Technical Tip: 

How to Connect and Troubleshoot Transducer Feedback 

Product(s):

  iQpump1000 and iQpump Micro Drives 

Doc. No. 

TN.iQp.03 

 

TN.iQp.03 ©2015 - Yaskawa America, Inc.  

Revision 1 

July 8, 2015 

Page 5 of 5 

 

3. Verify the parameter 

H3-09 Terminal A2 Signal Level Selection

 is properly set according 

to the signal type. Typically 

2

 for current feedback devices or 

0

 for voltage feedback 

devices. 

No. 

Name 

Description 

Values 

H3-09 

Terminal A2 Signal 
Level Selection 

0: 0 to 10 V 
1: -10 to 10 V 
2: 4 to 20 mA 
3: 0 to 20 mA 

Default: 2 
Range: 0 to 3 

4.  Verify the proper Terminal A2 Function Selection (H3-10), typically ‘B’ for PID Feedback. 

If terminal A2 is not chosen as the primary transducer feedback input, 

H3-10 Terminal A2 

Function Selection

 must  be disabled and terminal A1 or A3 must be configured for the 

appropriate settings following steps 1-4. 
 

How to Wire Multiple Transducers or use an External Transducer Power Supply

 

1.  External power supply and multi-drive transducer wiring diagrams can be found in: 

a. 

iQpump1000:

 Section 3.8 of the iQpump1000 Quick Start Guide 

TOEPYAIP1W01. 

Contact Yaskawa America, Inc. technical support at 800-YASKAWA (927-5292) if you have 
any other questions regarding the Transducer Feedback Loss feature. 

Table of Related Parameters 

No. 

Name 

Description 

Values 

H3-09 

Terminal A2 Signal 
Level Selection 

1: -10 to 10 V 
2: 4 to 20 mA 
3: 0 to 20 mA 
Note: Use Jumper S1 to set input terminal A2 for a 
current or voltage input signal. 

Default: 2 
Range: 0 to 3 

H3-10 Terminal 

A2 

Function 
Selection 

Sets the function of terminal A2. 

Default: B 
Range: 0 to 32 

 