Technical Tip:
How to Connect and Troubleshoot Transducer Feedback
Product(s):
iQpump1000 and iQpump Micro Drives
Doc. No.
TN.iQp.03
TN.iQp.03 ©2015 - Yaskawa America, Inc.
Revision 1
July 8, 2015
Page 5 of 5
3. Verify the parameter
H3-09 Terminal A2 Signal Level Selection
is properly set according
to the signal type. Typically
2
for current feedback devices or
0
for voltage feedback
devices.
No.
Name
Description
Values
H3-09
Terminal A2 Signal
Level Selection
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Default: 2
Range: 0 to 3
4. Verify the proper Terminal A2 Function Selection (H3-10), typically ‘B’ for PID Feedback.
If terminal A2 is not chosen as the primary transducer feedback input,
H3-10 Terminal A2
Function Selection
must be disabled and terminal A1 or A3 must be configured for the
appropriate settings following steps 1-4.
How to Wire Multiple Transducers or use an External Transducer Power Supply
1. External power supply and multi-drive transducer wiring diagrams can be found in:
a.
iQpump1000:
Section 3.8 of the iQpump1000 Quick Start Guide
TOEPYAIP1W01.
Contact Yaskawa America, Inc. technical support at 800-YASKAWA (927-5292) if you have
any other questions regarding the Transducer Feedback Loss feature.
Table of Related Parameters
No.
Name
Description
Values
H3-09
Terminal A2 Signal
Level Selection
1: -10 to 10 V
2: 4 to 20 mA
3: 0 to 20 mA
Note: Use Jumper S1 to set input terminal A2 for a
current or voltage input signal.
Default: 2
Range: 0 to 3
H3-10 Terminal
A2
Function
Selection
Sets the function of terminal A2.
Default: B
Range: 0 to 32