SIEP C730600 0MA BACnet/IP Technical Manual
■
Webpage Settings
The values displayed in the various tabs are refreshed at the rate defined in the
“
Data Update Time
”
select box.
The Data Update Time can be set to 250 ms, 500 ms, 1 second, 2 seconds, or 5 seconds.
■
Email Settings
The
“
Email Server IP Address
”
text box must contain the IP address of the email server. The subnet address is
configured in drive parameters
F7-05
through
F7-08
. The configured email alerts will use the server at this
address when sending emails.
Enter the email server port in the
“
Email Server Port
”
text box.
The value in the
“
From Email Address
”
text box identifies the origin of the email alerts to the recipient.
To save the entered information into the option, click
“
Save Email Settings
”
.
9
Troubleshooting
◆
Drive-Side Error Codes
Drive-side error codes appear on the drive keypad. This section lists causes of the errors and possible corrective
actions. Refer to the drive Technical Manual for additional error codes that may appear on the drive keypad.
■
Faults
Both
bUS [Option Communication Error]
and
EF0 [Option Card External Fault]
can appear as a fault. When a
fault occurs, the keypad ALM LED stays lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use these questions as a guide to help remove the fault:
•
Is the communication line properly connected to the option? Is it loose?
•
Is the option properly installed?
•
Is the host controller program working? Is the controller/host controller CPU stopped?
•
Did a momentary power loss interrupt communications?
Code
Name
Causes
Possible Solutions
bUS
Option Communication Error
The drive did not receive a signal from the
controller.
The communications cable wiring is incorrect.
•
Check for wiring errors.
•
Correct the wiring.
An existing short circuit or communications
disconnection
Check disconnected cables and short circuits and repair as needed
A data error occurred due to electric interference
•
Prevent noise in the control circuit, main circuit, and ground
wiring.
•
If you identify a magnetic contactor as a source of noise,
install a surge absorber to the contactor coil.
•
Use only recommended cables or other shielded line. Ground
the shield on the controller side or the drive input power side.
•
Separate all communication wiring from drive power lines.
Install an EMC noise filter to the drive power supply input.
•
Decrease the effects of electrical interference from the host
controller.
Option is damaged
If there are no problems with the wiring and the error continues to
occur, replace the option.
Connection Time-out
Check if the CPU of the controller is not stopped.
Duplicate IP Address found on network
Change to a different IP address. If
F7-13 = 0 [Address Mode at
Startup = Static]
, change parameters
F7-01 to F7-04 [IP Address
1 to 4]
.
EF0
Option Card External Fault
The option received an external fault from the
controller.
1.
Find the device that caused the external fault and remove the
cause.
2.
Clear the external fault input from the controller.
A programming error occurred on the controller
side.
Examine the operation of the controller program.
oFA00
Option Not Compatible with Port
The option connected to connector CN5-A is not
compatible.
Connect the option to the correct connector.
•
Use connector CN5-A when you connect the option.
To use other options, refer to those option manuals.
Invalid DIP switch S1 setting.
Set the option DIP switch S1 as shown in page
. Monitor,
U4-
75 [Communication OPT Protocol]
will display the DIP switch
S1 setting.