YASKAWA JOHB-SMP3 Скачать руководство пользователя страница 40

9 Troubleshooting

40

YASKAWA

SIEP C730600 0MA BACnet/IP Technical Manual

Webpage Settings

The values displayed in the various tabs are refreshed at the rate defined in the

Data Update Time

select box.

The Data Update Time can be set to 250 ms, 500 ms, 1 second, 2 seconds, or 5 seconds.

Email Settings

The

Email Server IP Address

text box must contain the IP address of the email server. The subnet address is

configured in drive parameters

F7-05

through

F7-08

. The configured email alerts will use the server at this

address when sending emails.

Enter the email server port in the

Email Server Port

text box.

The value in the

From Email Address

text box identifies the origin of the email alerts to the recipient.

To save the entered information into the option, click

Save Email Settings

.

9

Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive keypad. This section lists causes of the errors and possible corrective
actions. Refer to the drive Technical Manual for additional error codes that may appear on the drive keypad.

Faults

Both

bUS [Option Communication Error]

and

EF0 [Option Card External Fault]

can appear as a fault. When a

fault occurs, the keypad ALM LED stays lit. When an alarm occurs, the ALM LED flashes.

If communication stops while the drive is running, use these questions as a guide to help remove the fault:

Is the communication line properly connected to the option? Is it loose?

Is the option properly installed?

Is the host controller program working? Is the controller/host controller CPU stopped?

Did a momentary power loss interrupt communications?

Code

Name

Causes

Possible Solutions

bUS

Option Communication Error

The drive did not receive a signal from the
controller.

The communications cable wiring is incorrect.

Check for wiring errors.

Correct the wiring.

An existing short circuit or communications
disconnection

Check disconnected cables and short circuits and repair as needed

A data error occurred due to electric interference

Prevent noise in the control circuit, main circuit, and ground
wiring.

If you identify a magnetic contactor as a source of noise,
install a surge absorber to the contactor coil.

Use only recommended cables or other shielded line. Ground
the shield on the controller side or the drive input power side.

Separate all communication wiring from drive power lines.
Install an EMC noise filter to the drive power supply input.

Decrease the effects of electrical interference from the host
controller.

Option is damaged

If there are no problems with the wiring and the error continues to
occur, replace the option.

Connection Time-out

Check if the CPU of the controller is not stopped.

Duplicate IP Address found on network

Change to a different IP address. If

F7-13 = 0 [Address Mode at

Startup = Static]

, change parameters

F7-01 to F7-04 [IP Address

1 to 4]

.

EF0

Option Card External Fault

The option received an external fault from the
controller.

1.

Find the device that caused the external fault and remove the
cause.

2.

Clear the external fault input from the controller.

A programming error occurred on the controller
side.

Examine the operation of the controller program.

oFA00

Option Not Compatible with Port

The option connected to connector CN5-A is not
compatible.

Connect the option to the correct connector.

Use connector CN5-A when you connect the option.
To use other options, refer to those option manuals.

Invalid DIP switch S1 setting.

Set the option DIP switch S1 as shown in page

11

Monitor,

U4-

75 [Communication OPT Protocol]

will display the DIP switch

S1 setting.

Содержание JOHB-SMP3

Страница 1: ...SKAWA AC Drive Option BACnet IP Technical Manual Model JOHB SMP3 To correctly use the product read this manual thoroughly and keep it for easy reference inspection and maintenance Make sure that the e...

Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEP C730600 0MA BACnet IP Technical Manual...

Страница 3: ...ption LED States 9 Power Up Diagnostics 10 5 Installation Procedure 10 Section Safety 10 Settings for DIP Switch S1 11 Procedures to Install and Wire the Option 11 Procedure A 11 Procedure B 13 Proced...

Страница 4: ...y Login 39 Webpage Password 39 Webpage Settings 40 Email Settings 40 9 Troubleshooting 40 Drive Side Error Codes 40 Faults 40 Minor Faults and Alarms 41 bUS Fault Tolerance 41 bUS Fault Auto Restart 4...

Страница 5: ...gether with the product YASKAWA AC Drive Option BACnet IP Technical Manual Manual No SIEP C730600 0M This book The technical manual contains detailed information about the option Access the following...

Страница 6: ...equipment WARNING Electrical Shock Hazard Do not modify the drive or option circuitry Failure to obey can cause serious injury or death or cause damage to the drive or option and will void warranty Y...

Страница 7: ...shipping If there is damage to the option or other parts contact the shipping company immediately NOTICE Damage to Equipment Do not use damaged parts to connect the drive and the option Failure to com...

Страница 8: ...crew sizes are different for different drive capacities Prepare different screwdrivers for different screw sizes 4 Option Components Option Components A Connector CN5 B Installation hole C LED NS 1 D...

Страница 9: ...of the option LEDs after the power up diagnostic LED sequence is complete Refer to Table 4 3 for more information about the LEDs Table 4 2 Option LED States LED Name Indication Operating State Descrip...

Страница 10: ...operate the drive Use the drive only as specified by the instructions Some figures in this section include drives without covers or safety shields to more clearly show the inside of the drive If cover...

Страница 11: ...h S1 Note If you set the DIP switch for a different protocol it will erase all user entered data from the JOHB SMP3 including the Device Object Name Procedures to Install and Wire the Option Procedure...

Страница 12: ...nstall this option into the CN5 A connector on the drive control board 1 Shut off power to the drive and wait for the time specified on the drive warning label at a minimum Make sure that the charge i...

Страница 13: ...m main circuit wiring and other electrical and power lines Make sure that you firmly connect the cable end Refer to Communication Cable Specifications on page 17 for more information 8 Reattach the fr...

Страница 14: ...the drive is de energized The charge indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc When all indicators are OFF measure for dangerous voltages to make sure that the drive i...

Страница 15: ...cal and power lines Make sure that you firmly connect the cable end Refer to Communication Cable Specifications on page 17 for more information 9 Reattach the drive front cover E and the keypad F Refe...

Страница 16: ...er supplied network cable into the CN1 connection port on the option board When you have a dual port option connect two network cables to the two network ports in CN1 for flexibility in cabling topolo...

Страница 17: ...y Daisy Chained Use the communication connectors CN1A Port 1 and CN1B Port 2 at the same time A switch is not necessary for this connection Note This option does not support STP Spanning Tree Protocol...

Страница 18: ...op Use C1 09 3 Alarm Only 4 Alarm Run at d1 04 5 Alarm Ramp Stop Note When you set this parameter to 3 or 4 the drive will continue operation after it detects a fault Separately prepare safety protect...

Страница 19: ...the BACnet Device Object Example 1 Set the Device Object Instance Identifier to 1234 1234 decimal is equal to 4D2 Hex Set F6 48 4D2 Hex and F6 49 0 Hex Example 2 Set the Device Object Instance Identi...

Страница 20: ...ers Reload Reload Now enables communication OPT parameter changes without turning on the power again 192 0 255 F7 10 03EE Gateway Address 2 Sets the static fixed Gateway address Sets the second most s...

Страница 21: ...Broadcast Management Device BBMD to which the drive will register as a foreign device 0 0 255 F7 53 1BEB BBMD Foreign Register Addr 3 Sets the third octet of the IP Address of the BACnet Broadcast Man...

Страница 22: ...tet U4 81 Fifth octet Sixth octet Note Not all drive software versions will display this monitor Contact Yaskawa or your nearest sales representative for more information This monitor is not available...

Страница 23: ...ring Change Of Value Property B Client DM DDB B Device Management Dynamic Device Binding B Client DM DOB B Device Management Dynamic Object Binding B Client DM DCC B Device Management Device Communica...

Страница 24: ...Yes Yes Yes Yes Yes Polarity Yes Yes Present_Value Yes Yes Yes Yes Yes Yes Priority_Array Yes 2 Yes 2 Yes Yes 2 Property_List Yes Yes Yes Yes Yes Yes Yes Protocol_Object_Types_Supported Yes Protocol_...

Страница 25: ...FM set H4 01 0 Drv Anlg Out1 Level 0007 0 100 0 C AO2 1 Drive Analog Output 2 Level Drive Terminal AM set H4 01 0 Drv Anlg Out2 Level 0008 0 100 0 C 1 Not available on all drives Refer to the Technic...

Страница 26: ...sink Overheat oH2 External Overheat H1 XX B Bit 4 to 6 Reserved Bit 7 EF to EF7 External Fault Bit 8 CPFxx Hardware Fault includes oFAxx Bit 9 oL1 Motor Overload oL3 Overtorque Detection 1 UL3 Underto...

Страница 27: ...11 kVA A R AV32 2 120V to Kx Coils 8790 0 65535 V R AV33 Drive kWh consumed kWh consumed 005C 005D 0820 0822 for Z1000U 0 999999999 kWh R AV34 Drive kWh Regenerated kWh Regenerated Z1000U only 0823 0...

Страница 28: ...Not available on all drives Refer to the Technical Manual of your drive and check if the Modbus register of the applicable object exists 4 See Gateway Mode features in drive manuals for use instructio...

Страница 29: ...f HW Status Saf Trq Off Hw Stat 0020 Bit 12 ALARM OK R BI32 2 Safe Torque Off Status Saf Trq Off Stat 0020 Bit 13 ALARM OK R 1 Available on bypass only 2 Not available on Z1000U Binary Output Objects...

Страница 30: ...20 Bit 3 FAULTED OFF R BV17 Data Set Error 004B Bit 8 ERROR OFF R BV18 Overcurrent Ground Fault Overcurrent Gnd Flt 0021 Bit 0 OC GF OFF R BV19 Main Circuit Overvoltage Main Ckt Overvoltage 0021 Bit 1...

Страница 31: ...400 Bit 4 ON OFF C BV63 6 Emergency Override Drive Forward Em Over DRV FWD CMD Internal ON OFF C BV64 8 Bypass Motor OR Select Command BYP Mtr OR Sel CMD 8400 Bit 6 ON OFF C BV65 8 Bypass Motor AND Se...

Страница 32: ...atus BYP Motor 2 Sel Stat 8785 Bit 7 SELECT OFF R BV96 8 Bypass Drive Fault Status BYP Drive Flt Status 8786 Bit 0 FAULT OFF R BV97 8 BYP Safety Status 2 BYP Safety Status 2 8786 Bit 1 OPEN CLOSED R B...

Страница 33: ...9xxxx Number of APDU Retries 0 fixed Object Identifier Instance Numeric value set by F6 49 and F6 48 Type OBJECT_DEVICE fixed Object List List of all available objects Object Name Settable via the net...

Страница 34: ...er Quality Network Type 5 IPV4 fixed Object Identifier Instance 1 fixed Type OBJECT_NETWORK_PORT 1 fixed Object Type 56 Object Network Port fixed Out Of Service FALSE fixed Protocol Level 2 BACnet App...

Страница 35: ...Web Interface YASKAWA SIEP C730600 0MA BACnet IP Technical Manual 35 Figure 8 1 Home Page View BACnet IP Page The BACnet IP page shows basic information about the protocol Figure 8 2 BACnet IP Page Vi...

Страница 36: ...ns Duplex Display either Full or Half Excessive Collisions Cumulative number of excessive collisions FCS Errors Cumulative number of frame check sequence errors Frame Too Large Cumulative number of fr...

Страница 37: ...ulative number of non unicast packets sent Out Octets Cumulative number of outgoing octets Out Ucast Packets Cumulative number of unicast packets sent Single Collisions Cumulative number of single col...

Страница 38: ...cing emails about reoccurring errors Click Save Email Settings when you save the entered information into the option Figure 8 5 Email Alerts Page View Procedure Conditional Email Set up 1 Click the En...

Страница 39: ...nished Settings Page Requires Security Login The Settings page sets web page behavior parameters Access is restricted unless a valid password is entered The default password is yaskawa Figure 8 7 Sett...

Страница 40: ...ive did not receive a signal from the controller The communications cable wiring is incorrect Check for wiring errors Correct the wiring An existing short circuit or communications disconnection Check...

Страница 41: ...ion DIP switch S1 as shown in page 11 Monitor U4 75 Communication OPT Protocol will display the DIP switch S1 setting BACnet IP is not installed on the JOHB SMP3 card Upgrade the software in the JOHB...

Страница 42: ...guration bUS 1106 F7 13 0 Address Mode at Startup Static is set and F7 01 to F7 12 IPAddress 1 to 4 Subnet Mask 1 to 4 Gateway Address 1 to 4 are set to an invalid configuration Set the parameters to...

Страница 43: ...required for engaging in business and commerce in Europe This option displays the CE mark based on the EMC Directive 2014 30 EU Drives used in combination with this option and devices used in combinat...

Страница 44: ...shield to the metal panel according to Figure 10 2 Figure 10 3 and Figure 10 4 Figure 10 2 Option Installation for CE Compliance Z1000U Figure 10 3 Option Installation for CE Compliance HV600 Figure...

Страница 45: ...mestic environment Note The user guide applies only to Business Broadcasting Communication Equipment Comply with the EMC Directive to conform to the Korean Radio Act 12 Specifications Specifications T...

Страница 46: ...dardized Device Profile Annex L BACnet Cross Domain Advanced Operator Workstation B XAWS BACnet Advanced Operator Workstation B AWS BACnet Operator Workstation B OWS BACnet Operator Display B OD BACne...

Страница 47: ...Output Object Binary Value Object Data Link Layer Options ARCNET ATA 878 1 2 5 Mb Clause 8 ARCNET ATA 878 1 EIA 485 Clause 8 baud rate s BACnet IP Annex J BACnet IP Annex J BACnet Broadcast Management...

Страница 48: ...way Network Security Options Non secure Device is capable of operating without BACnet Network Security Secure Device is capable of using BACnet Network Security NS SD BIBB Multiple Application Specifi...

Страница 49: ...YASKAWA SIEP C730600 0MA BACnet IP Technical Manual 49 Revision History Date of Publication Revision Number Section Revised Content October 2022 First Edition...

Страница 50: ...Piraporinha Diadema S o Paulo 09950 000 Brasil Phone 55 11 3585 1100 Fax 55 11 3585 1187 www yaskawa com br YASKAWA EUROPE GmbH Hauptstra e 185 65760 Eschborn Germany Phone 49 6196 569 300 Fax 49 619...

Отзывы: