No.
Parameter Name
Setting Range
Default
E2-01
Motor Rated Current
10% to 200% of the drive
rated current
Determined by
o2-04
Note:
1.
The number of decimal places in the parameter value depends on the drive model. This value has two decimal places (0.01 A) if the
drive is set for a maximum applicable motor capacity up to and including 11 kW, and one decimal place (0.1 A) if the maximum applicable
motor capacity is higher than 11 kW.
Refer to Power Ratings on page 234
for details.
2.
An oPE02 error will occur if the motor rated current in E2-01 is set lower than the motor no-load current in E2-03. Set E2-03 correctly
to prevent this error.
n
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will automatically
be saved to E2-04.
No.
Parameter Name
Setting Range
Default
E2-04
Number of Motor Poles
2 to 48
2
n
H1-01 to H1-08: Functions for Terminals S1 to S8
.
No.
Parameter Name
Setting
Range
Default
H1-01
Multi-Function Digital Input Terminal S1 Function Selection
1 to 9F
: Forward Run Command (2-Wire sequence)
H1-02
Multi-Function Digital Input Terminal S2 Function Selection
1 to 9F
F: Through Mode
H1-03
Multi-Function Digital Input Terminal S3 Function Selection
0 to 9F
26: External Pump Fault
H1-04
Multi-Function Digital Input Terminal S4 Function Selection
0 to 9F
14: Fault Reset
H1-05
Multi-Function Digital Input Terminal S5 Function Selection
0 to 9F
H1-06
Multi-Function Digital Input Terminal S6 Function Selection
0 to 9F
H1-07
Multi-Function Digital Input Terminal S7 Function Selection
0 to 9F
H1-08
Multi-Function Digital Input Terminal S8 Function Selection
0 to 9F
Table 4.20 Multi-Function Digital Input Terminal Settings
Setting
Function
Page
0
3-Wire sequence
–
3
Multi-Step Speed Reference 1
–
4
Multi-Step Speed Reference 2
–
5
Multi-Step Speed Reference 3
–
6
Jog reference selection
–
7
Accel/decel time selection 1
–
8
Baseblock command (N.O.)
–
9
Baseblock command (N.C.)
–
A
Accel/decel ramp hold
–
B
Drive overheat alarm (oH2)
–
C
Analog terminal input selection
–
F
Through mode
–
10
Up command
–
11
Down command
–
12
Forward Jog
–
13
Reverse Jog
–
14
Fault reset
–
15
Fast Stop (N.O.)
–
17
Fast Stop (N.C.)
–
18
Timer function input
–
19
PID disable
–
Setting
Function
Page
1A
Accel/decel time selection 2
–
1B
Program lockout
–
1E
Reference sample hold
–
20 to 2F Ext. pump fault
–
30
PID integral reset
–
31
PID integral hold
–
32
Multi-Step Speed
Reference 4
–
34
PID soft starter cancel
–
35
PID input level selection
–
40
Forward run command
(2-Wire sequence)
–
41
Reverse run command
(2-Wire sequence)
–
42
Run command
(2-Wire sequence 2)
–
43
FWD/REV command
(2-Wire sequence 2)
–
47
Node setup
–
51
Sequence Timer Disable
–
52
Sequence Timer Cancel
–
60
DC Injection Braking command
–
4.6 Basic iQpump Setup and Application Preset Parameters
158
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
Содержание iQpump1000
Страница 2: ...This Page Intentionally Blank 2 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 12: ...This Page Intentionally Blank 12 YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide...
Страница 353: ...This Page Intentionally Blank YASKAWA TOEP YAIP1W 01A YASKAWA AC Drive iQpump1000 Quick Start Guide 353...
Страница 355: ......