B.1 A: Initialization Parameters
Table B.1 Symbols and Icons Used in Parameter Descriptions
Symbol
Description
V/f
V/f
Parameter is ONLY available when operating the drive with V/f control.
OLV
OLV
OLV
OLV
Parameter is ONLY available when operating the drive with Open Loop Vector control.
Parameter can be changed during run.
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
u
A1: Initialization
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
A1-00
(0100)
Language Selection
Select Language
0: English
1:
(Japanese)
2: Deutsch
3: Fran
ç
ais
4: Italiano
5: Español
6: Portugu
ê
s
7:
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
Default: 0
Range: 0 to 7
–
A1-01
(0101)
Access Level Selection
Access Level
0: Operation Only
1: User Parameters
2: Advanced Level
0: View and set A1-01 and A1-04. U
o
-
oo
parameters can also
be viewed.
1: User Parameters (access to parameters selected by the user,
A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
3: Lock parameters
Default: 2
Range: 0 to 3
–
A1-03
(0103)
Initialize Parameters
Init Parameters
0: No Initialize
1110: User Initialize
2220: 2-Wire Initial
3330: 3-Wire Initial
5550: Term->Cntrl Int
6008: Pressure Control
6009: Pump down level
6010: Geothermal
mode
6011: VTC Pressure Ctl
7770: General purpose
0: No initialization
1110: User Initialize (parameter values must be stored using
parameter o2-03)
2220: 2-Wire initialization
3330: 3-Wire initialization
5550: Terminal->Control Initialize
6008: Pressure Control
6009: Pump down level
6010: Geothermal mode
6011: VTC pressure control
7770: General purpose
Default: 0
Range: 0 to 5550;
6008 to 6011;
7770
A1-04
(0104)
Password
Enter Password
When the value set into A1-04 does not match the value set into
A1-05, parameters A1-01 through A1-03 and A2-01 through A2-33
cannot be changed.
Default: 0000
Min.: 0000
Max.: 9999
–
A1-05
(0105)
Password Setting
Select Password
Default: 0000
Min.: 0000
Max.: 9999
–
A1-06
(0127)
Application Preset
Application Sel
0: General
8: Pressure Control
9: Pump Down Level
10: Geothermal Mode
11: VTC Pressure Ctl
0: General-purpose
8: Pressure control
9: Pump down level
10: Geothermal mode
11: VTC pressure control
Note:
This parameter is not settable. It is used as a
monitor only.
Default: 0
Range: 0; 8 to 11
–
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting value is dependent on the Initialization parameter A1-03.
B.1 A: Initialization Parameters
256
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......