5 Output Phase Loss Protection
16
YASKAWA
TOEPC710616134G AC Drive L1000A Technical Manual Addendum
travel with a direction selected by S1/S2. In this case, set
S4-20 = 0 [Light Load Search Direction Override =
Disabled]
.
◆
Added and Modified Parameters for Advanced Light Load Search
■
Modified Parameters
Parameter
(Hex.)
Operator Display
[Parameter Name]
Description
Range
[Default]
S4-01
(06A6)
LightLoad Search
[Light Load Direction Search
Selection]
0 : Disabled
1 : Enabled
2 : Enabled for Motor 1 only
3 : Advanced Search
0 - 3
[0]
Yaskawa recommends a full up/down travel with empty car for calibration.
Note:
You must repeat the calibration after you initialized the drive with
A1-03
.
To reset the calibration, set
S4-01 = 0
. This is recommended in case of changed operating conditions of the
elevator.
When you change the setting from
S4-01 = 0
to
S4-01 = 1
, do a new calibration.
■
Added Parameters
Parameter
(Hex.)
Operator Display
Description
Value Range
[Default]
S4-20
(06DF)
LLS Dir Override
Evacuation in Light Load Direction determined by the drive.
0 : Disabled
Lift controller decides the direction with S1/S2
1 : Enabled
Drive can override S1/S2 direction
Perform a power cycle when changing
H5-13 [Serial Communication Mode]
.
0, 1
[1]
5
Output Phase Loss Protection
Enables or disables the output phase loss detection which is triggered when the output current falls below 5% of
the motor rated current.
◆
Modified Parameters for Output Phase Loss Protection
Table 5.1 Modified Parameters
Parameter
(Hex.)
Operator Display
[Parameter Name]
Description
Range
[Default]
L8-07
(04B3)
OutputPhLoss
[Output Phase Loss
Protection Selection]
0 : Disabled
1 : Triggered by a single phase loss
2 : Triggered when two phases are lost
3 : Fault at phase loss at start and during RUN
0 - 3
[0]
0 : Disabled
1 : Triggered by a single phase loss
An
output phase loss fault [LF]
is triggered when one output phase is lost. The output shuts off and the motor
coasts to stop.
2 : Triggered when two phases are lost
An
output phase loss fault [LF]
is triggered when two output phases are lost. The output shuts off and the motor
coasts to stop.
3 : Fault at phase loss at start and during RUN
An
output phase loss fault [LF]
is triggered when one or more phases are lost at motor start (before the brake
opens) and when motor is moving. When
LF
has been detected, the motor coasts to stop.
When setting
L8-07 = 3
, set parameters
S1-02
(only OLV and V/f) and
S1-04
as follows:
•
Set
S1-02 [DC Injection Current at Start]
to a value greater than 15%.
•
Set
S1-04 [DC Injection/Position Lock Time at Start]
to a value greater than 100 ms.
Содержание L1000A CIMR-LC F Series
Страница 1: ...AC Drive L1000A For Lift Applications Technical Manual Addendum Type CIMR LCxFxxxxxxx 913x Web...
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 97: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 97 15 Appendix EN...
Страница 98: ...15 Appendix 98 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 99: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 99 EN...
Страница 100: ...15 Appendix 100 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...
Страница 101: ...15 Appendix YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum 101 EN...
Страница 102: ...15 Appendix 102 YASKAWA TOEPC710616134G AC Drive L1000A Technical Manual Addendum...