10.6 MEMOBUS/Modbus Communications
744
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Calculation
Overflow
Description
Calculation
Overflow
XOR w A001 (Hex.)
1010 0000 0000 0001
-
XOR result
1000 0101 0000 0101
-
XOR result
1000 0100 1111 1110
-
Shift 7
0100 0010 1000 0010
1
Shift 7
0100 0010 0111 1111
0
XOR w A001 (Hex.)
1010 0000 0000 0001
-
Shift 8
0010 0001 0011 1111
1
XOR result
1110 0010 1000 0011
-
XOR w A001 (Hex.)
1010 0000 0000 0001
-
Shift 8
0111 0001 0100 0001
1
XOR result
1000 0001 0011 1110
-
XOR w A001 (Hex.)
1010 0000 0000 0001
-
Perform operations with next data (function code)
XOR result
1101 0001 0100 0000
-
CRC-16
1101 0001 0100 0000
-
D 1 4 0
(Lower) (Upper)
-
Continue from here with next data.
Response Data
The drive does the CRC-16 calculation for the response message and makes sure that the data does not have errors.
Make sure that the calculated value is the same value as the CRC-16 in the response message.
◆
Examples of Messages for Commands/Responses
The items in this section are examples of messages for commands/responses.
■
Read Multiple Holding Registers
Uses function code 03 (Hex.) to read the contents of a maximum of 16 holding registers.
shows example messages when the drive reads status signal from the drive of slave 2, the error contents,
fault contents, and frequency references.
Table 10.23 Message Example When Reading the Contents of Holding Register
Byte
Command Message
Setting Data
(Hex.)
Response Message (Normal)
Setting Data
(Hex.)
Response Message (Fault)
Setting Data
(Hex.)
0
Slave address
02
Slave address
02
Slave address
02
1
Function code
03
Function code
03
Function code
83
2
Starting No.
Upper
00
Data Qty
08
Error code
03
3
Lower
20
First storage
register
Upper
00
CRC-16
Upper
F1
4
Data Qty
Upper
00
Lower
65
Lower
31
5
Lower
04
Next storage
register
Upper
00
-
6
CRC-16
Upper
45
Lower
00
-
7
Lower
F0
Next storage
register
Upper
00
-
8
-
Lower
00
-
9
-
Next storage
register
Upper
01
-
10
-
Lower
F4
-
11
-
CRC-16
Upper
AF
-
12
-
Lower
82
-
■
Loopback Test
The loopback test uses function code 08 (Hex.) and returns the command message as a response message. This test
checks communication between the master and slave. The test code and data can use desired values.
shows examples of messages given out when the loopback test is done with the drive of slave 1.
Содержание HV600
Страница 2: ...This Page Intentionally Blank 2 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 30: ...1 2 Catalog Code and Nameplate Check 30 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 68: ...2 9 Knock Out Hole Dimensions 68 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 74: ...Page Intentionally Blank...
Страница 76: ...Page Intentionally Blank...
Страница 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 694: ...9 19 Defaults by Bypass and Drive Model 694 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 768: ...10 6 MEMOBUS Modbus Communications 768 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Страница 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...