal power supply NOTICE Damage to...

Страница 57: ...arately After connecting the drive to a PC Yaskawa DriveWizard Plus software can be used to monitor drive performance and manage parameter settings Contact Yaskawa for more information on DriveWizard...

Страница 58: ...sider the amount of voltage drop when selecting wire gauges Increase the wire gauge when the voltage drop is greater than 2 of motor rated voltage Ensure the wire gauge is suitable for the terminal bl...

Страница 59: ...k Start Guide 57 Electrical Installation 3 25 Analog signal line wiring should not exceed 50 m 164 ft 26 Safe Disable input wiring should not exceed 30 m 98 ft 27 Check the logic of the Safe Disable m...

Страница 60: ...on when the drive is operating the motor flashes during deceleration to stop or when the speed reference is 0 flashes quickly the drive is disabled by a DI the drive was stopped using a fast stop DI...

Страница 61: ...ting Mode A TUNE Displayed during Auto Tuning SETUP Displayed when in Setup Mode 2 Mode Display Area DRV Displayed when in Drive Mode PRG Displayed when in Programming Mode 3 Ready Rdy Indicates the d...

Страница 62: ...ayed when in Drive Mode 2 Displayed when in Drive Mode and Monitor Mode Power off Checks Description Power supply voltage Ensure the power supply voltage is correct on the supply side of the disconnec...

Страница 63: ...g Quickly Off When source of the Up Down command is assigned to the digital operator LOCAL Up Down command to be given from a device other than the digital operator REMOTE During run During decelerati...

Страница 64: ...DRV Speed Ref OPR Rdy MONITR Speed Ref 1 U1 01 000 00 3 4 0 00 50 00 0 00 DRV FWD Rdy MODE U1 01 0 00 U1 02 0 00 U1 03 0 00A DRV Monitor Menu Rdy MODE PRG Modified Consts HELP HELP DATA MODE PRG Quick...

Страница 65: ...t to 2 50 seconds Step Display Result 1 Turn on the power to the drive The initial display appears 2 Press or until the Parameter Setting Mode screen appears 3 Press to enter the parameter menu tree 4...

Страница 66: ...tically returns to the screen shown in Step 4 12 Press as many times as necessary to return to the initial display Step Display Result PRMSET C1 02 002 50 sec 0 0 600 00 1 50 sec PRG Decel Ramp 1 FWD...

Страница 67: ...Group is accessed to change b1 01 from 0 to 1 This changes the source of the speed reference from the digital operator to the control circuit terminals Figure 33 Setup Group Example 1 Use the up and...

Страница 68: ...ator Start Up Flowcharts This section covers basic setup for the drive including Auto Tuning procedures and corresponding flowcharts Follow the flowchart that matches the motor used in your applicatio...

Страница 69: ...Analog Input Digital operator b1 01 0 Speed selection by digital inputs Assign functions to the analog digital I O terminals using parameters H1 H2 H3 and H4 Set up Acceleration deceleration ramp C1 J...

Страница 70: ...WARNING Sudden Movement Hazard Operating a drive with untested emergency circuits could result in death or serious injury Always check the operation of drive fast stop circuits and any additional eme...

Страница 71: ...e indicator LED will extinguish when the DC bus voltage is below 50 Vdc To prevent electric shock wait at least five minutes after all indicators are OFF and measure the DC bus voltage level to confir...

Страница 72: ...lect Stationary Auto Tuning for Terminal Resistance only T1 01 2 Select Stationary Auto Tuning 1 or 2 T1 01 1 or 4 No A1 02 2 or 3 Yes A1 02 0 No Yes Ropes removed Select Rotational Auto Tuning T1 01...

Страница 73: ...he Baseblock input H1 8 9 if used Tuning Successful Refer to Remove the Fault Alarm source and repeat Auto Tuning Open terminals H1 HC and H2 HC if used during the normal sequence Open the motor conta...

Страница 74: ...ble Select Stationary Encoder Offset Auto Tuning T2 01 4 Press the Run key on the digital operator and wait until Auto Tuning is finished Set terminals H1 HC and H2 HC if Safe Disable function is used...

Страница 75: ...otational Auto Tuning No Yes Yes Stationary Auto Tuning for Line to Line Resistance T1 01 2 Used for V f Control or in vector control modes when the drive was previously set up properly and now the mo...

Страница 76: ...T2 16 N A Yes Yes N A N A N A N A N A N A Z Pulse Offset T2 17 deg mech Yes N A N A N A N A N A N A N A Speed Reference for Auto Tuning of PG E3 Encoder Characteristics 1 T2 18 r min N A N A N A N A...

Страница 77: ...ning is performed 3 The setting values of parameters F1 66 to F1 81 are reset to factory default values when A1 03 is set to 2220 The setting values of parameters F1 66 to F1 81 are modified at comple...

Страница 78: ...olding brake is applied on the load Ensure the motor can freely spin before beginning Auto Tuning Failure to comply could result in improper operation of the drive Enter the required information from...

Страница 79: ...und rated speed when using a vector control mode The no load voltage can usually be found in the motor test report available from the manufacturer If the motor test report is not available enter appro...

Страница 80: ...for one full motor rotation Note T1 08 will only be displayed in CLV T1 09 Motor No Load Current Sets the no load current for the motor The default setting displayed is no load current automatically c...

Страница 81: ...ing 12 Auto Tuning of PG E3 Encoder Characteristics T2 04 PM Motor Rated Power Specifies the PM motor rated power in kilowatts T2 05 PM Motor Rated Voltage Sets the PM motor rated voltage T2 06 PM Mot...

Страница 82: ...ill automatically set E5 09 Motor Induction Voltage Constant 1 to 0 0 If T2 13 is set to 1 then the drive will use E5 09 and will automatically set E5 24 to 0 0 T2 14 PM Motor Induced Voltage Constant...

Страница 83: ...e for execution of Auto Tuning of PG E3 encoder characteristics T2 01 12 T2 19 Rotation Direction for Auto Tuning of PG E3 Encoder Characteristics Note Available in drive software PRG 7017 or later Se...

Страница 84: ...e selected using parameter b1 02 Travel Start and Stop Travel Start To start the elevator in the up or down direction the following conditions must be fulfilled A speed reference greater than zero mus...

Страница 85: ...1 2 d1 18 0 or 3 Speed Selection When d1 18 0 or 3 multi function digital inputs are preset as shown below Different speed reference settings can be selected by combining the three digital inputs as s...

Страница 86: ...isplayed only if d1 18 is set to 1 or 2 Higher Speed has Priority and the Leveling Speed Input is Assigned d1 18 1 and H1 53 Default The higher speed has priority over the leveling speed The leveling...

Страница 87: ...ment Hazard This function may not work properly if a broken wire connection to the drive I O causes improper elevator speed selection Properly tighten wire connections at the drive terminals before en...

Страница 88: ...o Stop An emergency coast to stop is performed when the Up or Down command is cleared and all of the following conditions are met Parameter b1 03 Stopping Method Selection is set to 4 Parameter d1 18...

Страница 89: ...nd brake sequence at start as normal operation The carrier frequency is set to 2 kHz during Inspection Operation but can be changed using parameter C6 21 Stop Condition in Inspection Operation To stop...

Страница 90: ...do not set any analog input terminals for Torque compensation H3 14 Figure 38 Figure 43 Brake Sequence without Torque Compensation at Start 1 The drive stops if either the Up Down command or Inspectio...

Страница 91: ...ts the Brake Control output H2 50 in order to release the brake t3 DC Injection Braking or Position Lock will continue until the time S1 04 has elapsed or the time S1 06 has elapsed if S1 06 S1 04 thi...

Страница 92: ...l is on before the contactor control command has been issued an SE1 fault is triggered If the motor contactor feedback signal is not used then the drive waits for the operation start delay time set in...

Страница 93: ...e of the analog input monitor for the load signal input connected to U1 13 for terminal A1 U1 14 for terminal A2 4 Provide an elevator Up or Down command using Inspection Operation or normal operation...

Страница 94: ...S3 12 and S3 27 through S3 30 Figure 41 Figure 46 Torque Compensation at start for the Elevator in Up and Down Direction S3 30 S3 27 S3 28 Torque Compensation Value with Load Condition 2 Torque Compen...

Страница 95: ...unt of current to use for DC Injection at start Set as a percentage of the drive rated current S1 03 DC Injection Current at Stop Determines the amount of current to use for DC Injection at stop Set a...

Страница 96: ...able in drive software PRG 7016 or later Determines the state of the output contactor control command H2 51 during Auto Tuning The contactor closes as soon as the Enter key is pressed in the Auto Tuni...

Страница 97: ...of the motor S2 02 S2 03 Slip Compensation Gain in Motoring Mode Regenerative Mode Slip compensation for leveling speed can be set separately for motoring and regenerative states to help improve the a...

Страница 98: ...Note 1 Check the C5 parameters to make sure the speed control loop settings are correct before making any adjustments to the Position Lock gain 2 Faults may occur when detecting the direction of moto...

Страница 99: ...the Dwell 2 function Note Setting this parameter to 0 00 disables the Dwell 2 function Figure 42 Figure 47 Dwell Speed Reference at Start S3 21 Dwell 2 End Speed The Dwell 2 function will end when th...

Страница 100: ...om a load sensor for torque compensation Refer to Adjusting the Torque Compensation at Start on page 90 for details S3 30 Analog Input from Load Sensor with Load Condition 2 Adjusts the analog signal...

Страница 101: ...gain 2 have already been adjusted Lower S3 39 if oscillation occurs This parameter rarely needs to be changed S3 40 Anti Rollback Movement Detection Sets the amount of speed feedback signal pulses to...

Страница 102: ...orque Limit Sets the torque limit used during Rescue Operation S4 06 Rescue Operation Power Supply Selection Specifies the type of backup power supply the drive should switch to when the power goes ou...

Страница 103: ...riggered The following conditions will trigger PF5 During Rescue Operation DC bus voltage S4 12 S4 13 10 100 ms after Rescue Operation has been triggered the DC bus voltage does not rise above S4 12 S...

Страница 104: ...om nominal speed Figure 43 Figure 48 Speed During Normal Operation 1 The drive will recognize the speed reference that is lower than the Leveling Speed Detection Level d1 28 as the leveling speed if t...

Страница 105: ...Speed ON close The speed is 40 of the nominal speed or more d1 19 Nominal Speed d1 26 Leveling Speed H1 53 Leveling Speed 1 0 Operating speed Time 40 of nominal speed ON close The speed is over Optim...

Страница 106: ...level set to S5 04 and S5 05 if the leveling time is too short or if the optimum speed calculated by the drive is too fast Decrease the gain level set to S5 04 and S5 05 if the leveling time is too l...

Страница 107: ...eration times Droop Control b7 parameters Shoot Floor Advanced Short Floor S5 01 1 2 Leveling Distance Control is disabled when any one of the following functions are selected Analog frequency referen...

Страница 108: ...ditions Multi step speed sequence d1 18 0 3 The Up Down command is not active or the speed reference is 0 High speed reference has priority d1 18 1 Leveling speed reference is selected H1 53 The Up Do...

Страница 109: ...t which leveling operation is complete to when the car arrives at the designated floor No Parameter Name Setting Range Default S5 10 Stopping Method Selection 0 to 2 0 No Parameter Name Setting Range...

Страница 110: ...motor when the Brake Control command is activated as a percentage of the Motor No load Current E2 03 A Starting Current Error SE2 occurs when the drive s output current is less than the value in S6 0...

Страница 111: ...ock state H1 8 9 or from Safe Torque Off state Safe Disable inputs H1 and H2 enabled while the Up Down command is still active Setting 0 No restart after Baseblock or Safe Torque Off Do not restart th...

Страница 112: ...he voltage supplied to the drive control circuit must meet the specifications provided in Table 33 The DC bus voltage can either be supplied by a battery connected to the DC bus terminals of the drive...

Страница 113: ...separate batteries One is used for the main power supply a second battery supplies the controller via an optional 24 V Backup Power Supply Unit A single battery with minimum 250 Vdc for 200 V class d...

Страница 114: ...to operate under these conditions can trigger an overheat fault and damage the drive NOTICE Install the inrush current suppression circuit outside the drive if the DC bus battery voltage is lower than...

Страница 115: ...ion with normal power supply Application Precautions The drive may fault on a control power supply fault Uv2 if the UPS can t provide enough voltage or if the Light Load Direction Search is not set pr...

Страница 116: ...r DC Bus and Control Power Supply DC Bus Battery is less than 250 Vdc 500 Vdc 720 Vdc Operation Sequence Starting Rescue Operation 1 Open contactor B and wait at least 5 seconds 2 Set the input termin...

Страница 117: ...200 V class drives and 380 Vdc for 400 V class drives Failure to comply will cause the soft charge bypass relay to remain open and result in damage to the drive Current sensor R L1 S L2 T L3 1 U T1 V...

Страница 118: ...rive Model CIMR LU Resistor Relay 200 V 2 0215 1 0 80 W 1 2 0283 1 0 80 W 2 0346 1 0 80 W 2 0415 1 0 80 W 400 V 4 0150 1 0 120 W 4 0180 1 0 220 W 4 0216 1 0 220 W 4 0260 1 0 220 W 4 0304 1 0 220 W 4 0...

Страница 119: ...V Class Drives Current sensor R L1 S L2 T L3 1 3 U T1 V T2 W T3 Relay Power supply board Control board OPE CN19 A C B Battery for control circuit 200 V Class 250 to 340 Vdc 400 V Class 500 to 680 Vdc...

Страница 120: ...attery for the DC Bus and 24 V Power Supply Unit Option for the Control Circuit Operation Sequence Starting Rescued Operation 1 Open contactor B and wait at least 5 seconds 2 Set the input terminal pr...

Страница 121: ...is lower than 190 Vdc for 200 V class drives and 380 Vdc for 400 V class drives Failure to comply will cause the soft charge bypass relay to remain open and result in damage to the drive Current senso...

Страница 122: ...V Class Drives Current sensor R L1 S L2 T L3 1 3 U T1 V T2 W T3 Relay Power supply board Control board OPE A B DC bus power supply H1 55 Rescue Operation L1 L2 L3 DC bus power supply 200 V Class 190...

Страница 123: ...uence Starting Rescue Operation 1 Open contactor B 2 Set the input terminal programmed for Rescue Operation H1 55 3 Close contactor A 4 Set the Up Down command Ending Rescue Operation 1 After the car...

Страница 124: ...IMR LU5 0003 to 5 0027 1 Insert the tip of a screwdriver into the opening on the edge of the CN19 connector cover Slide the cover off the drive as indicated in Figure 59 NOTICE A straight edge screwdr...

Страница 125: ...cover with the cover fastened to the drive Figure 54 Figure 61 Reattaching the Connector Cover 1 4 Slide the connector cover back into place as shown in Figure 62 NOTICE Make sure the cable does not g...

Страница 126: ...nector cover in place Figure 57 Figure 64 Removing the CN19 Connector Cover 2 Slide the CN19 connector cover from the drive as shown in Figure 65 Figure 58 Figure 65 Sliding the CN19 Connector Cover 3...

Страница 127: ...t angle could damage the battery cable or connector Figure 60 Figure 67 Connecting the Cable 5 The cable should pass through the connector cover with the cover fastened to the drive Figure 61 Figure 6...

Страница 128: ...connector cover into place Using a different screw may damage the internal drive components Figure 63 Figure 70 Reattaching the CN19 Connector Cover Figure 64 Figure 71 Drive and Battery CN19 Connecti...

Страница 129: ...s Light Load Direction Search Function Light Load Direction Search can be used to automatically perform Rescue Operation in the direction with the lower load It can help to minimize the amount of powe...

Страница 130: ...minal set for Light load direction H2 54 will stay open and an output terminal set for Light Load Direction detection status H2 55 will close Figure 69 Figure 76 Light Load Direction Detection Down H1...

Страница 131: ...Recognize Safe Disable Monitor Output Signals Terminals DM and DM 131 Cause Possible Solutions The drive is running the motor i e the Up Down command is present Stop the drive and switch over to the...

Страница 132: ...ontrol terminal Correct wiring mistakes Check the input terminal status monitor U1 10 The speed reference source setting is incorrect Check parameter b1 01 Speed Reference Selection Set b1 01 to the c...

Страница 133: ...trol A1 02 0 Insufficient voltage insulation between motor phases When the motor cable is long high voltage surges occur between the motor coils and drive switching Normally surges can reach up to thr...

Страница 134: ...que limit was reached continuously for three seconds or longer while ramping to stop in OLV Control CoF Current Offset Fault The current sensor is damaged or there was residual induction current in th...

Страница 135: ...Rotor Position Estimation Error An invalid value resulted from Initial Pole Search Note Reset the fault and try Initial Pole Search again EF0 Option Card External Fault An external fault condition is...

Страница 136: ...port CN5 C to oFC12 to oFC17 oFC50 Encoder Option AD Conversion Error Error with the A D conversion level VCC level or A D conversion timed out oFC51 Encoder Option Analog Circuit Error Incorrect sign...

Страница 137: ...input power has an open phase or has a large imbalance of voltage between phases Detected when L8 05 1 2 3 enabled PF5 Rescue Operation Power Supply Deterioration Error PGo Encoder Disconnected for Co...

Страница 138: ...red while the drive was running Voltage in the DC bus fell below the undervoltage detection level L2 05 For 200 V class approximately 190 V For 400 V class approximately 380 V 350 V when E1 01 is less...

Страница 139: ...Fan Maintenance Time The cooling fan has reached its expected maintenance period and may need to be replaced Note An alarm output H2 10 will only be triggered if H2 2F LT 2 Capacitor Maintenance Time...

Страница 140: ...for alarm output H2 10 UL3 Undertorque Detection 1 Drive output current or torque in OLV CLV CLV PM less than L6 02 for longer than L6 03 time UL4 Undertorque Detection 2 Drive output current or torqu...

Страница 141: ...ctory setting is assigned to multi function contact inputs H1 03 to H1 08 oPE04 Terminal Board Mismatch Error oPE05 Reference Source Selection Error oPE06 Control Mode Selection Error Correct the sett...

Страница 142: ...ital Operator Display Error Name End1 Excessive V f Setting detected only during Rotational Auto Tuning and displayed after Auto Tuning is complete End2 Motor Iron Core Saturation Coefficient detected...

Страница 143: ...s Note 1 Whenever using the copy function the drive should be fully stopped 2 The drive will not accept an Up Down command while the Copy function is being executed 3 Parameters can only be saved to a...

Страница 144: ...rs Procedure Fix the cause of the fault restart the drive and reset the fault Press on the digital operator when error code is displayed Resetting via Fault Reset Digital Input S4 Close then open the...

Страница 145: ...e recommended daily inspection for Yaskawa drives Check the following items on a daily basis to avoid premature deterioration in performance or product failure Copy this checklist and mark the Checked...

Страница 146: ...ve foreign particles and dust by sucking them out with a vacuum cleaner to avoid touching parts Replace components if cleaning is not possible Conductors and Wiring Inspect wiring and connections for...

Страница 147: ...n and rust Make sure connections are properly fastened and that no dust or oil mist has accumulated on the surface of the board Fix any loose connections If an antistatic cloth or vacuum plunger canno...

Страница 148: ...o count down the performance life from the value that was reached with the old part If the Maintenance Monitor is not reset the drive will not have the correct value of the performance life for the ne...

Страница 149: ...damage due to lack of protective functions and poor drive performance The drive has a modular I O terminal block that facilitates quick drive replacement The terminal board contains on board memory th...

Страница 150: ...when handling the drive and circuit boards Failure to comply may result in ESD damage to the drive circuitry The following procedure explains how to replace a drive This section provides instructions...

Страница 151: ...he drive as shown in Figure 82 Use the installation screw to fasten the terminal block into place Figure 75 Figure 82 Drive Replacement Installing the Control Terminal Board 2 Reconnect all options to...

Страница 152: ...on and related components for reference Figure 76 Figure 83 Installing an Option Card Option Card 1 If two PG option cards are connected use both CN5 B and CN5 C If only one PG option card is connecte...

Страница 153: ...only by authorized personnel familiar with installation adjustment and maintenance of AC drives and Option Cards NOTICE Damage to Equipment Observe proper electrostatic discharge procedures ESD when...

Страница 154: ...ation is not accidentally pinched into electrical terminals WARNING Fire Hazard Tighten all terminal screws according to the specified tightening torque Loose electrical connections could result in de...

Страница 155: ...terminals on the option Connection Diagram of PG B3 Refer to Table 46 for a detailed description of the option board terminal functions Refer to Wire Gauges and Tightening Torques on page 155 for info...

Страница 156: ...hen the PG requires more than 200 mA to operate A A pulse signal input Pulse signal inputs from the PG Signal inputs from complementary and open collector outputs Signal level H level 8 to 12 V L leve...

Страница 157: ...B S185Y complementary output for cables running between the PG B3 Option and the PG as show in Figure 92 For instructions on wiring the terminal block refer to Table 46 Figure 84 Figure 92 Wiring PG E...

Страница 158: ...rresponding terminals on the option Connecting a Two Pulse Encoder with Z Marker Pulse When using a two pulse encoder with Z marker pulse connect the A B and Z pulse outputs to the corresponding termi...

Страница 159: ...ating at maximum speed Take the following steps to prevent erroneous operation caused by noise interference Use shielded wire for the PG encoder signal lines Use separate conduit or cable tray divider...

Страница 160: ...input Inputs for the A channel B channel and Z pulses from the PG encoder Signal level matches RS 422 A A pulse signal input B B pulse signal input B B pulse signal input Z Z pulse signal input Z Z pu...

Страница 161: ...leave no sharp edges to damage wiring Route the wiring inside the enclosure as shown in Figure 95 B for drive models CIMR LU2 0047 through 2 0415 4 0024 through 4 0605 and 5 0013 through 5 0200 that...

Страница 162: ...B Pulses 9 After connecting the PG encoder outputs to the option apply power to the drive and manually rotate the motor and check the rotation direction by viewing monitor U1 05 on the digital operato...

Страница 163: ...ing this current rating Higher carrier frequency settings require derating Specification CIMR LU2 000 8 0011 001 4 001 8 002 5 003 3 004 7 006 0 007 5 008 5 0115 014 5 018 0 021 5 028 3 034 6 041 5 Ma...

Страница 164: ...eater than the motor current Select the appropriate capacity drive if operating the motor continuously above motor nameplate current 2 Assumes operation at the rated output current Input current ratin...

Страница 165: ...ting Higher carrier frequency settings require derating 5 Carrier frequency can be set up to 8 kHz while keeping this current derating Higher carrier frequency settings require derating 6 Carrier freq...

Страница 166: ...or ft s2 Braking Transistor Models CIMR LU2 0008 to 2 0115 4 0005 to 4 0060 and 5 0003 to 5 0041 have a built in braking transistor V f Characteristics Freely programmable Main Control Functions Iner...

Страница 167: ...ociation International 5 2411 02 Elevator Equipment Enclosed Elevator and Escalator Electrical Equipment 3211 06 Industrial Control Equipment Motor Controllers Miscellaneous C22 2 No 04 04 Bonding and...

Страница 168: ...with version REV F or later The version number of the LCD operator s PRG software is shown on the back of the digital operator 2 Language selection settings 8 to 12 are available in drive software PR...

Страница 169: ...terminals 2 MEMOBUS Modbus communications 3 Option card Default 0 Min 0 Max 3 b1 02 Up Down Command Selection 0 Digital operator 1 Digital input terminals 2 MEMOBUS Modbus communications 3 Option card...

Страница 170: ...0 b6 02 Dwell Time at Start Default 0 0 s Min 0 0 s Max 10 0 s b6 03 Dwell Speed at Stop Default 0 0 Min 0 0 Max 100 0 b6 04 Dwell Time at Stop Default 0 0 s Min 0 0 s Max 10 0 s No Name Description...

Страница 171: ...s the ramp to decelerate from maximum speed to 0 C1 05 Acceleration Ramp 3 Motor 2 Accel Time 1 Sets the ramp to accelerate from 0 to maximum speed C1 06 Deceleration Ramp 3 Motor 2 Decel Time 1 Sets...

Страница 172: ...ion Setting C3 01 5 Default setting is determined by the control mode A1 02 Slip Compensation Gain Sets the gain for the motor slip compensation function Default 1 0 Min 0 0 Max 2 5 C3 02 Slip Compens...

Страница 173: ...ime 1 Sets the integral time 1 of the speed control loop Default 5 Min 0 000 s Max 10 000 s C5 03 Speed Control Loop Proportional Gain 2 Sets the proportional gain 2 of the speed control loop Default...

Страница 174: ...varies by the drive model o2 04 5 Default setting is determined by the control mode A1 02 45 Available in drive software versions PRG 7200 or later No Name Description Setting C6 03 4 Default setting...

Страница 175: ...to d1 23 d1 26 2 Leveling speed reference has priority d1 19 to d1 23 d1 26 3 Use multi speed references d1 02 to d1 08 no speed selection stops the drive Drive will stop when all input terminals prog...

Страница 176: ...lower than d1 28 then the drive uses the leveling speed as the speed reference Default 0 0 Min 0 0 Max 100 0 d1 29 Inspection Speed Detection Level Used when d1 18 0 or 3 If the speed reference select...

Страница 177: ...V f E1 04 through E1 13 settings define the V f pattern Default F Min Max F E1 04 Maximum Output Frequency To set linear V f characteristics set the same values for E1 07 and E1 09 In this case the s...

Страница 178: ...or poles Automatically set during Auto Tuning Default 4 Min 2 Max 48 E2 05 Motor Line to Line Resistance Sets the phase to phase motor resistance Automatically set during Auto Tuning Default 4 Min 0 0...

Страница 179: ...0 0 Hz E3 07 31 Motor 2 Mid Output Frequency Default 3 0 Hz Min 0 0 Hz Max 200 0 Hz E3 08 31 Motor 2 Mid Output Frequency Voltage Default 4 9 Min 0 0 V Max 255 0 V 9 E3 09 31 Motor 2 Minimum Output Fr...

Страница 180: ...Default 4 Min 0 10 kW Max 650 00 kW E5 03 1 Motor Rated Current Sets the motor rated current Default 4 Min 10 of drive rated current Max 200 of drive rated current 10 E5 04 1 Number of Motor Poles Set...

Страница 181: ...e Monitor Output Division Ratio Sets the division ratio for the pulse monitor used of the PG option card installed to connector CN5 C By setting xyz the division ratio becomes 1 x yz If only using the...

Страница 182: ...Min 0 Max 1 F1 66 to F1 81 B9AH to BA9H 44 Encoder Adjust 1 to 16 Sets encoder offsets 1 to 16 for the PG E3 option card These parameters are automatically set by the execution of Auto Tuning of PG E3...

Страница 183: ...minal V1 Default 0 0 Min 999 9 Max 999 9 F4 06 Terminal V2 Bias Sets the amount of bias added to the voltage output via terminal V2 Default 0 0 Min 999 9 Max 999 9 F4 07 Terminal V1 Signal Level Selec...

Страница 184: ...amp to stop Decelerate to stop using the deceleration ramp in C1 02 1 Coast to stop 2 Fast Stop Decelerate to stop using the deceleration ramp in C1 09 3 Alarm only Default 1 Min 0 Max 3 F6 04 bUS Err...

Страница 185: ...equence using the speed references set in d1 01 through d1 08 4 Multi Step Speed Reference 2 5 Multi Step Speed Reference 3 6 Jog reference selection Closed Jog frequency reference d1 17 selected The...

Страница 186: ...termediate Speed Closed Activates the Intermediate Speed d1 20 52 Releveling Speed Closed Activates the Releveling Speed d1 23 53 Leveling Speed Closed Activates the Leveling Speed d1 26 54 Inspection...

Страница 187: ...ive is ready to accept an Up Down command 7 DC Bus Undervoltage Closed DC bus voltage is below the Uv trip level set in L2 05 8 During Baseblock N O Closed Drive has entered the baseblock state no out...

Страница 188: ...tion is not available in models CIMR LU2 0145 to 2 0415 4 0075 to 4 0216 or 5 0052 to 5 0200 50 Brake Control Close Release brake Open Apply brake 51 Output Contactor Control Closed Close output conta...

Страница 189: ...in H3 10 when 0 V is input at terminal A2 Default 0 0 Min 999 9 Max 999 9 H3 13 Analog Input Filter Time Constant Sets a primary delay filter time constant for terminals A1 and A2 Used for noise filt...

Страница 190: ...dded to the terminal FM output signal Default 0 0 Min 999 9 Max 999 9 H4 04 Terminal AM Monitor Selection Selects the data to be output through multi function analog output terminal AM Set the desired...

Страница 191: ...Min 0 Max 2 H5 04 Stopping Method After Communication Error CE 0 Ramp to stop 1 Coast to stop 2 Fast Stop 3 Alarm only Default 3 Min 0 Max 3 H5 05 Communication Fault Detection Selection 0 Disabled 1...

Страница 192: ...Motor Overheat Alarm Operation Selection PTC thermistor input Sets operation when the motor temperature analog input H3 02 or H3 10 E exceeds the oH3 alarm level 0 Ramp to stop 1 Coast to stop 2 Emer...

Страница 193: ...0 16 No 44 Available in drive software versions PRG 7017 or later Name Description Setting L4 01 Speed Agreement Detection Level L4 01 sets the speed detection level for digital output functions H2 3...

Страница 194: ...peed agree output shuts down on an oL3 fault 8 UL3 detection always active during run output shuts down on an oL3 fault Default 0 Min 0 Max 8 L6 02 Torque Detection Level 1 Sets the overtorque and und...

Страница 195: ...led during operation 3 Enabled during constant speed Setting 1 cannot be selected for 600 V class drive models and models CIMR L F that are in compliance with IEC EN 61508 SIL3 Safety Integrity Level...

Страница 196: ...function Default 3 0 kHz Min 1 0 kHz Max 15 0 kHz L8 55 Internal Braking Transistor Protection 0 Disabled L8 55 should be disabled when using a regen converter or an optional braking unit 1 Protection...

Страница 197: ...2000 ms n2 03 Speed Feedback Detection Control AFR Time Constant 2 Sets the AFR time constant to be used during regen Default 750 ms Min 0 ms Max 2000 ms No Name Description Setting n5 01 4 Default s...

Страница 198: ...s n8 35 Initial Rotor Position Detection Selection 1 High frequency injection 2 Pulse injection Default 1 Min 1 Max 2 n8 36 High Frequency Injection Level Sets the frequency in Hz for the superimposed...

Страница 199: ...its set by o1 10 and o1 11 4 Elevator units 1 speed in m s accel decel rate and jerk in s 5 Elevator units 2 speed in m s accel decel rate in m s2 jerk in m s3 6 Elevator units 3 speed in ft min accel...

Страница 200: ...0 to 50 00 PRG 7200 or later 0 10 to 100 00 No Name Description Setting o2 01 1 Parameter setting value is not reset to the default value when the drive is initialized LO RE Key Function Selection 0 D...

Страница 201: ...Monitor for the soft charge bypass relay See U4 06 to check when the bypass relay may need to be replaced Default 0 Min 0 Max 150 o4 09 IGBT Maintenance Setting Sets the value of the Maintenance Monit...

Страница 202: ...perform DC Injection at stop In CLV and CLV PM S1 05 determines how long Position Lock should be performed A setting of 0 00 disables S1 05 Default 0 60 s Min 0 00 s Max 10 00 s S1 06 Brake Release De...

Страница 203: ...04 Position Lock Bandwidth Determines the bandwidth around the stop position in which a digital output programmed for Within Position Lock Bandwidth H2 33 is closed Default 10 Min 0 Max 16383 S3 10 St...

Страница 204: ...small position deviations during Position Lock at start Default 0 0 Min 0 0 Max 100 0 S3 35 Anti Rollback Torque Bias 2 Sets the Anti Rollback Bias applied at large position deviations during Positio...

Страница 205: ...1 5 Default setting is determined by the control mode A1 02 39 Available in drive software versions PRG 7016 or later No Name Description Setting S5 01 Short Floor Operation Selection 0 Disabled 1 En...

Страница 206: ...y time for detecting SE2 Default 200 ms Min 0 00 ms Max S1 04 S1 06 S6 03 44 SE2 Detect Current Level Sets the level of current applied to the motor when the Brake Control command is activated as a pe...

Страница 207: ...Max 650 00 kW T1 03 Motor Rated Voltage Sets the motor rated voltage as specified on the motor nameplate Default 200 0 V 9 Min 0 0 V Max 255 0 V 9 T1 04 Motor Rated Current Sets the motor rated curre...

Страница 208: ...the motor as indicated on the motor nameplate Default 6 Min 2 Max 120 43 T2 09 Motor Base Speed Enter the base speed for the motor as indicated on the motor nameplate Default 150 r min Min 0 r min Max...

Страница 209: ...0 Setting units are determined by the induced voltage constant unit selection for PM motors set to T2 13 43 When PG E3 option connected Max setting 48 44 Available in drive software versions PRG 7017...

Страница 210: ...as determined by the digital card input selection in F3 01 3FFFF Set 1 bit sign 1 bit 16 bit No signal output available No Name Description Analog Output Level Unit U1 10 00000000 Digital input 1 ter...

Страница 211: ...values in 0 1 A units 12 The display resolution depends on the rated output power of the drive Models CIMR LU2 0008 to 2 0033 4 0005 to 4 0018 and 5 0003 to 5 0013 display values in 0 01 kW units whi...

Страница 212: ...Bus Voltage at Previous Fault Displays the DC bus voltage at the previous fault No signal output available 1 Vdc U2 09 Output Power at Previous Fault Displays the output power at the previous fault N...

Страница 213: ...available 1 h U4 04 Cooling Fan Maintenance Displays main cooling fan usage time in as a percentage of its expected performance life Parameter o4 03 can be used to reset this monitor The fan should be...

Страница 214: ...Uv or Uv1 flashes after 10 s 04 Waiting for Up Down Command Prohibited time period to end 05 Fast Stop multi function input operator 07 During baseblock while coast to stop with timer 08 Speed referen...

Страница 215: ...ys the Minimum Stop Distance calculated by d1 26 No signal output available 1 mm 29 Setting units are determined by the digital operator display unit selection o1 03 When o1 03 0 the value is set in H...

Страница 216: ...0 Vrms 9 10 to 10 V 0 1 Vac U6 07 q Axis Current Controller Output Displays the output value for current control relative to motor secondary current q axis 10 V 200 Vrms 9 10 to 10 V 0 1 U6 08 d Axis...

Страница 217: ...mp 1 C1 03 Acceleration Ramp 2 C1 04 Deceleration Ramp 2 C1 05 Acceleration Ramp 3 C1 06 Deceleration Ramp 3 C1 07 Acceleration Ramp 4 C1 08 Deceleration Ramp 4 C1 09 Fast Stop Time C1 15 Inspection R...

Страница 218: ...ed Note 600 V class drives models 5 are not compliant with European Standards CE Low Voltage Directive Compliance This drive has been tested according to European standard IEC EN 61800 5 1 and it full...

Страница 219: ...0283 100 271 500 450 800 FWH 700A 700 2 0346 125 324 600 500 900 5 FWH 800A 800 2 0415 150 394 700 600 1100 5 FWH 1000A 1000 Three Phase 400 V Class 4 0005 3 4 4 15 7 12 FWH 70B 70 4 0006 3 6 15 10 1...

Страница 220: ...75 125 FWP 175A 175 5 0052 6 50 60 54 100 90 150 FWP 250A 250 5 0062 6 50 60 66 125 110 175 FWP 250A 250 5 0077 6 75 80 150 125 225 FWP 250A 250 5 0099 6 100 108 175 175 300 FWP 350A 350 5 0130 6 125...

Страница 221: ...use Holder Fuse Fuse Holder Type Rated Short circu it Breaking Current kA Qty Type Qty Type Rated Short circu it Breaking Current kA Qty Type Qty 200 V Class 400 V Class 2 0008 CR2LS 50 100 2 CM 1A 1...

Страница 222: ...MC guidelines 1 Install an EMC noise filter to the input side specified by Yaskawa for compliance with European standards 2 Place the drive and EMC noise filter in the same enclosure 3 Use braided shi...

Страница 223: ...ance Three Phase 200 V 400 V Class L3 L3 L2 L2 L1 L1 L3 L2 L1 E L3 L2 L1 PE Make sure the ground wire is grounded Enclosure panel Metal plate Grounding surface remove any paint or sealant Drive Ground...

Страница 224: ...3 0 4 5 12 3 1 2 0011 2 0014 FS5972 35 07 35 4 6 8 1 2 0 14 0 6 9 13 2 2 0018 2 0025 2 0033 FS5972 60 07 60 8 8 9 3 2 6 16 1 8 1 15 4 2 0047 2 0060 FS5972 100 35 100 7 5 3 5 5 9 13 0 2 6 10 0 2 2 0075...

Страница 225: ...arth ZSN High leakage current L3 L2 L1 LOAD LOAD PE Recommended torque 26 30Nm PE 15 17Nm L1 L2 L3 ZSN FS5972 250 37 250A 45 C 25 100 21 ZSN 3x480 275V 50 60Hz L1 L1 L2 L2 L3 L3 LINE LINE PE Recommend...

Страница 226: ...14 to 122 F Main Circuit Terminal Wiring Yaskawa recommends using closed loop crimp terminals on all drive models UL cUL approval requires the use of UL Listed closed loop crimp terminals when wiring...

Страница 227: ...6 to 4 B1 B2 10 to 6 M5 2 7 to 3 0 23 9 to 26 6 6 8 to 6 M6 5 4 to 6 0 47 8 to 53 1 2 0060 R L1 S L2 T L3 3 4 to 3 M8 9 9 to 11 0 87 6 to 97 4 U T1 V T2 W T3 3 4 to 3 1 2 4 to 3 B1 B2 8 to 6 M5 2 7 to...

Страница 228: ...54 2 0283 2 R L1 S L2 T L3 4 0 2P 3 0 to 300 M12 32 to 40 283 to 354 U T1 V T2 W T3 3 0 2P 3 0 to 300 1 3 0 to 300 3 3 0 to 300 M10 18 to 23 159 to 204 2 2 to 300 M12 32 to 40 283 to 354 2 0346 2 R L1...

Страница 229: ...1 2 12 to 6 B1 B2 12 to 10 10 14 to 10 M5 2 0 to 2 5 17 7 to 22 1 4 0018 R L1 S L2 T L3 10 10 to 6 M4 2 1 to 2 3 18 6 to 20 4 U T1 V T2 W T3 10 10 to 6 1 2 12 to 6 B1 B2 12 to 10 10 12 to 10 M5 2 0 to...

Страница 230: ...204 U T1 V T2 W T3 4 0 3 0 to 4 0 1 1 to 4 0 3 1 0 to 4 0 4 4 to 2 4 0180 1 R L1 S L2 T L3 300 2 to 300 M10 18 to 23 159 to 204 U T1 V T2 W T3 300 2 to 300 1 1 to 250 3 3 to 3 0 4 4 to 300 4 0216 1 R...

Страница 231: ...e use of closed loop crimp terminals for UL cUL compliance Use only the tools recommended by the terminal manufacturer for crimping 2 When an EMC filter is installed take additional measures to comply...

Страница 232: ...8 9 to 11 79 7 to 97 4 U T1 V T2 W T3 6 10 to 3 1 6 to 1 B1 B2 8 to 3 6 6 5 0052 R L1 S L2 T L3 4 10 to 4 0 M10 18 to 23 159 to 204 U T1 V T2 W T3 4 10 to 4 0 1 4 to 4 0 3 6 to 4 0 4 4 5 0062 R L1 S L...

Страница 233: ...300 M10 18 to 23 159 to 204 1 1 to 350 M12 32 to 40 283 to 354 Wire Gauge Terminal Screws Crimp Terminal Model Number Tool Insulation Cap Model No Code 1 Machine No Die Jaw 14 AWG M4 R2 4 YA 4 AD 900...

Страница 234: ...00 10 YF 1 YET 300 1 TD 327 TD 314 TP 200 100 051 563 350 kcmil 2P M12 180 L12 YF 1 YET 300 1 TD 326 TD 313 TP 200 100 066 688 400 kcmil 2P M12 200 L12 YF 1 YET 300 1 TD 327 TD 314 TP 200 100 051 564...

Страница 235: ...FWH 70B 70 2 0018 5 18 9 35 30 50 FWH 90B 90 2 0025 7 5 28 50 40 75 FWH 100B 100 2 0033 10 37 60 60 100 FWH 200B 200 2 0047 15 52 100 90 150 FWH 200B 200 2 0060 20 68 125 110 200 FWH 200B 200 2 0075...

Страница 236: ...40 40 60 FWP 100B 100 5 0022 20 31 60 50 90 FWP 125A 125 5 0027 25 38 75 60 100 FWP 125A 125 5 0032 30 33 60 50 90 FWP 175A 175 5 0041 40 44 75 75 125 FWP 175A 175 5 0052 50 54 100 90 150 FWP 250A 250...

Страница 237: ...2004 Mark Drive Motor Overload Protection Set parameter E2 01 E5 03 motor rated current to the appropriate value to enable motor overload protection The internal motor overload protection is UL Listed...

Страница 238: ...of the curves Figure 99 Figure 108 Protection Operation Time for General Purpose Motors at the Rated Output Frequency Setting Description 0 Disabled Disabled the internal motor overload protection of...

Страница 239: ...1508 SIL3 CIMR L F Table 70 Safety Standards and Applicable Harmonized Standards for CIMR L F The Safe Disable function is in compliance with these standards Setting Description 0 Ramp to Stop 1 Coast...

Страница 240: ...d to an external force use a mechanical brake that meets the safety requirements of entire system or machinery to stop the machine connected to the load The motor will move when an external gravitatio...

Страница 241: ...2 DM and DM on 600 V class models are designed to the functionality but are not certified to IEC EN 61800 5 2 ISO EN 13849 Cat 3 IEC EN 61508 SIL2 Insulation coordination class 1 The Safe Disable inpu...

Страница 242: ...afe Disable inputs are opened first when the motor has completely stopped Returning to Normal Operation after Safe Disable Note Terminals H1 H2 DM and DM on 600 V class models are designed to the func...

Страница 243: ...ontactor solutions but not as an EDM signal according to IEC EN 61800 5 2 When both Safe Disable inputs are open Hbb will flash in the digital operator display Should only one of the Safe Disable chan...

Страница 244: ...chain is interrupted A drive digital output must be programmed as Safe Disable feedback H2 58 This feedback signal must be implemented in the contactor supervision circuit of the controller that prev...

Страница 245: ...Sinking Sourcing Mode Selection for Safe Disable Inputs on page 55 for details on setting jumper S3 The figure below shows a wiring example Note 1 The drive output will immediately shut off when eith...

Страница 246: ...phase 600 V CIMR LU5A0003 to 5A0200 Revision Review and corrected entire documentation Upgraded the software version to PRG 7017 and PRG S7200 Back cover Revision Address August 2012 4 All Addition S...

Страница 247: ...17 0099 Fax 66 2 017 0799 http www yaskawa co th YASKAWA ELECTRIC CHINA CO LTD 22F One Corporate Avenue No 222 Hubin Road Shanghai 200021 China Phone 86 21 5385 2200 Fax 86 21 5385 3299 http www yaska...

Отзывы: