B.15 U: Monitors
Monitor parameters allow the user to view drive status, fault information, and other data concerning drive operation.
u
U1: Operation Status Monitors
No.
(Addr.
Hex)
Name
LCD Display
Description
Analog
Output Level
Unit
U1-01
(0040)
Frequency Reference
Frequency Ref
Monitors the frequency reference. Display units are determined
by o1-03.
10 V: Max
frequency
0.01 Hz
U1-02
(0041)
Output Frequency
Output Freq
Displays the output frequency. Display units are determined by
o1-03.
10 V: Max
frequency
0.01 Hz
U1-03
(0042)
Output Current
Output Current
Displays the output current.
10 V: Drive
rated current
U1-04
(0043)
Control Method
Control Method
0: V/f Control
2: OLV Control
No signal output
available
–
U1-05
(0044)
Motor Speed
Motor Speed
OLV
OLV
OLV
OLV
Displays the motor speed feedback. Display units are
determined by o1-03.
10 V: Max
frequency
0.01 Hz
U1-06
(0045)
Output Voltage
Reference
Output Voltage
Displays the output voltage.
0.1 Vac
U1-07
(0046)
DC Bus Voltage
DC Bus Voltage
Displays the DC bus voltage.
1 Vdc
U1-08
(0047)
Output Power
Output kWatts
Displays the output power (this value is calculated internally). 10 V: Drive
capacity
(motor capacity)
kW
U1-09
(0048)
Torque Reference
Torque Reference
OLV
OLV
OLV
OLV
Monitors the internal torque reference.
10 V: Motor
rated torque
0.1%
U1-10
(0049)
Input Terminal Status
Input Term Sts
Displays the input terminal status.
U1 - 10=
00000000
Digital input 1
(terminal S1 enabled)
Digital input 2
(terminal S2 enabled)
Digital input 3
(terminal S3 enabled)
Digital input 4
(terminal S4 enabled)
Digital input 5
(terminal S5 enabled)
Digital input 6
(terminal S6 enabled)
Digital input 7
(terminal S7 enabled)
Digital input 8
(terminal S8 enabled)
1
1
1
1
1
1
1
1
No signal output
available
–
U1-11
(004A) Output Terminal Status
Output Term Sts
Displays the output terminal status.
U1 - 11=
00000000
Multi-Function
Digital Output
(terminal M1-M2)
Digital Output
(terminal M3-M4)
Digital Output
Multi-Function
Multi-Function
Not Used
Fault Relay
(terminal MA-MC closed
MA-MC open)
1
1
1
1
0
(terminal MD-ME-MF)
No signal output
available
–
B.15 U: Monitors
326
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......